Omron H8CA-S Series User manual

1
H8CA-SSolid-State Counter/Timer
1/16 DIN, Easy-to-Operate
Combination Counter and Timer
■
Operation selectable as preset counter
or timer
■
6-digit LCD display—
Present Value: 8 mm (0.32 in)
Set Value: 4 mm (0.16 in)
■
Nonsignificant zeros suppressible from
preset or count value display
■
Selectable power supply voltages
24 to 240 VAC and 12 to 120 VDC
■
Memory protection
■
4 programmable output modes available for
both counter and timer functions
Ordering Information
■
Counter/Timer
Note:
Do not use the contact input at a counting speed of 1 kcps.
Mounting style Surface/flush mounting
Operating function Preset counter/timer (selectable)
Operating system (mode) Counter: reversible (Three input modes and four operating modes are selectable)
Timer: time-limit operation, integrating operation (Four operating modes are
selectable)
Backup power supply for memory protection Provided: Approx. 10 years at 20° C (68° F)
Number of counts 0 to 999999 (6 digits)
Timing ranges 0.00 to 9999.99 s, 0.0 to 99999.9 min., 0.0 to 99999.9 h (6 digits)
External connection Socket
Display type 6-digit backlit LCD; 8 mm (0.32 in) Present Value, 4 mm (0.16 in) Set Value
Count and reset input for counter function;
reset and gate input for timer function
No-voltage input (See Note.)
(solid-state/contact input)
Voltage input
Control output Contact Solid-state Contact Solid-state
Power supply/
counting speed
AC 30 cps
H8CA-SAL H8CA-SALS H8CA-SALV H8CA-SALVS
1 kcps
H8CA-SAH H8CA-SAHS H8CA-SAHV H8CA-SAHVS
DC 30 cps
H8CA-SDL H8CA-SDLS H8CA-SDLV H8CA-SDLVS
1 kcps
H8CA-SDH H8CA-SDHS H8CA-SDHV H8CA-SDHVS

2
H8CA-S
H8CA-S
■
Accessories (Order Separately)
Specifications
■
Ratings
Note: 1.
On power application, the following inrush current flows for 0.5 ms.
3.7 A at 240 VAC, 2.3 A at 120 VDC
2.
The source current output from each input terminal when using no-voltage input is 2 mA max.
Description
Part number
Sockets 11-pin Bottom surface or track mounting, top screw terminals
P2CF-11
Bottom surface or track mounting, top screw terminals, finger safe terminal
conforms to VDE0106/P100
P2CF-11-E
Back mounting, for use with Y92F-30 mounting adapter, bottom screw
terminals
P3GA-11
Panel mounting adapter Fits behind panel, ideal for side-by-side installation. Use P3G
❑
-
❑
sockets
Y92F-30
NEMA 4 cover Waterproof front cover
Y92A-48N
Mounting track DIN rail, 50 cm (1.64 ft) length; 7.3 mm thick
PFP-50N
DIN rail, 1 m (3.28 ft) length; 7.3 mm thick
PFP-100N
DIN rail, 1 m (3.28 ft) length; 16 mm thick
PFP-100N2
End plate
PFP-M
Spacer
PFP-S
Supply voltage AC 24 to 240 VAC, 50/60 Hz
DC 12 to 120 VDC (20% max. permissible ripple)
Operating voltage range 90 to 110% of rated voltage
Power consumption (See Note 1.) Approx. 2.2 VA (at 240 VAC, 50 Hz)
Approx. 1 W (at 120 VDC)
Max. counting speed of CP1 and CP2 In counter function mode:
30 cps (contact and solid-state inputs):
Minimum pulse width: 16.7 ms (ON/OFF ration: 1:1)
1 kcps (solid-state input):
Minimum pulse width: 0.5 ms (ON/OFF ratio: 1:1)
Reset system External reset (common to contact and solid-state inputs) and manual reset
Minimum reset signal width: 20 ms
Start and gate response time In timer function mode:
Start and gate response time (common to contact and solid-state inputs):
L-type: 16.5 ms
H-type: 0.5 ms
Count and reset inputs for counter
function/ start and gate inputs for timer function
No-voltage input: (See Note 2.)
Maximum short-circuit impedance: 1 k
Ω
Short-circuit residual voltage: 0.5 V max. (1.3 V max.)
Minimum open impedance: 100 k
Ω
Voltage input:
5 to 30 V at “High” level
0 to 2 V at “Low” level
Input impedance: Approx. 4.7 k
Ω
Control output Contact output type: SPDT 250 VAC 3 A p.f.=1 (resistive load)
Solid-state ouput type: Open collector 30 VDC max. 100 mA max.
Approvals UL / CSA / SEV

