  9. Omron E5CC User manual

Omron E5CC User manual

60 min.
45
45
+0.6
0
+0.6
0
+0.6
0
(48 x number of units - 2.5)+1
0
45
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
carefully before using the product.
E5CC
Digital Controller
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the
performance and functions of the product. Not doing so may occasionally result in unexpected events.
Use the product within specifications.
(1) The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product
in any of the following locations.
•Places directly subject to heat radiated from heating equipment.
•Places subject to splashing liquid or oil atmosphere.
•Places subject to direct sunlight.
•Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
•Places subject to intense temperature change.
•Places subject to icing and condensation.
•Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges. Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use the specified size of crimped terminals (M3, width 5.8 mm or less) for wiring. To connect bare wires to the
terminal block, use copper braided or solid wires with a gage of AWG24 to AWG18 (equal to cross- sectional
area of 0.205 to 0.8231 mm
2
). (The stripping length is 6 to 8 mm.) Up to two wires of same size and type, or
two crimped terminals can be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high- frequency
or surge. Separate the high-voltage or large-current power lines from other lines, and avoid parallel or
common wiring with the power lines when you are wiring to the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay
contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before
starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn
the controller ON.
(12) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within
easy reach of the operator, and must be marked as a disconnecting means for this unit.
(13) Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine, alcohol, or any
cleaners that contain these or other organic solvents. Deformation or discoloration may occur.
(14) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after
power ON.
(15) The output will turn OFF when you move to the Initial Setting Level. Take this into consideration when
performing control.
(16) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when
frequently overwriting data during communications or other operations.
(17) When disassembling the Temperature Controller for disposal, use suitable tools.
(18) Do not exceed the communications distance that is given in the specifications and use the specified
communications cable. Refer to the E5□C Digital Controllers User’s Manual (Cat. No.H174) for the
communications distance and cable specifications.
(19) Do not turn the power supply to the Digital Controller ON or OFF while the USB-Serial Conversion Cable is
connected. The Digital Controller may malfunction.
(20) The maximum terminal temperature is 75°C. Use wires with heat resistance of 75°C min to wire the terminals.
Precautions for Safe Use
Refer to the E5□C Digital Controllers User’s Manual (Cat. No. H174)
for detailed application procedures.
INSTRUCTION MANUAL
Thank you for purchasing the
OMRON E5CC Digital Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with
a knowledge of electrical systems.
•Before using the product, thoroughly read and understand
this manual to ensure correct use.
•Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
Refer to the E5□C Digital Controllers User’s Manual (Cat. No.
H174) for information on the Advanced Function Setting Level,
Manual Control Level, and other functions.
Refer to the E5□C Digital Controllers Communications Manual (Cat.
No. H175) for information on communications.
Power supply voltage 100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz / 24 VDC
Operating voltage range 85 to 110% of the rated voltage
Power consumption
Option 000: 5.2 VA max. (100 to 240 VAC)
3.1 VA max. (24 VAC)/1.6 W max. (24 VDC)
All other specifications: 6.5 VAmax. (100 to 240 VAC)
4.1 VA max. (24 VAC)/2.3 W max. (24 VDC)
Indication accuracy Thermocouple:
(Ambient temperature: 23°C) (±0.3 % of indication value or ±1°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input:
±0.2 % FS ±1 digit max.
Event input Output current: approx. 7 mA per contact.
Contact input ON:1 kΩ max., OFF: 100 kΩ min.
No-contact input ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Remote SP input 4 to 20 mA DC or 0 to 20 mADC
0 to 5 V DC or 1 to 5 V DC or 0 to 10 V DC
Control output 1 Relay output :SPST-NO
250VAC, 3A(resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR):
12 VDC ±20%, 21 mA
Current output: 4 to 20 mA DC, 0 to 20mADC
Load: 500Ω max.
Control output 2 Voltage output (for driving SSR):
12 VDC, 21 mA
Control method ON/OFF or 2-PID control
Auxiliary outputs Relay outputs:SPST-NO, 250 VAC,
two outputs: 3 A(resistive load),
three outputs: 2 A(resistive load),
Electrical life of relay: 100,000 operations
Transfer output 4 to 20 mA DC with load of 500 Ω max.
1 to 5 VDC with load of 1 kΩ min.
Ambient temperature -10 to 55°C
(Avoid freezing or condensation)
Ambient humidity 25% to 85%
Storage temperature -25 to 65°C
(Avoid freezing or condensation)
Altitude Max. 2,000m
Recommended fuse
T2A, 250 VAC, time-lag, low-breaking capacity
Weight Approx. 120 g (Digital Controller only)
Degree of protection Front panel: IP66
Rear case: IP20, Terminal section: IP00
Installation environment Installation categoryII, pollution
degree 2 (as per IEC61010-1)
Memory protection Non-volatile memory
(Number of write operations: 1,000,000)
Temporary overvoltage Short term: 1200 V+ (power supply voltage)
Long term: 250 V+ (power supply voltage)
CAUTION
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors,
cuttings from installation work, or moisture to enter the Digital Controller, the Setup Tool ports, or
between the pins on the connectors on the Setup Tool cable.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from
explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric
shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This is the product UL listed as OpenType Process Control Equipment. It must be mounted in an enclosure
that does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur.
Always consider the application conditions and use the output relays within their rated load and
electrical life expectancy. The life expectancy of output relays varies considerably with the output load
and switching conditions.
Loose screws may occasionally result in fire. Tighten the terminal screws to the specified torque of 0.43
to 0.58 N•m.
Set the parameters of the product so that they are suitable for the system being controlled. If they are
not suitable, unexpected operation may occasionally result in property damage or accidents.
Amalfunction in the Digital Controller may occasionally make control operations impossible or prevent
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital
Controller, take appropriate safety measures, such as installing a monitoring device on a separate line.
EN
Safety Precautions
Key to Warning Symbols
Dimensions
*2: Error shown only for "Process value / Set point". Not shown for other status.
When an error has occurred, the No.1 display shows the error code. Take necessary measure
according to the error code, referring the table below.
If the input value exceeds the display limit (-1999 to 9999), though it is within the control
range, [[[[ will be displayed under -1999 and ]]]] above 9999. Under these conditions,
control output and alarm output will operate normally.
Refer to the E5□C Digital Controllers User’s Manual (Cat. No. H174) for the controllable ranges.
Check the setting of the Input Type parameter,
check the input wiring, and check for broken or
shorts in the temperature sensor.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
repaired. If the display is restored to normal, then
a probable cause can be external noise affecting
the control system. Check for external noise.
After the correction of A/Dconverter error, turn the
power OFF then back ON again. If the display
remains the same, the controller must be repaired.
If the display is restored to normal, then a
probable cause can be external noise affecting the
control system. Check for external noise.
No.1 display Meaning
A/D converter error
*2
Memory error
Input error
*2
s.err (S. Err)
e111 (E111)
Action
OFF
Alarm
Control
output
Status at error
OFF
OFF
Operates
as above the
upper limit.
OFF
OFF
e333 (E333)
Error Display (troubleshooting)
Warning Symbols
Installation Connections (The applicability of the electric terminals varies with the type of machine.)
Specifications
Other functions
Wiring
Names of Parts on Front Panel
•°C / °F : temperature unit
The temperature unit is displayed when the displayed value
is a temperature. Either Cor Fis displayed according to
the set value of the temperature unit.
•
Mode key
Press this key to change the contents of the display.
Press this button for 1 s or longer for reverse scroll.
•Press the Okey and the Mkey together for at
least 3 seconds to switch to protect level.
•
Level key
Use this key to change levels:
•Shift key (PF key)
The default PF Setting parameter is for shifting the digit.
