OMS Double Light Series User manual

‘’ DOUBLE LIGHT ‘’ SERIES FOR NON-MAINTAINED LUMINAIRES
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently connected to
mains power supply.
In normal operation the battery is charging and the
2 yellow LED’s light in the screen.
In case of a mains power supply failure the
luminary will light the lamp automatically in
emergency mode. When the mains power
supply is restored the device turns to normal
operation.
ÁÔÔÅÍÔÉÏÍ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line’s power load.
3. It is sugested to check every month the
indication LED for battery charging, and by pushing
the TEST button to check the emergency cirquit.
The lamp should light as long as the TEST button
is pressed. In the opposite condition contact the
installer.
4. It is sugested to check every 6 months the
minimum autononous duration by disconnecting the
mains power supply. Count the time that the lamp
lights and in case of less time than the minimum
autonomous duration the battery must be replaced.
If the measured time is considerably less than the
minimum autonomous duration
In case of battery or lamp replacement, these must
be replaced by parts of the same type
It is sugested
hours of continuous operation The frequent
failures of mains power supply reduces dramaticaly
the lamp s life time
t i
in battery recycling points. Do not
incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions bellow.
contact the installer.
.
5. to replace the lamp every 8000
.
’.
6. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
7. I s not allowed to discard batteries in to
common trash bins, they must be discarded
only
1. Detach the plastic base (located in the bottom of the luminaire) by pulling the unlock hook and pass the cables
thru the respective hole. Mount the plastic base with the included mounting accessories.
2. Connect the cables to the terminal blocks as showed.
3. Attach the luminaire by sliding it on the plastic base until the plastic hook locks, and power the luminaire.
L
230V AC
NPlastic base
NN
LL
Cables
pass thru
hole
Lock - unlock hook
EM 2772
EM 2771
220-240V AC/50-60Hz
4 VA3 VA
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
FLUORESCENT LAMP
3h90min
24h
Battery charging LED, TEST button
From full discharge
2.4V/1.5Ah 2.4V/3Ah
EN 60598-1, EN 60598-2-22
o
0 to 40 C
Up to 95%
3 years (1 year for the lamp and the battery)
332 x 100 x 205 mm
770gr. 870gr.
923512000_09_004
IP 20
85lm
8W (T5)
‘’ DOUBLE LIGHT ‘’ SERIES FOR NON-MAINTAINED LUMINAIRES
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently connected to
mains power supply.
In normal operation the battery is charging and the
2 yellow LED’s light in the screen.
In case of a mains power supply failure the
luminary will light the lamp automatically in
emergency mode. When the mains power
supply is restored the device turns to normal
operation.
ÁÔÔÅÍÔÉÏÍ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line’s power load.
3. It is sugested to check every month the
indication LED for battery charging, and by pushing
the TEST button to check the emergency cirquit.
The lamp should light as long as the TEST button
is pressed. In the opposite condition contact the
installer.
4. It is sugested to check every 6 months the
minimum autononous duration by disconnecting the
mains power supply. Count the time that the lamp
lights and in case of less time than the minimum
autonomous duration the battery must be replaced.
If the measured time is considerably less than the
minimum autonomous duration
In case of battery or lamp replacement, these must
be replaced by parts of the same type
It is sugested
hours of continuous operation The frequent
failures of mains power supply reduces dramaticaly
the lamp s life time
t i
in battery recycling points. Do not
incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions bellow.
contact the installer.
.
5. to replace the lamp every 8000
.
’.
6. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
7. I s not allowed to discard batteries in to
common trash bins, they must be discarded
only
1. Detach the plastic base (located in the bottom of the luminaire) by pulling the unlock hook and pass the cables
thru the respective hole. Mount the plastic base with the included mounting accessories.
2. Connect the cables to the terminal blocks as showed.
3. Attach the luminaire by sliding it on the plastic base until the plastic hook locks, and power the luminaire.
L
230V AC
NPlastic base
NN
LL
Cables
pass thru
hole
Lock - unlock hook
EM 2772
EM 2771
220-240V AC/50-60Hz
4 VA3 VA
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
EMERGENCY ILLUMINATION
FLUORESCENT LAMP
3h90min
24h
Battery charging LED, TEST button
From full discharge
2.4V/1.5Ah 2.4V/3Ah
EN 60598-1, EN 60598-2-22
o
0 to 40 C
Up to 95%
3 years (1 year for the lamp and the battery)
332 x 100 x 205 mm
770gr. 870gr.
923512000_09_004
IP 20
85lm
8W (T5)