3
H8CA-S
H8CA-S
■
Characteristics
Note:
Operate time of output circuit is included in overall error.
Engineering Data
■
Electrical Service Life
Resistive Load Inductive Load
In timer
function mode
Repeat accuracy ±0.05% ±0.05 s
Setting error ±0.1% ±0.005 s
Variation due to
voltage change
±0.05% ±0.05 s max.
Variation due to
temperature change
Insulation resistance 100 m
Ω
min at 500 VDC
Dielectric Strength 1,500 VAC 50/60 Hz for 1 minute
Vibration Mechanical durability: 10 to 55 Hz, 0.75 mm (0.030 in) double amplitude
Malfunction durability: 10 to 55 Hz, 0.3 mm (0.012 in) double amplitude
Shock Mechanical durability: approx. 30 G
Malfunction durability: approx. 10 G
Ambient temperature Operating: -10° to 55° C (14° to 131° F)
Storage: -25° to 65° C (-13° to 149° F)
Humidity 35 to 85% RH
Service life Mechanically: 10,000,000 operations min.
Electrically: See “Engineering Data”
Weight Approx. 130 g (4.59 oz)
30 VDC (p.f. = 1)
250 VAC (p.f. = 1)
Load current (A)
0 1 2 3
Switching operations (x103)
100
500
1000
0
30 VDC (L/R = 7 ms)
250 VAC (p.f. = 0.4)
Load current (A)
0 1 2 3
Switching operations (x103)
100
500
1000
0

4
H8CA-S
H8CA-S
Timing Charts
■
Count Output Modes
In the timing charts below, “A” is the minimum signal width. “B” must be at least 1/2 of minimum signal width, otherwise, signals may not be
counted if the minimums for “A” and “B” are not met.
■
In Counter Function Mode
■
In Timer Function Mode
Command Input Mode A Individual Input Mode B
Phase Difference Input Mode C
Count
input 1
Count
input 2
Digitaldis
play
Count
input 1
Count
input 2
Digital
display
Count
input 1
Count
input 2
Digital
display
Enlargement from left.
Counting speeds of CP1 and CP2 must
be the same for Reversible C.

5
H8CA-S
H8CA-S
■
Functions of Input Signals
■
Output Modes in Both Counter and Timer Operations
Sustained control output One-shot control output, set to 0.5 second
Input type Counter output Signal high Signal low
No-voltage Contact The contact turns ON The contact turns OFF
Solid-state The open collector transistor is in the ON state The transistor is in the OFF state
Voltage Both Input signal voltage level is 5 to 30 V Input signal voltage level is 0 to 2 V
Input Counter mode A
(command input)
Counter mode B
(individual input)
Counter mode C
(phase difference)
Timer operation
Count input 1 Count input:
The count value is increased
by one when count input 2
(CP2) voltage goes low. The
count value is decreased by
one when count input 2 (CP2)
voltage goes up.
Addition count input The count value is increased by
one when phase of count input
2 (CP2) is delayed with respect
to phase of count input 1 (CP1).
The count value is decreased
by one when phase of count
input 2 (CP2) is ahead with
respect to phase of count input
1 (CP1).
Start input
Count input 2 Addition/subtraction control Subtraction count input Gate input
Output Mode N
Present value display and outputs are
maintained until reset.
Output Mode F
Present value runs continuously. Outputs
are maintained until reset.
Output Mode C
Present value is placed in reset start status
as soon as preset count is reached; the preset is not actually
displayed. Outputs are one-shot, fixed at 0.5 second, and
operate repeatedly.
Output Mode R
Present value display returns to reset start
status after expiration of one-shot time period. Outputs are
one-shot, fixed at 0.5 second, and operate repeatedly.
Reset
Preset
Digital
display
0
Control
output
Reset
Preset
Digital
display
0
Control
output
Reset
Preset
Digital
display
0
Control
output
Reset
Preset
Digital
display
0
Control
output