This is a function key. When it is pressed, the function
set for the PF Setting parameter will operate.
•:Protection indicator
Lit when Setting Change Protect is
ON (disables the Up and Down Keys).
• MANU: Manual output indicator
Lit when the Auto/Manual Mode is set
to Manual Mode.
Operation Menu
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to
provide for different types of alarm. These are indicated by the
letter "L" and "H".
• The default alarm type is "2"
Alarms
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIAPACIFIC PTE. LTD.
No. 438AAlexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which
apply to the combination of the Product in the Buyer’s application or use of the Product.
At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product, machine, system, or
other application or use. Buyer shall be solely responsible for determining appropriateness of the particular
product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in
all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALLEQUIPMENT OR SYSTEM.
Conformance to EN/IEC Standards
This is a class A product.
In residential areas it may cause radio interference, in which case the user
may be required to take adequate measures to reduce interference.
A 급 기기 (업무용 방송통신기자재)
이 기기는 업무용(A 급) 전자파적합기기로서 판매자또는 사용자는 이 점을
주의하시기 바라며, 가정외의지역에서 사용하는 것을 목적으로 합니다.
Operation stopped.
(Control/alarm are both stopped.) *5
Initial Setting Level
Use the following ranges for scaling: -1999
to 9999, -199.9 to 999.9, -19.99 to 99.99,
-1.999 to 9.999
Analog
input type
Current input
Voltage input
Do not connect anything to the terminals that are shaded gray.
Dimensions (mm)
The E5CC is set for a K thermocouple (input type of 5)
by default. If a different sensor is used, an input error
(s.err) will occur.
Check the setting of the Input Type parameter.
Check the wiring before turning ON the power supply.
*1
*1
*1
Alarm type
Vary with
"L", "H" values
Vary with
"L", "H" values
Vary with
"L", "H" values
No alarm function Output off
Deviation upper/lower limit
standby sequence ON
Absolute value upper limit
Absolute value lower limit
Absolute value upper limit
standby sequence ON
Absolute value lower limit
standby sequence ON
LBA (only for alarm 1)
Deviation lower limit
standby sequence ON
Deviation upper limit
standby sequence ON
Deviation upper/lower range
Deviation upper limit
Deviation upper/lower limit
Deviation lower limit
Alarm output function
Positive alarm value (X)
Negative alarm value (X)
Setting
PV Change Rate Alarm
X
ON
OFF SP
X
ON
OFF SP
ON
OFF SP
X
X
ON
OFF SP
L H
ON
OFF SP
X
ON
OFF SP
X
ON
OFF SP
X
ON
OFF 0
ON
OFF X
0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF X
0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF X
0
ON
OFF X
0
ON
OFF X
0
ON
OFF X
0
ON
OFF X
0
ON
OFF X
0
L H
ON
OFF SP
SP
ON
OFF X
ON
OFF X
0
1
0
2
3
4
5
6
7
8
9
SP absolute value upper limit
SP absolute value lower limit
14
15
MV absolute value upper limit
MV absolute value lower limit
16
17
RSP absolute value upper limit
RSP absolute value lower limit
18
19
10
11
12
13
SP
X
ON
OFF
ON
OFF X
0
Operation / Adjustment Protect
Restricts displaying and
modifying menu items in
Operation, Adjustment,
and Manual Control Levels.
oapt
0
Move to Protect Level
Displayed only when a
password is set. Restricts
moving to Protect Level.
pmov
0
Changed
Parameters Only
chgp
off
Parameter Mask
Enable
Displayed only
when a parameter
mask is set.
pmsk
on
Initial Setting / Communication Protect
Restricts movement to the
Initial Setting, Communications
Setting, and Advanced Function
Setting Levels.
icpt
1
Setting Change Protect
Restricts changes to settings
by operating the front panel keys.
wtpt
off
pfpt
off
PF Key Protect
Restricts PF key operation.
POWER ON
MV Monitor
(Heating)
*6 o
0.0
MV Monitor
(Cooling)
*6 c-o
0.0
Alarm Value
Lower Limit 1 *4
*6 al1l
0
Alarm Value 2 *4
*6 al-2
0
Alarm Value
Upper Limit 2 *4
*6 al2h
0
Alarm Value
Lower Limit 2 *4
*6 al2l
0
Alarm Value 3 *4
*6 al-3
0
Alarm Value
Upper Limit 3 *4
*6 al3h
0
Alarm Value
Lower Limit 3 *4
*6 al3l
0
Alarm Value
Lower Limit 4 *4
*6 al4l
0
Alarm Value 4 *4
*6 al-4
0
Alarm Value
Upper Limit 4 *4
*6 al4h
0
Input Type *3
Scaling Upper Limit
(only when setting
analog input)
Scaling Lower Limit
(only when setting
analog input)
Decimal Point
(only when setting
analog input)
Temperature
Unit
SP Upper Limit
SP Lower Limit
PID•ON/OFF
In ON/OFF control = onof
In 2-PID control = pid
Standard or Heating/Cooling
Standard control =
stnd
Heating and cooling control =
h-c
Control Period (Heating)
(Unit: Seconds)
*Voltage output (for driving SSR): 2
Alarm 1 Type:
Specified models only
Control Period (Cooling)
(Unit: Seconds)
*Voltage output (for driving SSR): 2
ST (Self-Tuning)
ST ON = on
ST OFF = off
Direct/Reverse Operation
In Reverse operation (Heating) =
or-r
In Direct operation (Cooling) = or-d
*3
*4
*6
*6
*6
*6
*6
*6
*6
*6
*6
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
onof
s-hc
stnd
st
on
Program Pattern
ptrn
off
cp
20
c-cp
20
orev
or-r
alt1
2
*6
Transfer
Output Type
*6 tr-t
off
Transfer Output
Upper Limit
*6 tr-h
100.0
Transfer Output
Lower Limit
*6 tr-l
0.0
Event Input
Assignment 1
*6 ev-1
msp0
Event Input
Assignment 2
*6 ev-2
stop
Event Input
Assignment 3
*6 ev-3
none
Event Input
Assignment 4
*6 ev-4
none
Extraction of Square
Root Enable
(Only when analog
input is set)
*6 sqr
off
Move to Advanced
Function Setting
Level
*6 amov
0
*6
Password to Move
to Protect Level
prlp
0
Alarm 1 Hysteresis
alh1
0.2
Alarm 2 Hysteresis
alh2
0.2
*6 Alarm 3
Type
alt3
2
Alarm 2 Type:
Specified models only
alt2
2
Adjustment Level
Displayed only once when
entering Adjustment Level.
*6
*8 l.adj
at
off
Heater Current 1 Value
Monitor (Unit: A) *7
*6 ct1
0.0
Communications Writing
*6 cmwt
off
SP Mode
*6 spmd
lsp
*6
Heater Burnout Detection 1
(Unit: A) *7
hb1
0.0
Heater Current 2 Value
Monitor (Unit: A) *7
*6 ct2
0.0
*6
Heater Burnout Detection 2
(Unit: A) *7
hb2
0.0
Soak Time
*6 soak
1
MV Upper Limit
*6 ol-h
100.0
Manual Reset Value
Clears the offset
during P or PD control.
*6 of-r
50.0
Wait Band
*6 wt-b
off
MV at Stop
*6 mv-s
0.0
MV at PV Error
*6 mv-e
0.0
SP Ramp Set Value
*6 sprt
off
SP Ramp Set Value
(SP Ramp Fall Value)
*6 sprl
same
Hysteresis (Cooling)
*6 chys
1.0
PV
Input Shift
*6 ins
0.0
PV input
Slope Coefficient
*6 inrt
1.000
Remote SP
Input Shift
*6 rss
0.0
Remote SP input
Slope Coefficient
*6 rsrt
1.000
Leakage Current 1 Value
Monitor (Unit: A) *7
*6 lcr1
0.0
Integral Time
(Unit: Seconds)
*6 i
233
Derivative Time
(Unit: Seconds)
*6 d
40 MV Lower Limit
*6 ol-l
0.0
MV Change
Rate Limit
*6 orl
0.0
Extraction of Square
Root Low-cut Point
*6 sqrp
0.0
Leakage Current 2 Value
Monitor (Unit: A) *7
*6 lcr2
0.0
HS Alarm 1
(Unit: A) *7
*6 hs1
50.0
HS Alarm 2
(Unit: A) *7
*6 hs2
50.0
SP 0
*6 sp-0
0
SP 1
*6 sp-1
0
SP 3
*6 sp-3
0
SP 4
*6 sp-4
0
SP 5
*6 sp-5
0
SP 6
*6 sp-6
0
SP 7
*6 sp-7
0
SP 2
*6 sp-2
0
25
0
Process Value/Set Point
s.err is displayed when
connected sensor is
different from input type.
AT Execute / Cancel
100%AT Execute at-2
40%AT Execute at-1
Dead Band
*6 c-db
0.0
Hysteresis (Heating)
*6 hys
1.0
*6
Alarm 3
Hysteresis
alh3
0.2
*6 Alarm 4
Type
alt4
2
*6
Control Output 1
Signal
o1st
4-20
*6 Transfer
Output Signal
trst
4-20
*6
Alarm 4
Hysteresis
alh4
0.2
Proportional
Band
*6 p
8.0
Integral Time
(Cooling)
(Unit: Seconds)
*6 c-i
233
Derivative Time
(Cooling)
(Unit: Seconds)
*6 c-d
40
Proportional Band
(Cooling)
*6 c-p
8.0
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V
25
26
27
28
29
Setting range
Input type Input
Pt100
JPt100
Thermocouple
Infrared
Thermosensor
ES1B
K
J
T
E
L
U
N
R
S
B
W
PL II
Setting
10 to 70°C
60 to 120°C
115 to 165°C
140 to 260°C
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
17
18 12
15
16
1
213
14
3
11
4
6
7
8
9
10
5
Operation indicators
•SUB1: Auxiliary output 1 indicator
•SUB2: Auxiliary output 2 indicator
• SUB3: Auxiliary output 3 indicator
•OUT1: Control output 1 indicator
• OUT2: Control output 2 indicator
6
4
5
65
6
Pt +
−
mA
−
+
5
4
*2 Sensor Temperature/Analog Input V
−5
V6
+
4
TC 4
I
(no polarity)
11
12
*4 Input Power Supply
11
12
100 to 240 VAC 24 VAC/DC
(64)
85
604
144.8×44.8 5. Options
1. Control outputs
10
7
8
9
*3 Auxiliary Outputs
Auxiliary outputs 1 and 2 Auxiliary outputs 1, 2, and 3
7
8
9
10
Auxiliary output 1
Auxiliary output 2 Auxiliary output 2
Auxiliary output 3
Auxiliary output 1
18
++
−
+
+
−
13
16
17
16
17
18
13
16
17
18
13
14
15
13
14
15
18
16
18
13
14
15
16
17
18
16
17
005
Event inputs 1 to 4
004
Communications (RS-485)
and event inputs 3 and 4
13
13
14
15
16
007
Event inputs 1 and 2,
and remote SP
006
Event inputs 1 and 2, and
transfer output
*5 Options
001
Event inputs 1 and 2,
and CT1
1717
18
V
IVmA
002
Communications
(RS-485) and CT1
003
Communications
(RS-485), CT1, and CT2
14
15 14
15 14
15
EV1
EV2 EV1
EV2
EV1
EV2
EV1
EV2
EV3
EV4 EV3
EV4
CT1 CT1
B(+)
A(−)
RS-485
B(+)
A(−)
RS-485
B(+)
A(−)
RS-485
CT2 COM
CT1
+−
3
1
2
3
1
2−
One linear
current output
One relay
output
3+Q
1+
2−
3
Two voltage outputs
(for driving SSR)
*1 Control Outputs 1 and 2
Q
1
2
One voltage output
(for driving SSR)
+
RX QX CX
Sold Separately
*Terminal cover (E53-COV23)
*USB-Serial Conversion Cable
(E58-CIFQ2)
In the pack:
*Main unit
*Instruction manual
*Watertight packing (Y92S-P8):

