Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
carefully before using the product.
E5CC-U
Digital Controller
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the
performance and functions of the product. Not doing so may occasionally result in unexpected events.
Use the product within specifications.
(1) The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product
in any of the following locations.
•Places directly subject to heat radiated from heating equipment.
•Places subject to splashing liquid or oil atmosphere.
•Places subject to direct sunlight.
•Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
•Places subject to intense temperature change.
•Places subject to icing and condensation.
•Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges. Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use the specified size of crimped terminals (M3.5, width 7.2 mm or less) for wiring. To connect bare wires to
the terminal block, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to cross-
sectional area of 0.205 to 2.081 mm2). (The stripping length is 5 to 6 mm.) Up to two wires of same size and
type, or two crimped terminals can be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high- frequency
or surge. Separate the high-voltage or large-current power lines from other lines, and avoid parallel or
common wiring with the power lines when you are wiring to the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or relay
contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before
starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn
the controller ON.
(12) A switch or circuit breaker should be provided close to this unit. The switch or circuit breaker should be within
easy reach of the operator, and must be marked as a disconnecting means for this unit.
(13) Wipe off any dirt from the Digital Controller with a soft dry cloth. Never use thinners, benzine, alcohol, or any
cleaners that contain these or other organic solvents. Deformation or discoloration may occur.
(14) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after
power ON.
(15) The output will turn OFF when you move to the Initial Setting Level. Take this into consideration when
performing control.
(16) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when
frequently overwriting data during communications or other operations.
(17) When disassembling the Temperature Controller for disposal, use suitable tools.
(18) Do not turn the power supply to the Digital Controller ON or OFF while the USB-Serial Conversion Cable is
connected. The Digital Controller may malfunction.
(19) The terminals can reach temperature of up to 65℃. Use wires with heat resistance of 65℃min to wire the
terminals.
Precautions for Safe Use
Refer to the E5□C Digital Controllers User’s Manual (Man. No. H174)
for detailed application procedures.
INSTRUCTION MANUAL
Thank you for purchasing the
OMRON E5CC-U Digital
Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with
a knowledge of electrical systems.
•Before using the product, thoroughly read and understand
this manual to ensure correct use.
•Keep this manual in a safe location so that it is available for
reference whenever required.
OMRON Corporation
©All Rights Reserved
Refer to the E5□C Digital Controllers User’s Manual (Man.
No.
H174)
for information on the Advanced Function Setting Level, Manual
Control Level, and other functions.
Suitability for Use
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which
apply to the combination of the Product in the Buyer’s application or use of the Product.
At Buyer’s request, Omron will provide applicable third party certification documents identifying ratings and
limitations of use which apply to the Product. This information by itself is not sufficient for a complete
determination of the suitability of the Product in combination with the end product, machine, system, or
other application or use. Buyer shall be solely responsible for determining appropriateness of the particular
product with respect to Buyer’s application, product or system. Buyer shall take application responsibility in
all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED
FOR THE INTENDED USE WITHIN THE OVERALLEQUIPMENT OR SYSTEM.
Power supply voltage 100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz / 24 VDC
Operating voltage range 85 to 110% of the rated voltage
Power consumption 5.2 VA max. (100 to 240 VAC)
3.1 VA max. (24 VAC)
1.6 W max. (24 VDC)
Indication accuracy Thermocouple:
(Ambient temperature: 23°C) (±1.0 % of indication value or ±2°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input:
±0.2 % FS ±1 digit max.
Control output 1 Relay output: SPDT, 250 VAC, 3A
(resistive load)
Electrical life of relay: 100,000 operations
Voltage output (for driving SSR):
12 VDC ±20%, 21 mA
Linear current output:
4 to 20 mA DC, 0 to 20 mADC
Load: 500Ω max.
Control method ON/OFF or 2-PID control
Auxiliary outputs Relay outputs:SPST-NO, 250 VAC, 3A
(resistive load)
Electrical life of relay: 100,000 operations
Ambient temperature -10 to 55°C
(Avoid freezing or condensation)
Ambient humidity 25% to 85%
Storage temperature -25 to 65°C
(Avoid freezing or condensation)
Altitude Max. 2,000m
Recommended fuse
T2A, 250 VAC, time-lag, low-breaking capacity
Weight Approx. 100 g (Digital Controller only)
Degree of protection Front panel: IP50
Rear case: IP20
Terminal section: IP00
Installation environment Installation categoryII, pollution
degree 2 (as per IEC61010-1)