6
H8CA-S
H8CA-S
Dimensions
Unit: mm (inch)
■
H8CA-S Counter/Timer
■
Accessories
P2CF-11 Track Mounting/Front Connecting Socket
Conforming to VDE0106/P100
P2CF-11-E Finger Safe Terminal Type
Conforming to VDE0106/P100
P3GA-11 Back Mounting Socket
48
(1.89)
48
(1.89)
8
(0.31)
6
(0.24)
63.7
(2.51)
0.7 (0.03) 13.6
(0.54)
78
(3.07)
50
(1.97)
45 (1.77)
45
(1.77)
50
(1.97)
Note: Recommended panel
thickness is 1 to 3.2 mm.
Panel cutout conforms
to DIN 43700.
70 max.
(2.76)
7.8
(0.31)
Eleven,
M3.5 x 7.5 sems
50 max.
(1.97)
3
(0.12)
4.5
(0.18)
Two,
4.5 dia.
holes
35.4
(1.39)
31.2 max.
(1.23)
arrangement
Two,
5.4 dia. mounting holes
40±0.2
Mounting holes
7.8
(0.18)
4.5
(0.18)
35.4
(1.39)
31.2 max31.2 max
(1.23)
5
Two, 4.5
dia. holes
Eight,
M3.5 x 7.5
sems
70 max
(2.76)
50 max
(1.97)
40±0.2)
3
1.2
Terminal arrangement
Panel cutout
Terminal

7
H8CA-S
H8CA-S
Y92F-30 Panel Mounting Adapter
Adapter installs behind the panel. It is ideal for side-by-side installation. Use a P3GA-11 socket.
PFP-100N, PFP-50N Mounting Track PFP-100N2 Mounting Track
PFP-M End Plate PFP-S Spacer
58
(2.28)
48
(1.89) 8
(0.31)
91.9
(3.62)
Panel Adapter for panel
mounting Y92F-30
P3GA-11 back
connecting socket
4.5
(0.18)
L
15 25 25 25 25 1 (0.04)
27±0.1535±0.3
7.3±0.15
10
10
L: Length
1 m PFP-100N
50 cm PFP-50N
1 m PFP-100N2
4.5
(0.18)
15 25 25 25 25 15
10
10 L
16
(0.63)
29.2
(1.15)
1.05
(0.06)
1
(0.04)
35±0.3 27 24
50
(1.97)
11.5
(0.45) 10
(10.39)
M4 x 8
pan head
screw
6.2
(0.24)
10 (0.39)
1.8 (0.07)
35.3
(1.39)
35.5
1.8
1.3 (0.05)
4.8 (0.19)
5 (0.20)
16 (0.63)
12
44.3
(1.74)
16.5
(0.65)
34.8
(1.37)

8
H8CA-S
H8CA-S
Nomenclature
Programming
■
Selecting Function Mode
Select timer or counter function first. It is not necessary for power
to be ON to set this function. When the H8CA-S is shipped, it is
set to counter function, input mode “A,” output mode “N,” and pre-
set value 1.
1. Terminals 1 and 3 must be connected to select timer or
counter function using the key.
“MODE ” is lit. The function, input mode, or output mode
display will be blinking. (The Power OFF display will stop
blinking when power comes ON.)
Output display
Input mode display
Output mode display
Reset key
Advance/Write key
Present value display
Set value display
Power OFF display
Power OFF display
Setting key
Short circuit
Key function:
Resets the Present value
display and the output.
Sets the set value. Selects
timer or counter function, and
input and output modes.
Selects the function and
mode, and writes. Normally
used to write, or advance one
column when setting the set
value.