*Adapter (Y92F-49): 
*
Terminal cover (Provided only for
models with E5CC-
□□□□
5
□
):

* Do not remove the terminal block. Doing so may result in failure or malfunction.
* A Setup Tool port is provided on the upper of the product. Use this port to connect a personal computer to the product when using
the Setup Tool. E58-CIFQ2 USB-Serial Conversion Cable is required to connect the personal computer to the product. (Do not use
the product with the USB-Serial Conversion Cable left permanently connected.)
Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods.
•No.1 display
Process value or set data type
•No.2 display
Set point, set data read-out value or changed input
value
• Up and Down keys
Each press of Ukey increments or advances the
values displayed on the No.2 display.
Each press of Dkey decrements or returns the
values displayed on the No.2 display.
•RSP: Remote SP indicator
Lit when the assigned function is ON.
•TUNE:
Flashing during self-tuning.
Lit during auto-tuning.
•STOP: Control stopped indicator
Lit when “Run/Stop” is stopped during operation.
During control stop, functions other than control output
are valid.
•CMW: Communications writing
enabled/disabled indicator
Lit when communications writing is enabled and not lit
when it is disabled.
E5CC
QQ
Input Type
-200 to 850
-199.9 to 500.0
0.0 to 100.0
-199.9 to 500.0
0.0 to 100.0
-200 to 1300
-20.0 to 500.0
-100 to 850
-20.0 to 400.0
-200 to 400
-199.9 to 400.0
-200 to 600
-100 to 850
-200 to 400
-199.9 to 400.0
-200 to 1300
0 to 1700
0 to 1700
100 to 1800
0 to 2300
0 to 1300
0 to 90
0 to 120
0 to 165
0 to 260
-300 to 1500
-199.9 to 900.0
0.0 to 210.0
-199.9 to 900.0
0.0 to 210.0
-300 to 2300
0.0 to 900.0
-100 to 1500
0.0 to 750.0
-300 to 700
-199.9 to 700.0
-300 to 1100
-100 to 1500
-300 to 700
-199.9 to 700.0
-300 to 2300
0 to 3000
0 to 3000
300 to 3200
0 to 3200
0 to 2300
0 to 190
0 to 240
0 to 320
0 to 500
Platinum
resistance
thermometer
Temperature inputs
*The default is“5”.
*s.err will be displayed when a platinum resistance thermometer is mistakenly connected
while input type is not set for it. To clear the s.err display, correct the wiring and cycle the
power supply.
°C= c
°F= f
*3
*4
Initial setting level enables users to specify their preferred
operating conditions (input type, alarm type, control method, etc.)
*3: Refer to the adjoining tables for details of input types and alarm types.
*4: Applicable only to models with alarm functions.
*5: Operation is stopped when moved to the initial setting level.
(control/alarm are both stopped.)
*6: The grayed-out setting items are not displayed for some models and
some settings of other setting items.
*7: Applicable only to models with heater burnout functions.
*8: The four numeric digits of the product code are displayed in the No. 2
display. The setting cannot be changed and there is nothing that you
need to set.
Hold Odown
for at least
1 second
(No.1 display flashes,
then the control stops.)
Hold Odown
for at least
3 seconds
*3
*4
*3
*4
Operation Level
Set Point During
SP Ramp
*6 sp-m
0
Heater Current 1
Value Monitor
(Unit: A) *7
*6 ct1
0.0
Heater Current 2
Value Monitor
(Unit: A) *7
*6 ct2
0.0
Multi-SP
Set Point Selection
*6 m-sp
0
Remote SP Monitor
*6 rsp
0.0
Auto/Manual Switch
PID control only.
*6 a-m
Leakage Current 1
Value Monitor
(Unit: A) *7
*6 lcr1
0.0
Leakage Current 2
Value Monitor
(Unit: A) *7
*6 lcr2
0.0
Program Start
*6 prst
rset
Soak Time Remain
*6 sktr
0
RUN/STOP
*6 r-s
run
Alarm Value 1 *4
*6 al-1
0
Alarm Value Upper Limit 1
*4
*6 al1h
0
When control start =
run
When control stop =
stop
Operation level should normally be used during operations.
Hold Oand Mkeys
down for at least
1 second
Hold Oand Mkeys
down for at least
3 seconds
Protect Level
Restricts which settings can be displayed or changed, and
restricts change by key operation.
Press O
(less than
1 second)
Adjustment Level
Only the value set to the ins: Temperature Input Shift parameter is applied to the entire temperature input range.
When the process value is 200°C, the process value is treated as 201.2°C after input shift if the input shift value
is set to 1.2°C. The process value is treated as 198.8°C after input shift if the input shift value is set to -1.2°C.
Adjustment level is for entering set values and shift values for control.
5377443-6A
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
* When complying with EMC standards, the line connecting the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
Individual mounting (mm) Side-by-side mounting (mm)
• Insert the main unit through the mounting hole in the panel (1 to 5 mm thickness). Insert the
mounting brackets (supplied) into the fixing slots located on the top and bottom of the rear
case.
• Tighten the two mounting screws on the top and bottom of the adapter to keep them
balanced, and finally tighten them to a torque of between 0.29 and 0.39 N·m.
• When more than one machine is installed, make sure that the ambient temperature does
not exceed the specified limit.
Waterproofing is impossible
with side-by-side
installation. When
waterproofing is required, fit
watertight packing on the
backside of front panel.
°C °F
CC1
CQR
48×48