Memory protection Non-volatile memory
(Number of write operations: 1,000,000)
Temporary overvoltage Long-term:250V+(Power supply voltage)
Short-term:1200V+(Power supply voltage)
CAUTION
CAUTION
Minor injury due to electric shock may occasionally occur.
Do not touch the terminals while power is being supplied.
Electric shock, fire, or malfunction may occasionally occur. Do not allow metal objects, conductors,
cuttings from installation work, or moisture to enter the Digital Controller, the Setup Tool ports, or
between the pins on the connectors on the Setup Tool cable.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from
explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric
shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This product is ULlisted as Open Type Process Control Equipment. It must be mounted in an enclosure that
does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur.
Always consider the application conditions and use the output relays within their rated load and electrical
life expectancy. The life expectancy of output relays varies considerably with the output load and
switching conditions.
Loose screws may occasionally result in fire. Tighten the terminal screws to the specified torque of 0.5
N•m.
Set the parameters of the product so that they are suitable for the system being controlled. If they are
not suitable, unexpected operation may occasionally result in property damage or accidents.
Amalfunction in the Digital Controller may occasionally make control operations impossible or prevent
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital
Controller, take appropriate safety measures, such as installing a monitoring device on a separate line.
EN
Safety Precautions
Key to Warning Symbols
Dimensions
Warning Symbols Specifications
Wiring
Operation Menu
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to
provide for different types of alarm. These are indicated by the
letter "L" and "H".
• The default alarm type is "2"
Alarms
*2: Error shown only for "Process value / Set point". Not shown for other status.
When an error has occurred, the No.1 display shows the error code. Take necessary measure
according to the error code, referring the table below.
If the input value exceeds the display limit (-1999 to 9999), though it is within the control
range, [[[[ will be displayed under -1999 and ]]]] above 9999. Under these conditions,
control output and alarm output will operate normally.
Refer to the E5□C Digital Controllers User’s Manual (Man.
No.
H174) for the controllable ranges.
Check the setting of the Input Type parameter,
check the input wiring, and check for broken or
shorts in the temperature sensor.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
repaired. If the display is restored to normal, then
a probable cause can be external noise affecting
the control system. Check for external noise.
After the check of Input error, turn the power OFF
then back ON again. If the display remains the
same, the controller must be repaired. If the
display is restored to normal, then a probable
cause can be external noise affecting the control
system. Check for external noise.
No.1 display Meaning
A/D converter error
*2
Memory error
Input error
*2
s.err (S. Err)
e111 (E111)
Action
OFF
Alarm
Control
output
Status at error
OFF
OFF
Operates
as above the
upper limit.
OFF
OFF
e333 (E333)
Error Display (troubleshooting)
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438AAlexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
Use the following ranges for scaling: -1999
to 9999, -199.9 to 999.9, -19.99 to 99.99,
-1.999 to 9.999
Analog
input type
Current input
Voltage input
Dimensions (mm)
*1
*1
*1
Alarm type
Vary with
"L", "H" values
Vary with
"L", "H" values
Vary with
"L", "H" values
No alarm function Output off
Deviation upper/lower limit
standby sequence ON
Absolute value upper limit
Absolute value lower limit
Absolute value upper limit
standby sequence ON
Absolute value lower limit
standby sequence ON
LBA (only for alarm 1)
Deviation lower limit
standby sequence ON
Deviation upper limit
standby sequence ON
Deviation upper/lower range
Deviation upper limit
Deviation upper/lower limit
Deviation lower limit
Alarm output function
Positive alarm value (X)
Negative alarm value (X)
Setting
PV Change Rate Alarm
X
ON
OFF SP
X
ON
OFF SP
ON
OFF SP
X
X
ON
OFF SP
L H
ON
OFF SP
X
ON
OFF SP
X
ON
OFF SP
X
ON
OFF 0
ON
OFF X
0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF X
0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF X
0
ON
OFF X
0
ON
OFF X
0
ON
OFF X
0
L H
ON
OFF SP
SP
ON
OFF X
ON
OFF X
0
1
0
2
3
4
5
6
7
8
9
SP absolute value upper limit
SP absolute value lower limit
14
15
MV absolute value upper limit
MV absolute value lower limit
16
17
10
11
12
13
SP
X
ON
OFF
ON
OFF X
0
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V
25
26
27
28
29
Setting range
Input type Input
Pt100
JPt100
Thermocouple
Infrared
Thermosensor
ES1B
K
J
T
E
L
U
N
R
S
B
W
PL II
Setting
10 to 70°C
60 to 120°C
115 to 165°C
140 to 260°C
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
44.8×44.8
Sold Separately
*USB-Serial Conversion Cable
(E58-CIFQ2)
In the pack:
*Main unit
*Instruction manual
*Adapter (Y92F-49)
* A Setup Tool port is provided on the upper of the product. Use this port to connect a personal computer to the product when using
the Setup Tool. E58-CIFQ2 USB-Serial Conversion Cable is required to connect the personal computer to the product. (Do not use