9
H8CA-S
H8CA-S
Blinking
2. Press the key to select counter or timer function, input
mode, and output mode. The characters below will flash
when the key is pressed.
■
Setting Example
1. Selecting the counter function with input
mode “A” and output mode “N.”
(Terminals 1 & 3 connected.)
“ MODE ” lights on the display.
“COUNTS” will begin blinking when the key is pressed. (Press
the keys until the desired place is reached.)
Press the key. “COUNTS” will stop blinking, and one of the
input modes will be blinking.
Press the key until input mode “A” begins blinking.
Press the
key. “A” will stop blinking, and one of the output
modes will begin blinking.
Press the key until output mode “N” begins blinking.
Disconnect terminals 1 and 3 before setting values. When termi-
nals 1 and 3 are disconnected, the “ MODE ” display will turn OFF
and output mode “N” will stop blinking.
Always disconnect terminals 1 and 3 when finished selecting the
function. Values cannot be preset if terminals 1 and 3 are con-
nected.
2. Selecting the timer function with “sec” and
output mode “N.” (Terminals 1 and 3 connected.)
If set for timer, “sec” will begin blinking when the key is
pressed. (Press the keys until the desired place is reached.)
Press the
key. “sec” will stop blinking, and one of the output
modes will begin blinking. The INPUT MODE will automcally
enter “T.”
Select the
output mode.
For the counter
function, select
the input mode.
Select counter
or timer function.
*Displayed automatically when
the timer function is selected.
COUNTS
hours
min
sec
A
B
C
N
F
C
R
• Press the key until the
desired function appears.
• Press the key to write
the desired input mode.
• Press the key until the
desired function appears.
• Press the key to write
the desired input mode.
• Press the key until the
desired function appears.
• Press the key to write
the desired input mode.
Blinking
Blinking
Blinking
Blinking

10
H8CA-S
H8CA-S
Press the key until input mode “N” begins blinking.
Disconnect terminals 1 and 3 before setting values. When termi-
nals 1 and 3 are disconnected, the “ MODE ” display will turn OFF,
and output mode “N” will stop blinking.
Always disconnect terminals 1 and 3 when finished selecting the
function. Values cannot be preset if terminals 1 and 3 are con-
nected.
■
Presetting Numeric Values
Preset values after selecting the function. Values can be preset
whether the power supply is ON or OFF.
Press the
key until the desired digit begins blinking.
Press the
key to set the desired value.
Continue pressing the and keys until the smallest digit has
been set.
To complete presetting, press the
key so that no place on the
display is blinking.
* Preset unnecessary higher digits at 0. (i.e. 000015)
Note:
The output will go ON if the set value is 0 (0.0 or 0.00) and
the displayed count is also 0 (0.0 or 0.00). In this case,
press reset after presetting, and the output will go OFF.
Blinking
High-order
digits
Low-order
digits
→→→
key: Press this key to
move to the next
column.
1
↓
2
↓
↓
9
↓
0
…
key: Press this key to
increment values.
Blinking
Blinking