Solderless terminal size
M3
OUT1 OUT1 OUT1 OUT1
OUT2
A
B
B
L H
ON
OFF
SP
Communications
Monitor
*6 plcm
1234
M
Control output 1
Voltage output (for driving SSR)
12 VDC, 21 mA
Control output 2
Relay output
250 VAC, 3 A (resistive load)
Voltage output (for driving SSR)
12 VDC, 21 mA
Current output
0 to 20 mA DC
Load: 500 Ω max.
4 to 20 mA DC
Relay outputs
two outputs 250 VAC: 3 A
(resistive load)
three outputs 250 VAC: 2 A
(resistive load)
Auxiliary outputs 1, 2, and 3
3+
1+
2-
Linear current output/
voltage output (for driving SSR)
OUT1
C
OUT2
Q
CQ
Conformance to Safety Standard
Reinforced insulation is provided between input power
supply, relay outputs, and between other terminals.
Always externally connect the recommended fuse that is specified
in the Instruction Manual before you use the Digital Controller.
Analog Input
•
If you input an analog voltage or current, set the Input Type
parameter to the correct input type.
•Do not use the Digital Controller to measure a circuit with
Measurement Category II, III, or IV.
•
Do not use the Digital Controller to measure an energized circuit to
which a voltage that exceeds 30 Vms or 60 VDC is applied.
The protection provided by the Digital Controller may be impaired if the
Digital Controller is used in a manner that is not specified by the
manufacturer.
Due to UL Listing requirements, use the E54-CT1Lor E54-CT3L
current transformer with the factory wiring (internal wiring).
Use a UL category XOBAor XOBA7 current transformer that is UL
Listed for field wiring (external wiring) and not the factory wiring
(internal wiring).
Check for a single-fault condition of the COM t
erminal before use if auxiliary outputs 1,2 and 3
will be connected to different electrical potentials.
* Use non-voltage inputs for the event inputs. The polarity for a non-contact input is indicated by “(-).”
(−)(−)(−)
(−)
(−)
(−)
●接続(機種によって端子の用途は異なります。) グレー表示の端子へは接続しないでください。
■配線
■操作メニュー
●取り付け
●外形寸法図
・外形寸法(単位mm)
60以上
45
45
+0.6
 0
+0.6
 0
+0.6
 0
(48×台数-2.5) +1
 0
45
個別取り付けのとき(単位mm) 密着取り付けのとき(単位mm)
正しい取扱いをしなければ、この危険のために、時に軽
傷・中程度の傷害をおったり、あるいは物的損害を受け
る恐れがあります。お使いになる前にこの取扱説明書を
お読みになり、十分にご理解ください。
注意
●フロント部の名称
形 E5CC
デジタル調節計
製品の動作不良、誤動作または性能・機能への悪影響を防ぐため、以下のことを守ってください。不具合事象が稀に
起こることがあります。仕様外の取扱いはしないでください。
(1)屋内専用機器のため屋内のみで使用してください。ただし、下記の環境では使用、または保管はしないでください。
・加熱機器から輻射熱を直接受けるところ ・水がかかるところ、被油のあるところ
・直射日光が当たるところ ・温度変化の激しいところ
・氷結、結露の恐れのあるところ ・振動、衝撃の影響が大きいところ
・塵あい、腐食性ガス(とくに硫化ガス、アンモニアガスなど)のあるところ
(2)周囲温度および湿度は仕様範囲内で使用および保存してください。必要により、強制冷却してください。
(3)放熱を妨げないよう、デジタル調節計の周辺をふさがないでください。デジタル調節計本体の通風孔はふさがな
いでください。
(4)端子の極性を確認し、正しく配線してください。
(5)配線用圧着端子は、指定サイズ(M3、幅5.8mm以下)のものをご使用ください。
裸線接続の配線材は、銅製でAWG24(断面積0.205mm2)-AWG18(断面積0.8231mm2)のより線か、単線を使用して
ください。(電線被覆剥きしろ:6~8mm)
1端子への配線は同じサイズ、同じ種類の線で2本まで、圧着端子は2枚までの接続としてください。
(6)使用しない端子には何も接続しないでください。
(7)強い高周波を発生する機器やサージを発生する機器から、できるだけ離して設置してください。配線は、高電圧、
大電流の動力線とは分離して配線してください。また、動力線との平行配線や同一配線を避けてください。
(8)電源電圧および負荷は、仕様、定格の範囲内でご使用ください。
(9)電源電圧は2秒以内に定格電圧に達するようにスイッチ、リレーなどの接点を介して一気に印加してください。
徐々に電圧を印加しますと、電源リセットしなかったり出力の誤動作が発生することがあります。
(10)デジタル調節計に電源を投入してから、正しい温度を表示するまで30分かかります。(実際に制御を始めるこの
時間前に電源を投入してください)
(11)セルフチューニングを使用される場合は、デジタル調節計と負荷の電源を同時、あるいは負荷の電源を先に投入
してください。
(12)作業者がすぐ電源をOFFできるようスイッチまたはサーキットブレーカを設置し、適切に表示してください。
(13)本製品の汚れはやわらかい布で乾拭きしてください。なお、シンナー、ベンジン、アルコールなどの溶剤を含む薬
品等を使用しないでください。変形、変色の恐れがあります。
(14)電源を投入して、デジタル調節計の出力が確定するまで2秒かかります。この時間を考慮して(制御盤などの)設
計してください。
(15)初期設定レベルへ移行すると出力がOFFになりますので、これを考慮した制御をしてください。
(16)不揮発性メモリには書き込み回数に寿命があります。通信などでデータを頻繁に書き換える場合はRAMモードで
使用してください。
(17)廃棄時に分別するとき、工具を使用してください。
(18)通信距離については仕様範囲内で、通信線は指定のケーブルをご使用ください。
なお、通信距離仕様、ケーブルについては、「形E5□C ユーザーズマニュアル」(カタログ番号:SGTD-
740)をご参照ください。
(19)USB-シリアル変換ケーブルをデジタル調節計に接続した状態で、デジタル調節計本体の電源を投入または切断
しないでください。デジタル調節計の誤動作の原因となります。
(20)最大端子温度は75℃ですのでご注意ください。 配線は耐熱仕様75℃以上の電線を使用してください。
安全上の要点
●警告表示の意味
取扱説明書