the product with the USB-Serial Conversion Cable left permanently connected.)
Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods.
Input Type
-200 to 850
-199.9 to 500.0
0.0 to 100.0
-199.9 to 500.0
0.0 to 100.0
-200 to 1300
-20.0 to 500.0
-100 to 850
-20.0 to 400.0
-200 to 400
-199.9 to 400.0
-200 to 600
-100 to 850
-200 to 400
-199.9 to 400.0
-200 to 1300
0 to 1700
0 to 1700
100 to 1800
0 to 2300
0 to 1300
0 to 90
0 to 120
0 to 165
0 to 260
-300 to 1500
-199.9 to 900.0
0.0 to 210.0
-199.9 to 900.0
0.0 to 210.0
-300 to 2300
0.0 to 900.0
-100 to 1500
0.0 to 750.0
-300 to 700
-199.9 to 700.0
-300 to 1100
-100 to 1500
-300 to 700
-199.9 to 700.0
-300 to 2300
0 to 3000
0 to 3000
300 to 3200
0 to 3200
0 to 2300
0 to 190
0 to 240
0 to 320
0 to 500
Platinum
resistance
thermometer
Temperature inputs
*The default is“5”.
*s.err will be displayed when a platinum resistance thermometer is mistakenly connected
while input type is not set for it. To clear the s.err display, correct the wiring and cycle the
power supply.
5377447-9A(Side-A)
60 min.
45
45
+0.6
0
+0.6
0
+0.6
0
(48 x number of units - 2.5)+1.0
0
45
Installation
Individual mounting (mm) Side-by-side mounting (mm)
• Insert the main unit through the mounting hole in the panel (1 to 5 mm thickness). Insert the
mounting brackets (supplied) into the fixing slots located on the top and bottom of the rear
case.
• Tighten the two mounting screws on the top and bottom of the adapter to keep them
balanced, and finally tighten them to a torque of between 0.29 and 0.39 N·m.
• When more than one machine is installed, make sure that the ambient temperature does
not exceed the specified limit.
°C °F
CU1
48×48 Adapter (Y92F-49)
L H
ON
OFF
SP
458.6
76.8 14.2
44.8
58
48×48
Connections (The applicability of the electric terminals varies with the type
of machine.) Do not connect anything to the terminals that are shaded gray.
* When complying with EMC standards, the line connecting the sensor must be 30 m or less.
If the cable length exceeds 30 m, compliance with EMC standards will not be possible.
The is set for a K thermocouple (input
type of 5) by default. If a different sensor is used,
an input error (s.err ) will occur. Check the
setting of the Input Type parameter.
Linear current output
0 to 20 mA DC
Relay output
(three terminals used)
SPDT, 250 VAC, 3 A
Voltage output
(for driving SSR)
12 VDC, 21 mA
Load: 500 Ωmax.
4 to 20 mA DC
Control output 1
(resistive load)
Control output 1:
RW
CX
A
B
B
+
-
Relay outputs
250 VAC, 3 A
(resistive load)
Control output 1
Input power supply
• 100 to 240 VAC
• 24 VAC/DC (no polarity)
Auxiliary output 1
Sensor (Temperature/Analog) Input
-
+
V
-
mA
+Auxiliary output 2
(Control output (cooling side))
Conformance to EN/IEC Standards
This is a class A product.
In residential areas it may cause radio interference, in which case the user
may be required to take adequate measures to reduce interference.
A 급 기기 (업무용 방송통신기자재)
이 기기는 업무용(A 급) 전자파적합기기로서 판매자또는 사용자는 이 점을
주의하시기 바라며, 가정외의지역에서 사용하는 것을 목적으로 합니다.
E5CC-U + P2CF-11
(93.8)
Surface mounting
Names of Parts on Front Panel
•°C / °F : temperature unit
The temperature unit is displayed when the displayed value
is a temperature. Either Cor Fis displayed according to
the set value of the temperature unit.
•Mode key
Press this key to change the contents of the display.
Press this button for 1 s or longer for reverse scroll.
•Press the Okey and the Mkey together for at
least 3 seconds to switch to protect level.
•Level key
Use this key to change levels:
•Shift key (PF key)
The default PF Setting parameter is for shifting the digit.
This is a function key. When it is pressed, the function
set for the PF Setting parameter will operate.
•:
Lit when Setting Change Protect is ON (disables
the Up and Down Keys).
• MANU:
Lit during Manual Mode.
Operation indicators
•SUB1: Auxiliary output 1 indicator
•SUB2: Auxiliary output 2 indicator
•OUT1: Control output 1 indicator
For a current output, lit except for a
0% output.
•No.1 display
Process value or set data type
•No.2 display
Set point, set data read-out value or changed input
value
• Up and Down keys
Each press of Ukey increments or advances the
values displayed on the No.2 display.
Each press of Dkey decrements or returns the
values displayed on the No.2 display.
•TUNE:
Flashing during ST(self-tuning).
Lit during AT(auto-tuning).
•STOP:
Lit when “Run/Stop” is stopped during operation.
During control stop, functions other than control output
are valid.
E5CC-U
One relay output
QX
One voltage output
(for driving SSR) One linear
current output
OUT1
QOUT1
C
OUT1
R
Other functions
Operation stopped.
(Control/alarm are both stopped.) *5
Initial Setting Level Check the wiring before turning ON the power supply.
POWER ON
MV Monitor
(Heating)
o
0.0
MV Monitor
(Cooling)
c-o
0.0
Alarm Value
Lower Limit 1 *4
al1l
0
Alarm Value 2 *4
al-2
0
Alarm Value
Upper Limit 2 *4
al2h
0
Alarm Value
Lower Limit 2 *4
al2l
0
Input Type *3
Scaling Upper Limit
(only when setting
analog input)
Scaling Lower Limit
(only when setting
analog input)
Decimal Point
(only when setting
analog input)
Temperature
Unit
SP Upper Limit
SP Lower Limit
PID•ON/OFF
In ON/OFF control = onof
In 2-PID control = pid
Standard or Heating/Cooling
Standard control =
stnd
Heating and cooling control =
h-c
Alarm 1 Type:
Specified models only
Control Period (Cooling)
(Unit: Seconds)
*Voltage output (for driving SSR): 2
ST (Self-Tuning)
ST ON = on
ST OFF = off
Direct/Reverse Operation
In Reverse operation (Heating) =
or-r
In Direct operation (Cooling) = or-d