11
H8CA-S
H8CA-S
Connections
■
Terminal Arrangements
In Counter Function Mode
Note:
When the control power supply is DC, terminals
➁
and
➂
are internally connected.
Mode Switch (
①
&
➂
)
When these terminals are short-circuited, set the input and output
modes with the RESET key, not the MODE key.
In Timer Function Mode
Note:
When the control power supply is DC, terminals
➁and ➂
are internally connected.
* Check the operating status of terminals ➂and ➃(see table
below) before connecting or disconnecting them.
Timer Control Terminals ➂& ➃
Be sure these terminals are not connected when using the
H8CA-S as a counter. These terminals are used as shown below
only when H8CA-S functions as a timer.
■Power Supply Connection
Connect power supply across terminals ➁and ➉and apply one
of the specified voltages. (Pay special attention to the polarity
when using a DC-operated model.)
! Caution
Do not touch the input terminals while power is supplied to the
H8CA-S or you may experience an electric shock, since this
counter does not have a built-in power transformer. Use of a
model rated at a low DC voltage is recommended when the
counter is installed at a location where the input terminals are
easily accessible.
Note: When connecting external signal input contacts and tran-
sistors, use a power supply having a power transformer
whose primary and secondary circuits are isolated from
each other with the secondary circuit not grounded, for the
input devices, to prevent current feedback and
short-circuiting.
Note: Do not arrange the peripheral circuits of the counter in ei-
ther way, as the internal circuit may be destroyed, render-
ing the counter
unoperational.
To input a signal from a single input contact to several
H8CA-Ss at the same time, be sure to connect the termi-
nals of the same numbers in parallel.
Terminals ➂& ➃Operation
Short-circuited Timer operation temporarily interrupted
when power failure accurs in control power
supply
Open Timer operation continues even when
power failure accurs in control power
supply
Reset input
Count input 1
Count input 2
Power
Supply
Reset input
Start input
Gate input
Power
Supply
24 to 240 VAC (50/60 Hz)
12 to 120 VDC
(-) (+)
H8CA-S
Input
terminals
Circuit
Insulated transformer
is necessary
Rectifier
Power supply
Correct:
H8CA-S
Input
terminals
Autotransformer
Grounding
Circuit
Power
supply
Incorrect:
Rectifier

12
H8CA-SH8CA-S
■Connection of Load Circuit
Control Output
Contact Output Type
Note: The load is turned on when the set count or time is up.
Solid-State Output Type
Note: 1. The load is turned on when the set count or time is up.
2. Be sure to connect terminal ⑧when an inductive load
is connected.
Output Delay Time
The output delay time is the time from the application of the count
input signal of the preset value until the generation of control out-
put. The delay time differs depending on counting speed and
model of control output used, as shown in the table below.
■Reset Input Connection
Voltage Input Type
Type of
control output
Max. counting speed
of rated time
Output delay
time
Contact output 30 cps Common to
hours, minutes
and seconds
30 ms max.
1 kcps 10 ms max.
Solid-state output 30 cps 30 ms max.
1 kcps 2 ms max.
Load
Power supply for load
(250 VAC max.)
Load
Power supply for load
(250 VAC max.)
(+)
(-)
Reset input contact
(Resets the unit when
turned ON.)
Reset input NPN
transistor
(Resets the unit when
turned ON.)
Reset input contact
(Resets the unit when turned ON.)
30 VDC max.
(+)
(-)
Reset input NPN
transistor
(Resets the unit
when turned OFF.)
E (30 VDC max.)*
R
*At “High”level
4.7 E
4.7 + R (V) 5 V
30 VDC max.
Reset input PNP
transistor
(Resets the unit
when turned ON.)

13
H8CA-SH8CA-S
■Connection of Count Inputs
No-Voltage Input Type
Voltage Input Type
E (30 VDC max.)*
R
Reset input NPN
transistor
(Resets the unit
when turned OFF.)
*At “High”level
4.7 E
4.7 + R (V) 5 V
Input 1
Input 2
(Counts when
turned ON.)
Input 1
Input 2 (Counts when
turned ON.)
(+)
(-)
Input 2
Input 1
(A count signal is
input when turned
ON)
30 VDC max.
30 VDC max.
(+)
(-)
Input 1 Input 2
(A count
signal is input
when turned
OFF)
* At “High”level
4.7E
4.7 + R
RR
(V) 5V
30 VDC max.
Input 2 Input 1
(A count
signal is
input when
turned
ON)
(-)
(+)
30 VDC max.
(+)
(-)
Input 1 Input 2
(A count
signal is input
when turned
OFF)
* At “High”level
4.7E
4.7 + R
RR
(V) 5V