このたびは、オムロン製品をお買い上げいただきまして、まことにあり
がとうございます。この取扱説明書では、この製品を使用する上で、
必要な機能、性能、使用方法などの情報を記載しています。
この製品をご使用に際して下記のことを守ってください。
・この製品は電気の知識を有する専門家が扱ってください。
・この取扱説明書をよくお読みになり、十分にご理解のうえ、正しくご
使用ください。
・この取扱説明書はいつでも参照できるよう大切に保管ください。
©All Rights Reserved
■その他の機能
「高機能設定レベル」および「マニュアル制御レベル」やその他、
詳細は「形E5□C ユーザーズマニュアル」(カタログ番号:
SGTD-740)を参照してください。
通信については、「形E5□C 通信マニュアル」(カタログ番号:
SGTD-741)を参照してください。
梱包内容
・本体
・取扱説明書
・防水パッキン(形Y92S-P8):①
・アダプタ(形Y92F-49):②
・端子カバー(形E5CC-□□□□5□タイプのみに付属):③
●仕様
電源電圧 AC100-240V 50/60Hz
またはAC24V 50/60Hz/DC24V
許容電圧変動範囲 定格電圧の85~110%
消費電力 オプション000は、5.2VA以下(AC100-240V)
3.1VA以下(AC24V)/ 1.6W以下(DC24V)
上記以外の仕様は、6.5VA以下(AC100-240V)
4.1VA以下(AC24V)/ 2.3W以下(DC24V)
指示精度 熱電対:(指示値の±0.3%または±1℃の大きい方)
(周囲温度:23℃) ±1ディジット以下
白金測温抵抗体:(指示値の±0.2%または±0.8℃
の大きい方)±1ディジット以下
アナログ入力±0.2%FS±1ディジット以下
イベント入力 流出電流:約7mA(1接点あたり)
  有接点 ON:1kΩ以下、OFF:100kΩ以上
  無接点 ON:残留電圧1.5V以下、OFF:漏れ電流0.1mA以下
リモートSP入力 DC4-20mA/DC0-20mA
DC0-5V/DC1-5V/DC0-10V
制御出力1 リレー出力 AC250V 3A (抵抗負荷)
リレーの電気的寿命 10万回
電圧出力(SSR駆動用)DC12V±20%、21mA
電流出力 DC4-20mA/DC0-20mA、負荷500Ω以下
制御出力2 電圧出力(SSR駆動用)DC12V 21mA
制御方式 2自由度PIDまたはON/OFF
補助出力 リレー出力AC250V、2出力 3A(抵抗負荷)、
3出力 2A(抵抗負荷)
リレーの電気的寿命 10万回
伝送出力 DC4-20mA 負荷500Ω以下
DC1-5V 負荷1kΩ以上
使用周囲温度 -10~55℃(ただし、氷結、結露しないこと)
使用周囲湿度 25~85%RH
保存温度 -25~65℃(ただし、氷結、結露しないこと)
高度 2,000m以下
推奨ヒューズ T2A、AC250V タイムラグ低遮断容量
質量 約120g(本体のみ)
保護構造 前面:IP66、リアケ-ス:IP20、端子部:IP00
設置環境 設置カテゴリⅡ、汚染度2(IEC61010-1による)
メモリ保護 不揮発性メモリ(書込み回数:100万回)
一時過電圧 短時間過電圧 1200V+(電源電圧)
長時間過電圧 250V+(電源電圧)
詳細な使用方法は別冊「形E5□C ユーザーズマニュアル
」(カタ
ログ番号
:
SGTD-740
)を参照してください。
*3:入力種別と警報種別の項目は、左の表を参照してください。
*4:警報機能がある機種だけ機能します。
*5:初期設定レベルへ移行すると運転が停止します。(制御・ 警報共
に停止)
*6:
グレー表示になっている設定項目は機種や設定内容により表示されな
い場合があります。
*7:
ヒータ断線機能がある機種だけ機能します。
*8:
第2表示には、商品コードの数字部4桁が表示されます。設定変更がで
きませんが、お客様に何か設定していただく必要はございません。
注意
JPN
●警告表示
*端子台の取り外しは故障や誤動作の原因となりますので行わないでください。
*製品上面部に設定ツールを使用する際、パソコンとデジタル調節計を接続するために使用する設定ツール用ポートを標準搭載しています。
接続には専用のUSB-シリアル変換ケーブル(形E58-CIFQ2)が必要です。(常時接続状態での使用はできません。)
詳細な接続方法は、USB-シリアル変換ケーブルに付属の取扱説明書を参照ください。
入力が制御可能範囲内で表示可能範囲
(-1999~9999)
を超えた場合、
-1999
より小さい値は
[[[[、
9999
より大きい値は ]]]]
と表示します。
この表示のときは制御出力および警報出力ともに正常に動作します。
制御可能範囲についての詳細は
「形E5□C ユーザーズマニュアル」(カタログ番号:SGTD-740)
を参照し
てください。
*2:
表示が「現在値/目標値」のときだけエラー表示します。他の状態ではエラー表示しません。
●異常時の表示について(トラブルシューティング)
異常が発生すると、第1表示にエラー内容を表示します。エラー表示によってエラー
の内容を確認し、その内容についての処置をしてください。
OFF
異常高温と
して処理
●警報種別
*2
*2
メモリ異常
入力異常
s.err(S.Err)
e111(E111)
A/Dコンバータ
異常
異常時の出力状態
制御出力 警報出力
OFF
OFF
OFF
OFF
e333(E333)
第1表示 異常内容 処置
入力種別の設定を確認、あるいは入力の誤配線、
測温体の断線・短絡を確認してください。
入力異常を確認後、電源を入れ直してください。
表示内容が変わらない場合は修理が必要です。
正常になった場合はノイズの影響が考えられるので、
ノイズが発生していないか確認してください。
電源を入れ直してください。
表示内容が変わらない場合は修理が必要です。
正常になった場合はノイズの影響が考えられるので、
ノイズが発生していないか確認してください。
電圧出力(SSR駆動用)
DC12V 21mA
制御出力2
安全上のご注意
ご購入時、入力種別は「5」熱電対(K)に設定されてい
ます。センサが異なる場合は、入力異常(s.err)が発
生することがあります。入力種別を確認してください。
電源投入する前に配線を確認してください。
・初期値は「5」です。
・測温抵抗体以外の設定値で、誤って測温抵抗体を接続したときはs.errを表示
します。s.errを解除するには配線を見直し、電源を入れ直してください。
*1
*1
*1
警報種別
L,Hの値による
L,Hの値による
L,Hの値による
警報機能なし 出力
OFF
上下限待機シーケンス付
絶対値上限
絶対値下限
絶対値上限待機シーケンス付
絶対値下限待機シーケンス付
LBA
(警報1種別のみ)
下限待機シーケンス付
上限待機シーケンス付
上下限範囲
上限
上下限
下限
警報出力機能
警報値(X)が正 警報値(X)が負
設定値
PV変化率警報
X
ON
OFF SP
X
ON
OFF SP
ON
OFF SP
X
X
ON
OFF SP
LH
ON
OFF SP
X
ON
OFF SP
X
ON
OFF SP
X
ON
OFF 0
ON
OFF
X
0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF
X
0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
LH
ON
OFF SP
LH
ON
OFF
SP
SP
ON
OFF
X
ON
OFF
X
0
1
0
2
3
4
5
6
7
8
9
SP絶対値上限
SP絶対値下限
14
15
MV絶対値上限
MV絶対値下限
16
17
RSP絶対値上限
RSP絶対値下限
18
19
10
11
12
13
*1:設定値1、4、5は警報の上・下限値が個別に設定でき、L,Hで表してい
ます。
  ・初期値は「2」です。
SP
X
ON
OFF
ON
OFF
X
0
制御出力1
電流出力
 DC0-20mA
 DC4-20mA
 負荷500Ω以下
電圧出力(SSR駆動用)
 DC12V 21mA
リレー出力
 AC250V 3A (抵抗負荷)
リレー出力
 2出力 AC250V 3A
 (抵抗負荷)
 3出力 AC250V 2A
 (抵抗負荷)
補助出力1,2,3
Oキー
3秒以上
(表示が点滅し制御
 が停止します。)
●初期設定レベル
運転が停止します。 (制御・警報共に停止)
*5
Oキー
1秒以上
●調整レベル
調整レベルは、制御を行うための設
定値や補正値を入力するレベルです。
キー操作による設定変更やレベルの移行を制限します。
運転/調整プロテクト