*3
*4
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
onof
s-hc
stnd
st
on
c-cp
20
orev
or-r
alt1
2
Move to Advanced
Function Setting
Level
amov
0
Alarm 1 Hysteresis
alh1
0.2
Alarm 2 Hysteresis
alh2
0.2
Alarm 2 Type:
Specified models only
alt2
2
at
off
Manual Reset Value
Clears the offset
during P or PD control.
of-r
50.0
Hysteresis (Cooling)
chys
1.0
PV
Input Shift
*8
ins
0.0
Derivative Time
(Unit: Seconds)
d
40
SP 0
sp-0
0
SP 1
sp-1
0
SP 3
sp-3
0
SP 4
sp-4
0
SP 5
sp-5
0
SP 6
sp-6
0
SP 7
sp-7
0
SP 2
sp-2
0
25
0
Process Value/Set Point
s.err is displayed when
connected sensor is
different from input type.
AT Execute / Cancel
100%AT Execute at-2
40%AT Execute at-1
Dead Band
c-db
0.0
Hysteresis (Heating)
hys
1.0
Control Output 1
Signal
o1st
4-20
Integral Time
(Cooling)
(Unit: Seconds)
c-i
233
Derivative Time
(Cooling)
(Unit: Seconds)
c-d
40
Proportional Band
(Cooling)
c-p
8.0
°C= c
°F= f
*3
*4
Initial setting level enables users to specify their preferred
operating conditions (input type, alarm type, control method, etc.)
*3: Refer to the adjoining tables for details of input types and alarm types.
*4: Applicable only to models with alarm functions.
*5: Operation is stopped when moved to the initial setting level.
(control/alarm are both stopped.)
*6: The grayed-out setting items are not displayed for some models and
some settings of other setting items.
*7: The four numeric digits of the product code are displayed in the No. 2
display. The setting cannot be changed and there is nothing that you
need to set.
*8: Only the value set to the
ins
: Temperature Input Shift parameter is
applied to the entire temperature input range. When the process value
is 200°C, the process value is treated as 201.2°C after input shift if
the input shift value is set to 1.2°C. The process value is treated as
198.8°C after input shift if the input shift value is set to -1.2°C.
Hold Odown
for at least
1 second
(No.1 display flashes,
then the control stops.)
Hold Odown
for at least
3 seconds
Operation Level
Set Point During
SP Ramp
sp-m
0
Multi-SP Set Point
Selection
m-sp
0
Auto/Manual Switch
PID control only.
a-m
RUN/STOP
r-s
run
Alarm Value 1 *4
al-1
0
When control start = run
When control stop = stop
Operation level should normally be used during operations.
Hold Oand Mkeys
down for at least
1 second
Hold Oand Mkeys
down for at least
3 seconds
Press O
(less than
1 second)
Adjustment Level
Adjustment level is for entering set values and shift values for control.
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
Alarm Value
Upper Limit 1 *4
al1h
0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
Integral Time
(Unit: Seconds)
i
233
Proportional
Band
p
8.0
M
M
M
M
M
M
M
M
MV Upper Limit
ol-h
100.0
SP Ramp Set Value
sprt
off
MV Lower Limit
ol-l
0.0
M
M
M
M
M
(mm)
Control output 1
E5CC 000UM
+
-
+
-
Program Pattern
ptrn
off
M
Extraction of Square
Root Enable
(Only when analog
input is set)
sqr
off
M
Program Start
prst
rset
Soak Time Remain
sktr
0
M
M
Adjustment Level
Displayed only once when
entering Adjustment Level.
*7 l.adj
M
PV input
Slope Coefficient
inrt
1.000
M
M
Soak Time
soak
1
Wait Band
wt-b
off
MV at Stop
mv-s
0.0
MV at PV Error
mv-e
0.0
M
M
M
M
SP Ramp Set Value
(SP Ramp Fall Value)
sprl
same
M
MV Change
Rate Limit
orl
0.0
Extraction of Square
Root Low-cut Point
sqrp
0.0
M
M
M
Auxiliary output 1,2
Operation / Adjustment Protect
Restricts displaying and
modifying menu items in
Operation, Adjustment,
and Manual Control Levels.
oapt
0
Move to Protect Level
Displayed only when a
password is set. Restricts
moving to Protect Level.
Changed
Parameters Only
chgp
off
Parameter Mask
Enable
Displayed only
when a parameter
mask is set.
pmsk
on
Initial Setting / Communication Protect
Restricts movement to the
Initial Setting, Communications
Setting, and Advanced Function
Setting Levels.
icpt
1
Setting Change Protect
Restricts changes to settings
by operating the front panel keys.
wtpt
off
pfpt
off
PF Key Protect
Restricts PF key operation.
Password to Move
to Protect Level
prlp
0
Protect Level
Restricts which settings can be displayed or changed, and
restricts change by key operation.
M
M
M
M
M
M
M
M
pmov
0
30
0 to 50mV
Control Period (Heating)
(Unit: Seconds)
*Voltage output (for driving SSR): 2
cp
20
Simple Transfer Output 1
Upper Limit
o1th
100.0
M
Simple Transfer Output 1
Lower Limit
o1tl
0.0
M
This product with sokect P2CF-11(E) or P3GA-11 gets the UL Listing
Certification.It must be used with the sokect which mentioned above.
Conformance to Safety Standard
Reinforced insulation is provided between input power
supply, relay outputs, and between other terminals.
Always externally connect the recommended fuse that is specified
in the Instruction Manual before you use the Digital Controller.
Analog Input
•
If you input an analog voltage or current, set the Input Type
parameter to the correct input type.
•Do not use the Digital Controller to measure a circuit with
Measurement Category II, III, or IV.
•
Do not use the Digital Controller to measure an energized circuit to
which a voltage that exceeds 30 Vms or 60 VDC is applied.
The protection provided by the Digital Controller may be impaired if the
Digital Controller is used in a manner that is not specified by the
manufacturer.
Conformance to Safety Standards
*Check for a single-fault condition of the COM
terminal before use if auxiliary outputs 1 and 2
will be connected to different electrical potentials.
■配線
■操作メニュー
●外形寸法図
・外形寸法(単位mm)
正しい取扱いをしなければ、この危険のために、時に軽