14
H8CA-SH8CA-S
Operations
■Power Failure Detection
The H8CA-S is capable of detecting and indicating a power failure
on the display. Before power application or when a power failure
occurs, the “PW OFF ”display flickers indicating that the control
power supply is off.
Relation Among t1, t2, and Supply Voltage
When a power failure occurs, there is a period during which the
counter does not respond to the input signal, as shown below,
because of the lag in the rise in the internal circuit voltage.
Likewise, on power application, there is a period during which the
counter does not respond to the input signal, as show below,
because of a lag in the rise in the internal circuit voltage.
■Operation and Display
“OUT ”is displayed when counting or timing is complete.
When “MODE ”lights on display, terminals 1 and 3 ae connected.
In this case, it is not possible to preset values. Be sure to discon-
nect the terminals.
The H8CA-S uses “regular read format,”so the preset values can
be changed whether power is ON or OFF.
When changing the preset value during timer or counter opera-
tion, a signal will be output when the new value is the same as the
displayed value.
The front panel keys operate at a touch. Do not press the keys
with excessive force or tools, such as a screwdriver. Press only
with fingers.
After presetting values, part of the display might be blinking. The
H8CA-S will operate normally in this condition, but press the
key so that characters do not blink.
Mounting
There is no limitation in mounting direction. However, avoid
mounting the unit at an angle.
■Surface Mounting
Using P2CF-11 Front Connecting Socket
When a number of the H8CA-S are mounted in a vertical line or
when an H8CA-S is mounted close to an obstacle such as a wir-
ing duct, be sure to provide a separation of approximately 20 mm
(0.79 in) between adjacent units or between the unit and the
obstacle to allow room for engagement and disengagement of
hooks as shown below.
■Panel Mounting
Using Y92F-30 Adapter for Flush Mounting
Insert the H8CA-S into a square-cut hole from the front of the
mounting panel; insert the adapter from the rear of the H8CA-S
until the clearance between the panel surface and the adaptor is
minimized. Then secure the H8CA-S with two screws onto the
panel.
Wiring duct, etc.
Hook
Panel
20
105.7
H8CA-S
P2CF-11
H8CA-S
+
Adapter
Y92F-30 P3GA-11
91.9
8

15
H8CA-SH8CA-S
When mounting two or more counters in a vertical line, arrange all
the adapters so that the molded springs of the Y92F-30 adapters
are positioned on the right and left sides.
When mounting two or more counters in a horizontal line, arrange
all the adapters so that the molded springs of the Y92F-30 adapt-
ers are positioned on the top and bottom sides.
By attaching the P3GA-11 back connecting socket to a panel
mounted H8CA-S, wiring can be performed in the same manner
as the front connecting socket.
Removal
To remove an H8CA-S panel mounted witha Y92F-30 adapter,
loosen the two screws of the adapter, pry up the top and bottom
hooks of the adapter, and pull the H8CA-S out from the front of
the panel.
! Caution
The H8CA-S has a built-in lithium battery. Be sure to dispose
of the old H8CA-S properly, as lithium batteries are likely to ex-
plode if incinerated.
Molded spring
Molded spring
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, divide by 25.4
Cat. No. GC TMCN1 Printed in USA
OMRON CANADA, INC.
885 Milner Avenue
Scarborough, Ontario M1B 5V8
416-286-6465
OMRON ELECTRONICS LLC
One East Commerce Drive
Schaumburg, IL 60173
1-800-55-OMRON
OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.omron.com/oei
Canada - http://www.omron.com/oci
3/02 Specifications subject to change without notice
Other manuals for H8CA-S Series
1
Table of contents
Other Omron Timer manuals

Omron
Omron H3BF-N8 User manual

Omron
Omron H3DE-F User manual

Omron
Omron H5CC-AWSD User manual

Omron
Omron H5CR series User manual

Omron
Omron Ateg H3DT Series User manual

Omron
Omron H3CR User manual

Omron
Omron H5CC User manual

Omron
Omron H8GN - V1.02 User manual

Omron
Omron H2C User manual

Omron
Omron H5S - User manual
Popular Timer manuals by other brands

Kemo Electronic
Kemo Electronic B042 manual

EPH Controls
EPH Controls A17 operating instructions

LEGRAND
LEGRAND LEXIC Rex2000 D21F operating instructions

Learning Resources
Learning Resources time tracker mini user manual

Conrad
Conrad MFT1816-12 V operating instructions

HTP
HTP TIMER-DIG installation instructions