運転・調整・マニュアル制御
レベルのメニュー表示、書込
み等を制限
oapt
0
プロテクトレベル移行
パスワード設定時のみ表示
プロテクトレベルへの移行を
制限
pmov
0
変更パラメータ
表示
chgp
off
パラメータマスク
有効
パラメータマスク
設定時のみ
pmsk
on
初期/通信プロテクト
初期設定・通信設定・高機能
設定レベルへの移行を制限
icpt
1
設定変更プロテクト
キー操作による設定変更を
制限
wtpt
off
pfpt
off
PFキープロテクト
PFキー操作を制限
電源投入
●運転レベル
運転中は通常、運転レベルでご使用ください。
ランプ目標値モニタ
*6 sp-m
0
ヒータ電流値2モニタ
(単位:A) *7
*6 ct2
0.0
リモートSPモニタ
*6 rsp
0.0
オート/マニュアル切替
PID制御のみ
*6 a-m
漏れ電流値1モニタ
(単位:A) *7
*6 lcr1
0.0
漏れ電流値2モニタ
(単位:A) *7
*6 lcr2
0.0
操作量モニタ
(加熱) 
*6 o
0.0
操作量モニタ
(冷却) 
*6 c-o
0.0
プログラムスタート
*6 prst
rset
ソーク残り時間モニタ
*6 sktr
0
制御開始の時 run
制御停止の時 stop
ラン/ストップ
*6 r-s
run
警報値1*4
*6 al-1
0
警報上限値1*4
*6 al1h
0
警報下限値1*4
*6 al1l
0
警報値2*4
*6 al-2
0
警報上限値2*4
*6 al2h
0
警報下限値2*4
*6 al2l
0
警報値3*4
*6 al-3
0
警報上限値3*4
*6 al3h
0
警報下限値3*4
*6 al3l
0
警報下限値4*4
*6 al4l
0
警報値4*4
*6 al-4
0
警報上限値4*4
*6 al4h
0
入力種別*3
スケーリング上限値
(アナログ入力設定時のみ)
スケーリング下限値
(アナログ入力設定時のみ)
小数点位置
(アナログ入力設定時のみ)
温度単位
目標値リミット上限値
目標値リミット下限値
PID・ON/OFF
ON/OFF制御の時 onof
2自由度PID制御の時 pid
標準/加熱冷却
標準制御の時 stnd
加熱冷却制御の時 h-c
制御周期(加熱)
(単位:秒)
※電圧出力(SSR駆動用)は2
警報1種別
制御周期(冷却)
(単位:秒)
※電圧出力(SSR駆動用)は2
℃の時 c
。
Fの時 f
ST
(セルフチューニング)
ST
ONの時     
on
ST
OFFの時    
off
正/逆動作
逆動作(加熱制御)の時
or-r
正動作(冷却制御)の時
or-d
*3
*4
初期設定レベルでは、入力種別、警報種別、制御方式などのお客様の
ご使用条件を設定します。
*6
*6
*6
*6
*6
*6
*6
*6
*6
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
onof
s-hc
stnd
st
on
プログラムパターン
ptrn
off
cp
20
c-cp
20
orev
or-r
alt1
2
*6
伝送出力種別
*6 tr-t
off
伝送出力上限値
*6 tr-h
100.0
伝送出力下限値
*6 tr-l
0.0
イベント入力
割付1
*6 ev-1
msp0
イベント入力
割付2
*6 ev-2
stop
イベント入力
割付3
*6 ev-3
none
イベント入力
割付4
*6 ev-4
none
開平演算有効
(アナログ入力
設定時のみ)
*6 sqr
off
高機能設定
レベル移行
*6 amov
0
*6
●プロテクトレベル
 O+Mキー
3秒以上
 O+Mキー
1秒以上
プロテクトレベル
移行パスワード
prlp
0
警報1ヒステリシス
alh1
0.2
警報2ヒステリシス
alh2
0.2
*6 警報3種別 *3
*4
alt3
2
警報2種別 *3
*4
alt2
2
調整レベル表示
調整レベル移行時に
1回のみ表示
*6
*8 l.adj
at
off
ヒータ電流値1モニタ
(単位:A) *7
*6 ct1
0.0
通信書込
*6 cmwt
off
SPモード
*6 spmd
lsp
*6 ヒータ断検出1
(単位:A) *7
hb1
0.0
ヒータ電流値2モニタ
(単位:A) *7
*6 ct2
0.0
*6 ヒータ断検出2
(単位:A) *7
hb2
0.0
ソーク時間
*6 soak
1
操作量リミット上限値
*6 ol-h
100.0
ウェイト幅
*6 wt-b
off
ストップ時操作量
*6 mv-s
0.0
異常時操作量
*6 mv-e
0.0
SPランプ設定値
*6 sprt
off
SPランプ設定値
(下降値)
*6 sprl
same
調節感度(冷却)
*6 chys
1.0
PV入力補正値
*6 ins
0.0
PV入力傾き
補正係数
*6 inrt
1.000
リモートSP入力
補正値
*6 rss
0.0
リモートSP入力
傾き補正係数
*6 rsrt
1.000
漏れ電流値1モニタ
(単位:A) *7
*6 lcr1
0.0
積分時間
(単位:秒)
*6 i
233
微分時間
(単位:秒)
*6 d
40
操作量リミット下限値
*6 ol-l
0.0
操作量変化率リミット
*6 orl
0.0
開平演算ローカット点
*6 sqrp
0.0
「ins」PV入力補正値の設定値分だけ、センサ入力範囲のすべての点において入力温
度を補正します。補正前の現在値が200℃のとき、補正値を1.2℃とすると補正後は
201.2℃、補正値を-1.2℃とすると補正後は198.8℃として扱います。
漏れ電流値2モニタ
(単位:A) *7
*6 lcr2
0.0
SSR故障検出1
(単位:A) *7
*6 hs1
50.0
SSR故障検出2
(単位:A) *7
*6 hs2
50.0
目標値0
*6 sp-0
0
目標値1
*6 sp-1
0
目標値4
*6 sp-4
0
目標値5
*6 sp-5
0
目標値6
*6 sp-6
0
目標値7
*6 sp-7
0
目標値2
*6 sp-2
0
25
0
現在値/目標値
接続したセンサと入力種
別が異なる場合、s.err
AT実行/中止
100%AT実行の時
at-2
40%AT実行の時
at-1
調節感度(加熱)
*6 hys
1.0
*6
警報3ヒステリシス
alh3
0.2
*6 警報4種別 *3
*4
alt4
2
*6 制御出力1
信号種別
o1st
4-20
*6 伝送出力
信号種別
trst
4-20
*6
警報4ヒステリシス
alh4
0.2
比例帯
*6 p
8.0
積分時間(冷却)
(単位:秒)
*6 c-i
233
微分時間(冷却)
(単位:秒)
*6 c-d
40
比例帯(冷却)
*6 c-p
8.0
M
M
M
MM
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
デッドバンド
*6 c-db
0.0
M
マニュアルリセット値
P、PD制御時
オフセットをクリア
*6 of-r
50.0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
目標値3
*6 sp-3
0
M
M
M
M
M
M
M
M
M
M
M
M
M
マルチSP
目標値の選択
*6 m-sp
0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
25
0
M
M
M
M
M
M
M
M
M
M
M
ヒータ電流値1モニタ
(単位:A) *7
*6 ct1
0.0
M
M M
M
M
M
M
M
M
Oキー
1秒未満
①②③
入力電源-リレー出力-その他の端子相互間は強化絶縁さ
れていることを示します。
安全規格対応について
取扱説明書記載の推奨ヒューズを必ず外部に取り付けて使用してください。
製造者が指定しない方法で機器を使用すると、機器が備える保護を損なう
場合があります。
UL認証上、形E54-CT1Lまたは形E54-CT3LのCTは、
工場配線(盤内配線)で使用してください。工場配線(盤内配線)
ではなく現場配線(盤外配線)ではULカテゴリ:XOBAまたはXOBA7
でリスティング認証を受けたCTを使用してください。
アナログ入力に関して
・電圧または電流を入力する場合、入力種別に合わせて入力タイプを設定し
てください。
・ 計測カテゴリⅡ、Ⅲ、Ⅳに該当する回路の測定には使用しないでください。
・ 30Vrmsまたは60VDCを超える電圧が印加された対象の測定には使用し
ないでください。
●製品に関するお問い合わせ先
お客様相談室
インダストリアルオートメーションビジネスカンパニー 
●その他のお問い合わせ
 