傷・中程度の傷害をおったり、あるいは物的損害を受け
る恐れがあります。お使いになる前にこの取扱説明書を
お読みになり、十分にご理解ください。
注意
●フロント部の名称
形 E5CC-U
デジタル調節計
製品の動作不良、誤動作または性能・機能への悪影響を防ぐため、以下のことを守ってください。不具合事象が稀に
起こることがあります。仕様外の取扱いはしないでください。
(1)屋内専用機器のため屋内のみで使用してください。ただし、下記の環境では使用、または保管はしないでください。
・加熱機器から輻射熱を直接受けるところ ・水がかかるところ、被油のあるところ
・直射日光が当たるところ ・温度変化の激しいところ
・氷結、結露の恐れのあるところ ・振動、衝撃の影響が大きいところ
・塵あい、腐食性ガス(とくに硫化ガス、アンモニアガスなど)のあるところ
(2)周囲温度および湿度は仕様範囲内で使用および保存してください。必要により、強制冷却してください。
(3)放熱を妨げないよう、デジタル調節計の周辺をふさがないでください。デジタル調節計本体の通風孔はふさがな
いでください。
(4)端子の極性を確認し、正しく配線してください。
(5)配線用圧着端子は、指定サイズ(M3.5、幅7.2mm以下)のものをご使用ください。
裸線接続の配線材は、銅製でAWG24(断面積0.205mm2)-AWG14(断面積2.081mm2)のより線か、単線を使用して
ください。(電線被覆剥きしろ:5~6mm)
1端子への配線は同じサイズ、同じ種類の線で2本まで、圧着端子は2枚までの接続としてください。
(6)使用しない端子には何も接続しないでください。
(7)強い高周波を発生する機器やサージを発生する機器から、できるだけ離して設置してください。配線は、高電圧、
大電流の動力線とは分離して配線してください。また、動力線との平行配線や同一配線を避けてください。
(8)電源電圧および負荷は、仕様、定格の範囲内でご使用ください。
(9)電源電圧は2秒以内に定格電圧に達するようにスイッチ、リレーなどの接点を介して一気に印加してください。
徐々に電圧を印加しますと、電源リセットしなかったり出力の誤動作が発生することがあります。
(10)デジタル調節計に電源を投入してから、正しい温度を表示するまで30分かかります。(実際に制御を始めるこの
時間前に電源を投入してください)
(11)セルフチューニングを使用される場合は、デジタル調節計と負荷の電源を同時、あるいは負荷の電源を先に投入
してください。
(12)作業者がすぐ電源をOFFできるようスイッチまたはサーキットブレーカを設置し、適切に表示してください。
(13)本製品の汚れはやわらかい布で乾拭きしてください。なお、シンナー、ベンジン、アルコールなどの溶剤を含む薬
品等を使用しないでください。変形、変色の恐れがあります。
(14)電源を投入して、デジタル調節計の出力が確定するまで2秒かかります。この時間を考慮して(制御盤などの)設
計してください。
(15)初期設定レベルへ移行すると出力がOFFになりますので、これを考慮した制御をしてください。
(16)不揮発性メモリには書き込み回数に寿命があります。通信などでデータを頻繁に書き換える場合はRAMモードで
使用してください。
(17)廃棄時に分別するとき、工具を使用してください。
(18)USB-シリアル変換ケーブルをデジタル調節計に接続した状態で、デジタル調節計本体の電源を投入または切断
しないでください。デジタル調節計の誤動作の原因となります。
(19)最大端子温度は65℃ですのでご注意ください。 配線は耐熱仕様65℃以上の電線を使用してください。
安全上の要点
●警告表示の意味
取扱説明書
このたびは、オムロン製品をお買い上げいただきまして、まことにあり
がとうございます。この取扱説明書では、この製品を使用する上で、
必要な機能、性能、使用方法などの情報を記載しています。
この製品をご使用に際して下記のことを守ってください。
・この製品は電気の知識を有する専門家が扱ってください。
・この取扱説明書をよくお読みになり、十分にご理解のうえ、正しくご
使用ください。
・この取扱説明書はいつでも参照できるよう大切に保管ください。
©All Rights Reserved
梱包内容
・本体
・取扱説明書
・アダプタ(形Y92F-49)
ご承諾事項
当社商品は、一般工業製品向けの汎用品として設計製造されています。従いまして、次に掲げる用途での使用を意
図しておらず、お客様が当社商品をこれらの用途に使用される際には、当社は当社商品に対して一切保証をいたし
ません。ただし、次に掲げる用途であっても当社の意図した商品用途の場合や特別の合意がある場合は除きます。
a) 高い安全性が必要とされる用途(例:原子力制御設備、燃焼設備、航空・宇宙設備、鉄道設備、昇降設備、娯楽設
備、医用機器、安全装置、その他生命・身体に危険が及びうる用途)
b) 高い信頼性が必要な用途(例:ガス・水道・電気等の供給システム、24時間連続運転システム、決済システムほか
権利・財産を取扱う用途など)
c) 厳しい条件または環境での用途(例:屋外に設置する設備、化学的汚染を被る設備、電磁的妨害を被る設備、振
動・衝撃を受ける設備など)
d) カタログ等に記載のない条件や環境での用途
* (a)から(d)に記載されている他、本カタログ等記載の商品は自動車(二輪車含む。以下同じ)向けではありません。自動車に搭載する用途には
利用しないで下さい。自動車搭載用商品については当社営業担当者にご相談ください。
* 上記は適合用途の条件の一部です。当社のベスト、総合カタログ、データシート等最新版のカタログ、マニュアルに記載の保証・免責事項の内
容をよく読んでご使用ください。
●仕様
電源電圧 AC100-240V 50/60Hz
またはAC24V 50/60Hz/DC24V
許容電圧変動範囲 定格電圧の85~110%
消費電力 5.2VA以下(AC100-240V)
3.1VA以下(AC24V)
1.6W以下(DC24V)
指示精度 熱電対:(指示値の±1.0%または±2℃の大きい方)
(周囲温度:23℃) ±1ディジット以下
白金測温抵抗体:(指示値の±0.2%または±0.8℃
の大きい方)±1ディジット以下
アナログ入力±0.2%FS±1ディジット以下
制御出力1 リレー出力 AC250V 3A (抵抗負荷)
リレーの電気的寿命 10万回
電圧出力(SSR駆動用) DC12V±20%、21mA
リニア電流出力 DC4-20mA/DC0-20mA、
負荷500Ω以下
制御方式 2自由度PIDまたはON/OFF
補助出力 リレー出力 AC250V 3A (抵抗負荷)
リレーの電気的寿命 10万回
使用周囲温度 -10~55℃(ただし、氷結、結露しないこと)
使用周囲湿度 25~85%RH
保存温度 -25~65℃(ただし、氷結、結露しないこと)
高度 2,000m以下
推奨ヒューズ T2A、AC250V タイムラグ低遮断容量
質量 約100g(本体のみ)
保護構造 前面:IP50
リアケ-ス:IP20
端子部:IP00
設置環境 設置カテゴリⅡ、汚染度2(IEC61010-1による)
メモリ保護 不揮発性メモリ(書込み回数:100万回)
一時過電圧 長時間過電圧 250V + (電源電圧)
短時間過電圧 1200V + (電源電圧)
詳細な使用方法は別冊「形E5□C ユーザーズマニュアル
」
(Man. No.
:
SGTD-740
)を参照してください。
*3:入力種別と警報種別の項目は、左の表を参照してください。
*4:警報機能がある機種だけ機能します。
*5:初期設定レベルへ移行すると運転が停止します。(制御・ 警報共に停止)
*6:グレー表示になっているモニタ/設定の項目は機種や設定内容により表
示されない場合があります。
*7:第2表示には、商品コードの数字部4桁が表示されます。設定変更ができ
ませんが、お客様に何か設定していただく必要はございません。
*8:
「ins」
PV入力補正値の設定値分だけ、センサ入力範囲のすべての
点において入力温度を補正します。補正前の現在値が200℃のと
き、補正値を1.2℃とすると補正後は201.2℃、補正値を-1.2℃とする
と補正後は198.8℃として扱います。
注意
JPN
●警告表示
*製品上面部に設定ツールを使用する際、パソコンとデジタル調節計を接続するために使用する設定ツール用ポートを標準搭載しています。
接続には専用のUSB-シリアル変換ケーブル(形E58-CIFQ2)が必要です。(常時接続状態での使用はできません。)
詳細な接続方法は、USB-シリアル変換ケーブルに付属の取扱説明書を参照ください。
入力が制御可能範囲内で表示可能範囲
(-1999~9999)
を超えた場合、
-1999
より小さい値は
[[[[、
9999
より大きい値は ]]]]
と表示します。
この表示のときは制御出力および警報出力ともに正常に動作します。
制御可能範囲についての詳細は
「形E5□C ユーザーズマニュアル」(Man.
No.:SGTD-740)
を参照してく
ださい。
*2:
表示が「現在値/目標値」のときだけエラー表示します。他の状態ではエラー表示しません。
●異常時の表示について(トラブルシューティング)
異常が発生すると、第1表示にエラー内容を表示します。エラー表示によってエラー
の内容を確認し、その内容についての処置をしてください。
OFF
異常高温と
して処理
●警報種別
*2
*2
メモリ異常
入力異常
s.err(S.Err)
e111(E111)
A/Dコンバータ
異常
異常時の出力状態
制御出力 警報出力
OFF
OFF
OFF
OFF
e333(E333)
第1表示 異常内容 処置
入力種別の設定を確認、あるいは入力の誤配線、測
温体の断線・短絡を確認してください。
入力異常を確認後、電源を入れ直してください。
表示内容が変わらない場合は修理が必要です。
正常になった場合はノイズの影響が考えられるので、ノ
イズが発生していないか確認してください。
電源を入れ直してください。
表示内容が変わらない場合は修理が必要です。
正常になった場合はノイズの影響が考えられるので、
ノイズが発生していないか確認してください。
安全上のご注意
・初期値は「5」です。
・測温抵抗体以外の設定値で、誤って測温抵抗体を接続したときはs.errを表示
します。s.errを解除するには配線を見直し、電源を入れ直してください。
*1
*1
*1
警報種別
L,Hの値による
L,Hの値による
L,Hの値による
警報機能なし 出力
OFF
上下限待機シーケンス付
絶対値上限
絶対値下限
絶対値上限待機シーケンス付
絶対値下限待機シーケンス付
LBA
(警報1種別のみ)
下限待機シーケンス付
上限待機シーケンス付
上下限範囲
上限
上下限
下限
警報出力機能
警報値(X)が正 警報値(X)が負
設定値
PV変化率警報
X
ON
OFF SP
X
ON
OFF SP
ON
OFF SP
X
X
ON
OFF SP
LH
ON
OFF SP
X
ON
OFF SP
X
ON
OFF SP
X
ON
OFF 0
ON
OFF
X
0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF
X
0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
X
ON
OFF 0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
ON
OFF
X
0
LH
ON
OFF SP
LH
ON
OFF
SP
SP
ON
OFF
X
ON
OFF
X
0
1
0
2
3
4
5
6
7
8
9
SP絶対値上限
SP絶対値下限
14
15
MV絶対値上限
MV絶対値下限
16
17
10
11
12
13
*1:設定値1、4、5は警報の上・下限値が個別に設定でき、L,Hで表してい
ます。
  ・初期値は「2」です。
SP
X
ON
OFF
ON
OFF
X
0
Oキー
3秒以上
(表示が点滅し制御
 が停止します。)
●初期設定レベル
運転が停止します。 (制御・警報共に停止)
*5
Oキー
1秒以上
初期設定レベルでは、入力種別、警報種別、制御方式などのお客様の
ご使用条件を設定します。
25
0
電源投入する前に配線を確認してください。
電源投入
●運転レベル
運転中は通常、運転レベルでご使用ください。
ランプ目標値モニタ
sp-m
0
オート/マニュアル切替
PID制御のみ
a-m 警報下限値1*4
al1l
0
警報値2*4
al-2
0
警報上限値2*4
al2h
0
警報下限値2*4
al2l
0
25
0
現在値/目標値
接続したセンサと入力