‘’ DOUBLE LIGHT ‘’ SERIES FOR MAINTAINED LUMINAIRES
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently connected to
mains power supply.
In normal operation the battery is charging and the
lamp lights in maintained operation.
In case of a mains power supply failure the
luminary will light the lamp automatically in
emergency mode. When the mains power supply
is restored the device turns to normal operation.
ÁÔÔÅÍÔÉÏÍ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line’s power load.
3. It is sugested to check every month the indication
LED for battery charging, and by pushing the TEST
button to check the emergency cirquit. The lamp
should light as long as the TEST button is pressed
4. It is sugested to check every 6 months the
.
In the opposite condition contact the installer.
minimum autononous duration by disconnecting the
mains power supply. Count the time that the lamp
lights and in case of less time than the minimum
autonomous duration the battery must be replaced. If
the measured time is considerably less than the
minimum autonomous duration
In case of battery or lamp replacement, these must
be replaced by parts of the same type
It is sugested
hours of continuous operation
t i
in battery recycling points. Do not incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions bellow.
contact the installer.
.
5. to replace the lamp every 8000
.
6. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
7. I s not allowed to discard batteries in to
common trash bins, they must be discarded only
1. Detach the plastic base (located in the bottom of the luminaire) by pulling the unlock hook and pass the cables
thru the respective hole. Mount the plastic base with the included mounting accessories.
2. Connect the cables to the terminal blocks as showed.
3. Attach the luminaire by sliding it on the plastic base until the plastic hook locks, and power the luminaire.
L
230V AC
NPlastic base
Cables
pass thru
hole
Lock - unlock hook
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION
FLUORESCENT LAMP
3h90min
24h
Battery charging LED, TEST button
From full discharge
IP 20
8W (T5)
EN 60598-1, EN 60598-2-22
o
0 to 40 C
Up to 95%
3 years (1 year for the lamp and the battery)
332 x 100 x 205 mm
970gr. 1040gr.
EM 2774 EM 2775
220-240V AC/50-60Hz
2.4V/1.5Ah 2.4V/3Ah
23 VA 24 VA
315lm (230V AC) / 85lm (emergency)
NN
LLL1L1
923516000_09_004
‘’ DOUBLE LIGHT ‘’ SERIES FOR MAINTAINED LUMINAIRES
GENERAL
These luminaires are used in places where
emergency luminaires are needed.
Each luminaire must be permanently connected to
mains power supply.
In normal operation the battery is charging and the
lamp lights in maintained operation.
In case of a mains power supply failure the
luminary will light the lamp automatically in
emergency mode. When the mains power supply
is restored the device turns to normal operation.
ÁÔÔÅÍÔÉÏÍ!!!
1. Operations for installation, maintainance or
testing must be done by authorized personel only.
2. The device must be connected to the mains
power supply thru a fuse dependent by the total
amount of the line’s power load.
3. It is sugested to check every month the indication
LED for battery charging, and by pushing the TEST
button to check the emergency cirquit. The lamp
should light as long as the TEST button is pressed
4. It is sugested to check every 6 months the
.
In the opposite condition contact the installer.
minimum autononous duration by disconnecting the
mains power supply. Count the time that the lamp
lights and in case of less time than the minimum
autonomous duration the battery must be replaced. If
the measured time is considerably less than the
minimum autonomous duration
In case of battery or lamp replacement, these must
be replaced by parts of the same type
It is sugested
hours of continuous operation
t i
in battery recycling points. Do not incinerate.
INSTALLATION
To install the luminaire follow the installation
instructions bellow.
contact the installer.
.
5. to replace the lamp every 8000
.
6. In case of inactive use for a period greater than 2
months, disconnect the battery by pulling out the
battery’s connector.
7. I s not allowed to discard batteries in to
common trash bins, they must be discarded only
1. Detach the plastic base (located in the bottom of the luminaire) by pulling the unlock hook and pass the cables
thru the respective hole. Mount the plastic base with the included mounting accessories.
2. Connect the cables to the terminal blocks as showed.
3. Attach the luminaire by sliding it on the plastic base until the plastic hook locks, and power the luminaire.
L
230V AC
NPlastic base
Cables
pass thru
hole
Lock - unlock hook
Bayblend FR3010, transparent polycarbonate
TECHNICAL CHARACTERISTICS
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
BATTERY PROTECTION
MINIMUM AUTONOMOUS DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION
FLUORESCENT LAMP
3h90min
24h
Battery charging LED, TEST button
From full discharge
IP 20
8W (T5)
EN 60598-1, EN 60598-2-22
o
0 to 40 C
Up to 95%
3 years (1 year for the lamp and the battery)
332 x 100 x 205 mm
970gr. 1040gr.
EM 2774 EM 2775
220-240V AC/50-60Hz
2.4V/1.5Ah 2.4V/3Ah
23 VA 24 VA
315lm (230V AC) / 85lm (emergency)
NN
LLL1L1
923516000_09_004
This manual suits for next models
2
Other OMS Lighting Equipment manuals
Popular Lighting Equipment manuals by other brands

Kessil
Kessil H80 Tuna Flora owner's manual

US Energy Sciences
US Energy Sciences reflect-a-light KSH Series Installation procedures

Future light
Future light PRO Slim PAR-18 TCL user manual

Jered Systems
Jered Systems Galaxy Comet user guide

Snowball
Snowball SB5-SM installation instructions

ML Accessories
ML Accessories AC65136EM Installation & maintenance manual