納期・価格・サンプル・仕様書は貴社のお取引先、または貴社担当オムロン販売員にご相談ください。
オムロン制御機器販売店やオムロン販売拠点は、Webページでご案内しています。
●FAXやWebページでもお問い合わせいただけます。
FAX055-982-5051/www.fa.omron.co.jp
クイック オムロン
0120-919-066
携帯電話・PHS・IP電話などではご利用いただけませんので、下記の電話番号へおかけください。
電話055-982-5015
(通話料がかかります)
■営業時間:8:00〜21:00
■営業日:365日
ご承諾事項
当社商品は、一般工業製品向けの汎用品として設計製造されています。従いまして、次に掲げる用途での使用を意図して
お
らず、お客様が当社商品をこれらの用途に使用される際には、当社は当社商品に対して一切保証をいたしませ
ん。ただし、次に掲げる用途であっても当社の意図した商品用途の場合や特別の合意がある場合は除きます。
a) 高い安全性が必要とされる用途(例:原子力制御設備、燃焼設備、航空・宇宙設備、鉄道設備、昇降設備、娯
楽設備、医用機器、安全装置、その他生命・身体に危険が及びうる用途)
b) 高い信頼性が必要な用途(例:ガス・水道・電気等の供給システム、24時間連続運転システム、決済システム
ほか権利・財産を取扱う用途など)
c) 厳しい条件または環境での用途(例:屋外に設置する設備、化学的汚染を被る設備、電磁的妨害を被る設備、
振動・衝撃を受ける設備など)
d) カタログ等に記載のない条件や環境での用途
* (a)から(d)に記載されている他、本カタログ等記載の商品は自動車(二輪車含む。以下同じ)向けではありません。自動車に搭載する用途
には利用しないで下さい。自動車搭載用商品については当社営業担当者にご相談ください。
* 上記は適合用途の条件の一部です。当社のベスト、総合カタログ、データシート等最新版のカタログ、マニュアルに記載の保証・免責事項の
内容をよく読んでご使用ください。
異なる電位を補助出力1、2、3に接続する
場合、COM端子の単一故障状態をご確認
の上、ご使用ください。
EMC規格適合上、センサの長さは、30m以内
で使用してください。30mを超えて使用される
場合はEMC規格適合外となりますのでご注意く
ださい。
通信モニタ
*6 plcm
1234
M
・取り付けは、本体をパネル(厚さ1~5mm)角穴へ入れ、付属のアダプタをリアケースの上面およ
び下面の固定溝にはめ込んでください。
・上下の取付金具のネジを、交互に少しずつバランスをとりながら、トルク0.29~0.39N・mで締め付
けてください。
・複数個を取り付けて使用される場合、本機の周囲温度が仕様を超えないようにご注意ください。
防水になるように取り付ける
には、本体に防水パッキンを
挿入してください。
密着取付時は防水ができま
せん。
別売品
・端子カバー(形E53-COV23)
・USB-シリアル変換ケーブル
 (形E58-CIFQ2)
電流入力
電圧入力
ア ナ ロ グ入力
4~20mA
0~20mA
1~5V
0~5V
0~10V
℃
-200~850
-199.9~500.0
0.0~100.0
-199.9~500.0
0.0~100.0
-200~1300
-20.0~500.0
-100~850
-20.0~400.0
-200~400
-199.9~400.0
-200~600
-100~850
-200~400
-199.9~400.0
-200~1300
0~1700
0~1700
100~1800
0~2300
0~1300
0~90
0~120
0~165
0~260
設定範囲
入力種別
測温抵抗体
仕様
Pt100
JPt100
熱電対
非接触
温度センサ
形ES1B
K
J
T
E
L
U
N
R
S
B
W
PLⅡ
温度入力
設定値
10~70℃
60~120℃
115~165℃
140~260℃
スケーリングにより-1999~9999、
-199.9~999.9、-19.99~99.99、
-1.999~9.999の範囲で使用。
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
°F
-300~1500
-199.9~900.0
0.0~210.0
-199.9~900.0
0.0~210.0
-300~2300
0.0~900.0
-100~1500
0.0~750.0
-300~700
-199.9~700.0
ー300~1100
-100~1500
-300~700
-199.9~700.0
-300~2300
0~3000
0~3000
300~3200
0~3200
0~2300
0~190
0~240
0~320
0~500
感電により軽度の傷害が稀に起こる恐れがあります。
通電中は端子に触らないでください。
軽度の感電、発火、機器の故障が稀に起こる恐れがあります。製品の内部や設定ツール用ポート内部、
設定ツール用ケーブルのコネクタ部のピン間に金属、導線、取り付け加工中の切粉、または水分などが
入らないようにしてください。
爆発により稀に軽度の傷害の恐れがあります。
引火性、爆発性ガスのある所では使用しないでください。
軽度の感電、発火、機器の故障が稀に起こる恐れがあります。
分解、改造、修理したり、内部に触らないでください。
注意 火災や感電の危険
a) 当機は、オープンタイプのプロセスコントローラとしてUL Listedの認証を受けていますので、必ず外へ
火の出ない構造の盤内でご使用ください。
b)
2つ以上の遮断スイッチをご使用の場合、修理点検前に、全てのスイッチをOFFし製品を無通電状態にしてください。
c) 信号入力はSELV、制限回路です。
d) 注意:火災や感電の危機を低減する為、異なるClass2回路の出力を内部で接続しないでください。
寿命を超えた状態で使用すると接点溶着や焼損が稀に起こる恐れがあります。
必ず実使用条件を考慮し、定格負荷、電気的寿命回数内でご使用ください。
出力リレーの寿命は、開閉容量、開閉条件により大きく異なります。
ネジがゆるむと発火が稀に起こる恐れがあります。端子ネジは規定トルク0.43-0.58N・mで締めてください。
設定内容と制御対象の内容が異なる場合には、意図しない動作により稀に、装置の破損や事故の原因
となります。デジタル調節計の各種設定値は、制御対象に合わせて正しく設定してください。
デジタル調節計の故障により制御不能や警報出力が出なくなると本機へ接続されている設備、機器等へ
の物的損害が稀に起こる恐れがあります。本機の故障時にも安全なように、別系統で監視機器を取り付
けるなどの安全対策を行ってください。
圧着端子サイズ:M3
●入力種別
この商品は「class A」(工業環境商品)です。住宅環境でご利用されると、電波
妨害の原因となる可能性があります。その場合には電波妨害に対する適切な
対策が必要となります。
EN/IEC 規格対応について
・STOP:制御停止表示
運転中に「ラン/ストップ」を停止「stop」にした
とき点灯します。
制御停止中でも制御出力以外は動作します。
・CMW:通信による書き込み可否表示
通信書込が許可(ON)で点灯、禁止(OFF)で
消灯します。
・   :プロテクト表示
「設定変更プロテクト」がON(プロテクト状態で
アップキー、ダウンキーが無効)のときに点灯
します。
・MANU:マニュアル出力表示
「オート/マニュアルモード」がマニュアルモー
ドで点灯します。
・℃/゜F:温度単位表示
表示されているデータが、温度の場合に点灯しま
す。選択されている「温度単位」の設定値により、
CまたはFを表示します。
・レベルキー
このキーを押すと、各レベル間を移行します。
・モードキー
このキーを押すと、表示項目が変更されます。
1秒以上押すと、逆方向へ遷移します。
・OレベルキーとMモードキーを同時に3秒以
上押すと、プロテクトレベルに切り替わります。
・シフトキー(PFキー)
工場出荷時は「PF設定」が「桁シフト」設定となっ
ています。ファンクションキーであり、キーを押す
と「PF設定」で設定した機能が動作します。
・第1表示
現在値または設定データの種別を表示し
ます。
・第2表示
目標値、設定データの読出値、変更時の
入力値を表示します。
・ダウンキー/アップキー
Uキーを押すごとに、第2表示の値がアッ
プします。または設定内容が進みます。
Dキーを押すごとに、第2表示の値がダウ
ンします。または設定内容が戻ります。
動作表示灯
・SUB1:補助出力1表示
・SUB2:補助出力2表示
・SUB3:補助出力3表示
・OUT1:制御出力1表示
・OUT2:制御出力2表示
・RSP:リモートSP表示
割り当てた機能がONのとき点灯し
ます。
・TUNE:
セルフチューニング時に点滅します。
オートチューニング時に点灯します。
6
4
5
6
5
6
Pt
+
-
m
A
-
+
5
4
*2 センサ(温度/アナログ)入力
V
-5
V6
+
4
TC
4
I
(極性なし)
11
12
*4 入力電源
11
12
AC100~240V AC/DC 24V
~
(64)
58
604
1
48 44.8
形式 E5CC-□□□□□□-□□□
{
{
5. オプション
1. 制御出力
17
15
16
1
2
13
14
3
11
4
6
7
8
9
10
5
18 12
10
7
8
9
*3 補助出力
補助出力1、2 補助出力1、2、3
7
8
9
10
補助出力1
補助出力2
● ●
補助出力2
補助出力3
補助出力1
18
++
-
+
+
-
13
16
17
16
17
18
13
16
17
18
13
14
15
13
14
15
18
16
18
13
14
15
16
17
18
16
17
005
イベント入力1,2/
イベント入力3,4
004
通信(RS-485)/
イベント入力3,4
13
13
14
15
16
007
イベント入力1,2/
リモートSP
006
イベント入力1,2/
伝送出力
*5 オプション
001
イベント入力1,2/
CT1
1717
18
V
I
V
m
A
002
通信(RS-485)/
CT1
003
通信(RS-485)/
CT1,2
14
15
14
15
14
15
EV1
EV2
EV1
EV2
EV1
EV2
EV1
EV2
EV3
EV4
EV3
EV4
CT1 CT1
B(+)
A(-)
RS-485
B(+)
A(-)
RS-485
B(+)
A(-)
RS-485
CT2
COM
CT1
+-
3
1
2
3
1
2-
リニア電流
出力1点タイプ
リレー出力
1点タイプ
3+
1+
2-
3
電圧出力(SSR駆動用)
2点タイプ
*1 制御出力1、2
出力1
R出力1
Q
出力1
Q
出力2
Q
出力1
C
1
2
電圧出力(SSR駆動用)
1点タイプ
+
RX QX CX QQ
3+
1+
2-
リニア電流出力/
電圧出力(SSR駆動用)タイプ
出力1
C
出力2
Q
CQ
※イベント入力は、無電圧入力で使用してください。
(-)は、無接点入力時の極性です。
A
B
B
(-)
(-)
(-) (-) (-)
(-)