種別が異なる場合、
s.err
M
M
M
M
操作量モニタ
(加熱) 
o
0.0
操作量モニタ
(冷却) 
c-o
0.0
M
M
M
マルチSP
目標値の選択
m-sp
0
M
M
制御開始の時 run
制御停止の時 stop
ラン/ストップ
r-s
run
警報値1*4
al-1
0
M
M
警報上限値1*4
al1h
0
M
M
■その他の機能
「高機能設定レベル」および「マニュアル制御レベル」やその他、
詳細は「形E5□C ユーザーズマニュアル」(Man. No.:SGTD-740)
を参照してください。
キー操作による設定変更やレベルの移行を制限します。
運転/調整プロテクト
運転・調整・マニュアル制御
レベルのメニュー表示、書込
み等を制限
oapt
0
プロテクトレベル移行
パスワード設定時のみ表示
プロテクトレベルへの移行を
制限
変更パラメータ
表示
chgp
off
パラメータマスク
有効
パラメータマスク
設定時のみ
pmsk
on
初期/通信プロテクト
初期設定・通信設定・高機能
設定レベルへの移行を制限
icpt
1
設定変更プロテクト
キー操作による設定変更を
制限
wtpt
off
pfpt
off
PFキープロテクト
PFキー操作を制限
●プロテクトレベル
 O+Mキー
3秒以上
 O+Mキー
1秒以上
プロテクトレベル
移行パスワード
prlp
0
M M
M
M
M
M
M
M
Oキー
1秒未満
入力種別*3
スケーリング上限値
(アナログ入力設定時のみ)
スケーリング下限値
(アナログ入力設定時のみ)
小数点位置
(アナログ入力設定時のみ)
温度単位
目標値リミット上限値
目標値リミット下限値
PID・ON/OFF
ON/OFF制御の時 onof
2自由度PID制御の時 pid
標準/加熱冷却
標準制御の時 stnd
加熱冷却制御の時 h-c
警報1種別
制御周期(冷却)
(単位:秒)
※電圧出力(SSR駆動用)は2
℃の時 c
。
Fの時 f
ST
(セルフチューニング)
ST
ONの時     
on
ST
OFFの時    
off
正/逆動作
逆動作(加熱制御)の時
or-r
正動作(冷却制御)の時
or-d
*3
*4
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
onof
s-hc
stnd
st
on
c-cp
20
orev
or-r
alt1
2
高機能設定
レベル移行
amov
0
警報1ヒステリシス
alh1
0.2
警報2ヒステリシス
alh2
0.2
警報2種別 *3
*4
alt2
2
制御出力1
信号種別
o1st
4-20
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
M
開平演算有効
(アナログ入力
設定時のみ)
sqr
off
M
プログラムスタート
prst
rset
ソーク残り時間モニタ
sktr
0
M
M
*7
●調整レベル
調整レベルは、制御を行うための設
定値や補正値を入力するレベルです。
調整レベル表示
調整レベル移行時に
1回のみ表示
at
off
操作量リミット上限値
ol-h
100.0
SPランプ設定値
sprt
off
SPランプ設定値
(下降値)
sprl
same
PV入力補正値*8
ins
0.0
PV入力傾き
補正係数
inrt
1.000
操作量リミット下限値
ol-l
0.0
操作量変化率リミット
orl
0.0
開平演算ローカット点
sqrp
0.0
目標値0
sp-0
0
目標値1
sp-1
0
目標値4
sp-4
0
目標値5
sp-5
0
目標値6
sp-6
0
目標値7
sp-7
0
目標値2
sp-2
0
比例帯
p
8.0
M
調節感度(冷却)
chys
1.0
調節感度(加熱)
hys
1.0
M
M
ソーク時間
soak
1
ウェイト幅
wt-b
off
M
M
ストップ時操作量
mv-s
0.0
異常時操作量
mv-e
0.0
M
M
M
M
M
M
M
M
M
M
M
M
M
M
積分時間
(単位:秒)
i
233
微分時間
(単位:秒)
d
40
積分時間(冷却)
(単位:秒)
c-i
233
微分時間(冷却)
(単位:秒)
c-d
40
比例帯(冷却)
c-p
8.0
M
M
M
M
デッドバンドc-db
0.0
M
マニュアルリセット値
P、PD制御時
オフセットをクリア
of-r
50.0
M
M
M
M
M
目標値3
sp-3
0
M
M
M
AT実行/中止
100%AT実行の時
at-2
40%AT実行の時
at-1
単位(mm)
l.adj
pmov
0
制御周期(加熱)
(単位:秒)
※電圧出力(SSR駆動用)は2
cp
20
M
簡易伝送出力1上限値 
o1th
100.0
M
簡易伝送出力1下限値 
o1tl
0.0
M
感電により軽度の傷害が稀に起こる恐れがあります。
通電中は端子に触らないでください。
軽度の感電、発火、機器の故障が稀に起こる恐れがあります。製品の内部や設定ツール用ポート内部、
設定ツール用ケーブルのコネクタ部のピン間に金属、導線、取り付け加工中の切粉、または水分などが
入らないようにしてください。
爆発により稀に軽度の傷害の恐れがあります。
引火性、爆発性ガスのある所では使用しないでください。
軽度の感電、発火、機器の故障が稀に起こる恐れがあります。
分解、改造、修理したり、内部に触らないでください。
注意 火災や感電の危険
a) 当機は、オープンタイプのプロセスコントローラとしてUL Listingの認証を受けていますので、必ず外へ
火の出ない構造の盤内でご使用ください。
b)
2つ以上の遮断スイッチをご使用の場合、修理点検前に、全てのスイッチをOFFし製品を無通電状態にしてください。
c) 信号入力はSELV、制限回路です。
d) 注意:火災や感電の危機を低減する為、異なるClass2回路の出力を内部で接続しないでください。
寿命を超えた状態で使用すると接点溶着や焼損が稀に起こる恐れがあります。
必ず実使用条件を考慮し、定格負荷、電気的寿命回数内でご使用ください。
出力リレーの寿命は、開閉容量、開閉条件により大きく異なります。
ネジがゆるむと発火が稀に起こる恐れがあります。端子ネジは規定トルク0.5N・mで締めてください。
設定内容と制御対象の内容が異なる場合には、意図しない動作により稀に、装置の破損や事故の原因
となります。デジタル調節計の各種設定値は、制御対象に合わせて正しく設定してください。
デジタル調節計の故障により制御不能や警報出力が出なくなると本機へ接続されている設備、機器等へ
の物的損害が稀に起こる恐れがあります。本機の故障時にも安全なように、別系統で監視機器を取り付
けるなどの安全対策を行ってください。
●取り付け
60以上
45
45
+0.6
 0
+0.6
 0
+0.6
 0
(48×台数-2.5) +1.0
 0
45
個別取り付けのとき(単位mm) 密着取り付けのとき(単位mm)
・取り付けは、本体をパネル(厚さ1~5mm)角穴へ入れ、付属のアダプタをリアケースの上面およ
び下面の固定溝にはめ込んでください。
・アダプタの固定ねじ(2箇所)を、交互に少しずつバランスをとりながら、トルク0.29~0.39N・mで締
め付けてください。
・複数個を取り付けて使用される場合、本機の周囲温度が仕様を超えないようにご注意ください。
別売品
・USB-シリアル変換ケーブル
 (形E58-CIFQ2)
電流入力
電圧入力
ア ナ ロ グ入力
4~20mA
0~20mA
1~5V
0~5V
0~10V
0~50mV
℃
-200~850
-199.9~500.0
0.0~100.0
-199.9~500.0
0.0~100.0
-200~1300
-20.0~500.0
-100~850
-20.0~400.0
-200~400
-199.9~400.0
-200~600
-100~850
-200~400
-199.9~400.0
-200~1300
0~1700
0~1700
100~1800
0~2300
0~1300
0~90
0~120
0~165
0~260
設定範囲
センサ種類
測温抵抗体
センサ仕様
Pt100
JPt100
熱電対
非接触
温度センサ
形ES1B
K
J
T
E
L
U
N
R
S
B
W
PLⅡ
温度入力
設定値
10~70℃
60~120℃
115~165℃
140~260℃
スケーリングにより-1999~9999、
-199.9~999.9、-19.99~99.99、
-1.999~9.999の範囲で使用。
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
°F
-300~1500
-199.9~900.0
0.0~210.0
-199.9~900.0
0.0~210.0
-300~2300
0.0~900.0
-100~1500
0.0~750.0
-300~700
-199.9~700.0
ー300~1100
-100~1500
-300~700
-199.9~700.0
-300~2300
0~3000
0~3000
300~3200
0~3200
0~2300
0~190
0~240
0~320
0~500
●入力種別
この商品は「class A」(工業環境商品)です。住宅環境でご利用されると、電波
妨害の原因となる可能性があります。その場合には電波妨害に対する適切な
対策が必要となります。
EN/IEC 規格対応について
・STOP:
運転中に「ラン/ストップ」を停止「stop」にした
とき点灯します。
制御停止中でも制御出力以外は動作します。
・   :
「設定変更プロテクト」がON(プロテクト状態
でアップキー、ダウンキーが無効)のときに
点灯します。
・MANU:
マニュアルモード時に点灯します。
・℃/゜F:温度単位表示
表示されているデータが、温度の場合に点灯しま
す。選択されている「温度単位」の設定値により、
CまたはFを表示します。
・レベルキー
このキーを押すと、各レベル間を移行します。
・モードキー
このキーを押すと、表示項目が変更されます。
1秒以上押すと、逆方向へ遷移します。
・OキーとMキーを同時に3秒以
上押すと、プロテクトレベルに切り替わります。
・シフトキー(PFキー)
工場出荷時は「PF設定」が「桁シフト」設定となっ
ています。ファンクションキーであり、キーを押す
と「PF設定」で設定した機能が動作します。
・第1表示
現在値またはモニタ/設定の項目が表示さ
れます。
・第2表示
目標値またはモニタ/設定の値が表示され
ます。
・ダウンキー/アップキー
Uキーを押すごとに、第2表示の値がアッ
プします。または設定内容が進みます。
Dキーを押すごとに、第2表示の値がダウ
ンします。または設定内容が戻ります。
動作表示灯
・SUB1:補助出力1表示
・SUB2:補助出力2表示
・OUT1:制御出力1表示
リニア電流出力の場合は、0%出力以外
で点灯します。
・TUNE:
ST(セルフチューニング)時に点滅します。
AT(オートチューニング)時に点灯します。
□44.8
□48 アダプタ(形Y92F-49)
458.6
76.8 14.2
44.8
58
□48
グレー表示の端子へは接続しないでください。
A
B
B
+
-
AC250V 3A(抵抗負荷)
制御出力1
•
•
補助出力1
リレー出力
-
+
V
-
mA
+
●接続(機種によって端子の用途は異なります。)
ご購入時、入力種別は「5」熱電対(K)に設定されてい
ます。センサが異なる場合は、入力異常(s.err)が発
生することがあります。入力種別を確認してください。
センサ(温度/アナログ)入力
補助出力2
(制御出力(冷却側))
入力電源
制御出力1:
リニア電流出力
DC0-20mA
リレー出力
1cAC250V 3A
(抵抗負荷)
電圧出力(SSR駆動用)
DC12V 21mA
負荷500Ω以下
DC4-20mA
(3端子使用)
制御出力 1
※EMC規格適合上、センサの長さは、30m以内で使用してください。
30mを超えて使用される場合はEMC規格適合外となりますのでご注意ください。
E5CC-U + P2CF-11
(93.8)
●表面取付
AC100~240V
AC/DC 24V(極性なし)
RW
CX
リレー出力
1点タイプ
QX
+
-
電圧出力(SSR駆動用)
1点タイプ
リニア電流
出力1点タイプ
出力1
Q出力1
C
出力1
R
プログラムパターン
ptrn
off
M
形式 E5CC-□□□□UM-000
{
制御出力1
+
-
補助出力1,2
●製品に関するお問い合わせ先
お客様相談室
インダストリアルオートメーションビジネスカンパニー 
●その他のお問い合わせ
 
