V
NOTICE
Be sure to observe these precautions to ensure safe use.
(1) Do not wire the terminals which are not used.
(2) Be sure to wire properly with correct polarity of terminals.
(3) To reduce induction noise, separate the highvoltage or largecurrent power lines from other lines,
and avoid parallel or common wiring with the power lines when you are wiring to the terminals.
We recommend to use separating pipes, ducts, or shielded lines.
(4) Do not use this product in the following places:
•Places subject to dust or corrosive gases (in particular, sulfide gas and ammonia gas)
•Places subject to high humidity, condensation or freezing.
•Places subject to direct sunlight.
•Places subject vibration and large shocks.
•Places subject to splashing liquid or oil atmosphere.
•Places directly subject to heat radiated from heating equipment.
•Places subject to intense temperature changes.
•Places subject to flammable or explosive gas.
(5) To allow heat to escape, do not block the area around the product. (Ensure enough space for heat
to escape.)
(6) If you remove the controller from its case, never touch nor apply shock to the electronic parts
inside.
(7) Cle a ning: Do not use paint thinne r or the equivalent. Use st andard grade alcohol to clean the produ ct .
(8) Use specified size (M3.5, width 7.2mm or less) crimped terminals for wiring.
(9) Allow as much space as possible between the controller and devices that generate a powerful hig
frequency (e.g. highfrequency welders, highfrequency sewing machines) or surge.
PRECAUTIONS FOR ENSURING CORRECT USE
FUse a 100 to 240 V AC (50/60 Hz), 24 VAC (50/60 Hz) or 24 VDC power supply matched to the power
specifications of the E5EKDRT. Also, make sure that rated voltage is attained within two seconds
of turning the power ON.
FAttach a surge suppressor or noise filter to peripheral devices that generate noise (in particular, motors,
transformers, solenoid s , m a g ne tic coils or other equipme nt that h a ve a n ind u ctance compone nt ) .
FWhen mounting a noise filter on the power supply, be sure to first check the filter’s voltage and cur
rent capacity, and then mount the filter as close as possible to the controller.
FInsert a noise filter (TDK ZCB220611 or equivalent) on the AC power line to satisfy conducted emis
sion rating (FCC Regulation Class A EN500812compliant).
FUse within the following temperature and humidity ranges:
•Temperature: 10 to 55°C, Humidity: 35 to 85% (with no icing or condensation)
If the E5EKDRT is installed inside a control board, the ambient temperature must be kept to under
55°C, including the temperature around the controller.
If the controller is subject ed to heat rad iation, us e a fan to cool the surfa ce of the controlle r to under 55°C.
FStore within the following temperature and humidity ranges:
•Temperature: 25 to 65°C, Humidity: 35 to 85% (with no icing or condensation)
FNever place heavy objects on, or apply pressure to the controller that may cause it to deform and dete
riorate during use or storage.
FAvoid using the controller in places near a radio, television set, or wireless installation. These devices
can cause radio disturbances which adversely affect the performance of the controller.