Other manuals for E5CC

8

Other Omron Controllers manuals

Omron YSC-8361 User manual

Omron

Omron YSC-8361 User manual

Omron CJ2*-CPU Series User manual

Omron

Omron CJ2*-CPU Series User manual

Omron V720 Series User manual

Omron

Omron V720 Series User manual

Omron E5ED-8 Series User manual

Omron

Omron E5ED-8 Series User manual

Omron CJ Series User manual

Omron

Omron CJ Series User manual

Omron CS1 - User manual

Omron

Omron CS1 - User manual

Omron V530-R160E User manual

Omron

Omron V530-R160E User manual

Omron CPM1A User manual

Omron

Omron CPM1A User manual

Omron E5EC-T User manual

Omron

Omron E5EC-T User manual

Omron C200HS Series Parts list manual

Omron

Omron C200HS Series Parts list manual

Omron CPM1A User manual

Omron

Omron CPM1A User manual

Omron F39-TGR-MCL Series User manual

Omron

Omron F39-TGR-MCL Series User manual

Omron NX-ECC201 User manual

Omron

Omron NX-ECC201 User manual

Omron NX Series Instructions for use

Omron

Omron NX Series Instructions for use

Omron NX Series User manual

Omron

Omron NX Series User manual

Omron E5AN User manual

Omron

Omron E5AN User manual

Omron E5EK DEVICENET User manual

Omron

Omron E5EK DEVICENET User manual

Omron EJ1N-TC4 User manual

Omron

Omron EJ1N-TC4 User manual

Omron 1S Series User guide

Omron

Omron 1S Series User guide

Omron E5EK PROGRAMMABLE TYPE User manual

Omron

Omron E5EK PROGRAMMABLE TYPE User manual

Omron Sysmac NJ-series User manual

Omron

Omron Sysmac NJ-series User manual

Omron ES100 User manual

Omron

Omron ES100 User manual

Omron SYSMAC CS Series User manual

Omron

Omron SYSMAC CS Series User manual

Omron E5GC User manual

Omron

Omron E5GC User manual

Popular Controllers manuals by other brands

Belimo NKQB24-1 quick start guide

Belimo

Belimo NKQB24-1 quick start guide

Western Co WRM30 user manual

Western Co

Western Co WRM30 user manual

Olsberg OEC II Instruction

Olsberg

Olsberg OEC II Instruction

Giant 22910AR-22913AR Installation & operating instructions

Giant

Giant 22910AR-22913AR Installation & operating instructions

Capstone Microturbine C1000 Series installation guide

Capstone

Capstone Microturbine C1000 Series installation guide

Motrona CT340 operating instructions

Motrona

Motrona CT340 operating instructions

Emerson Dixell XR03CH Installing and operating instructions

Emerson

Emerson Dixell XR03CH Installing and operating instructions

ABB MS325 operating instructions

ABB

ABB MS325 operating instructions

Hunter X-CORE XC-2 quick start guide

Hunter

Hunter X-CORE XC-2 quick start guide

Basler KR4FFX instructions

Basler

Basler KR4FFX instructions

VMK VMK-I88plus instruction manual

VMK

VMK VMK-I88plus instruction manual

Honeywell S9200U1000 installation instructions

Honeywell

Honeywell S9200U1000 installation instructions

SOMFY CB 230 RTS installation instructions

SOMFY

SOMFY CB 230 RTS installation instructions

MULTISPAN PID 2303-1C manual

MULTISPAN

MULTISPAN PID 2303-1C manual

Eaton ELC-PC12NNDR instruction sheet

Eaton

Eaton ELC-PC12NNDR instruction sheet

Kuka KR C4 compact Assembly and operating instructions

Kuka

Kuka KR C4 compact Assembly and operating instructions

AVT 2854 quick start guide

AVT

AVT 2854 quick start guide

Vega VEGATOR 141 operating instructions

Vega

Vega VEGATOR 141 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.