納期・価格・サンプル・仕様書は貴社のお取引先、または貴社担当オムロン販売員にご相談ください。
オムロン制御機器販売店やオムロン販売拠点は、Webページでご案内しています。
●FAXやWebページでもお問い合わせいただけます。
FAX 055-982-5051 / www.fa.omron.co.jp
クイック
0120-919-066
携帯電話・PHS・IP電話などではご利用いただけませんので、下記の電話番号へおかけ
く
ださい。
電話
055-982-5015
(通話料がかか り ま す)
■営業時間:8:00~21:00
■営業日:365日
オムロン
この製品は、ソケット 形P2CF-11(E) および 形P3GA-11 とセットで、UL Listing の認
証を受けていますので、必ず、上記いずれかのソケットとセットでご使用ください。
入力電源-リレー出力-その他の端子相互間は強化絶縁されているこ
とを示します。
安全規格対応について
取扱説明書記載の推奨ヒューズを必ず外部に取り付けて使用してください。
製造者が指定しない方法で機器を使用すると、機器が備える保護を損なう場合があ
ります。
アナログ入力に関して
・電圧または電流を入力する場合、入力種別に合わせて入力タイプを設定してください。
・ 計測カテゴリⅡ、Ⅲ、Ⅳに該当する回路の測定には使用しないでください。
・ 30Vrmsまたは60VDCを超える電圧が印加された対象の測定には使用しないでください。
安全規格対応について
5377447-9A(Side-B)
異なる電位を補助出力1、2に接続する場合、COM端
子の単一故障状態をご確認の上、ご使用ください。

Other manuals for E5CC-U

2

Other Omron Controllers manuals

Omron FH-L550 User manual

Omron

Omron FH-L550 User manual

Omron OMNUC G5 R88M-K series User manual

Omron

Omron OMNUC G5 R88M-K series User manual

Omron CK3W-AX2323 Series User guide

Omron

Omron CK3W-AX2323 Series User guide

Omron NJ501-1500 User manual

Omron

Omron NJ501-1500 User manual

Omron K8AK-LS User manual

Omron

Omron K8AK-LS User manual

Omron SYSMAC C200H User manual

Omron

Omron SYSMAC C200H User manual

Omron CS1G/H-CPUxx-EV1 Owner's manual

Omron

Omron CS1G/H-CPUxx-EV1 Owner's manual

Omron SYSMAC-SE20 Series User guide

Omron

Omron SYSMAC-SE20 Series User guide

Omron E5 K-T - User manual

Omron

Omron E5 K-T - User manual

Omron CS1G/H-CPUxx-H User manual

Omron

Omron CS1G/H-CPUxx-H User manual

Omron C200H-ASC11 User manual

Omron

Omron C200H-ASC11 User manual

Omron NJ501-1 Series User manual

Omron

Omron NJ501-1 Series User manual

Omron E5AX-LA User manual

Omron

Omron E5AX-LA User manual

Omron NE1A-SCPU02 User manual

Omron

Omron NE1A-SCPU02 User manual

Omron V700 series User manual

Omron

Omron V700 series User manual

Omron G9SP Series User manual

Omron

Omron G9SP Series User manual

Omron CK3W-AX1313 Series User guide

Omron

Omron CK3W-AX1313 Series User guide

Omron CPM1A User manual

Omron

Omron CPM1A User manual

Omron CJ Series User manual

Omron

Omron CJ Series User manual

Omron NX Series User manual

Omron

Omron NX Series User manual

Omron G3PW User manual

Omron

Omron G3PW User manual

Omron SYSMAC C200HW-ZW3AT2-E-V2 User manual

Omron

Omron SYSMAC C200HW-ZW3AT2-E-V2 User manual

Omron Trajexia TJ1-MC16 User manual

Omron

Omron Trajexia TJ1-MC16 User manual

Omron CQM1H - 08-2005 Parts list manual

Omron

Omron CQM1H - 08-2005 Parts list manual

Popular Controllers manuals by other brands

PXM Driver LED 1x2A/48V manual

PXM

PXM Driver LED 1x2A/48V manual

Honeywell EVOTOUCH CONTROLLER user guide

Honeywell

Honeywell EVOTOUCH CONTROLLER user guide

Holiday Brilliant TY-T7 instruction manual

Holiday Brilliant

Holiday Brilliant TY-T7 instruction manual

Navien NR-35D user manual

Navien

Navien NR-35D user manual

Mitsubishi Electric MELSEC FX2N-232-BD user guide

Mitsubishi Electric

Mitsubishi Electric MELSEC FX2N-232-BD user guide

Munters Farm Premium user manual

Munters

Munters Farm Premium user manual

Novus N120 instruction manual

Novus

Novus N120 instruction manual

IBM 8248-L4T manual

IBM

IBM 8248-L4T manual

Automationdirect.com Stellar SR44 user manual

Automationdirect.com

Automationdirect.com Stellar SR44 user manual

Audioplex LLP-1 installation manual

Audioplex

Audioplex LLP-1 installation manual

Baldor DBSC 100 Series Installation and operating manual

Baldor

Baldor DBSC 100 Series Installation and operating manual

Osram DALI MCU manual

Osram

Osram DALI MCU manual

Hunter Hydrawise HCC-FPUP quick start guide

Hunter

Hunter Hydrawise HCC-FPUP quick start guide

Mitsubishi Electric MELSEC-F FX3U-232ADP-MB installation manual

Mitsubishi Electric

Mitsubishi Electric MELSEC-F FX3U-232ADP-MB installation manual

Penn TC3B21 installation guide

Penn

Penn TC3B21 installation guide

Hunter X-CORE Owners manual and programming instructions

Hunter

Hunter X-CORE Owners manual and programming instructions

HTC VIVE Operation guide

HTC

HTC VIVE Operation guide

Mitsubishi Electric MELSEC iQ-R Series Safety function block reference

Mitsubishi Electric

Mitsubishi Electric MELSEC iQ-R Series Safety function block reference

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.