4 / 6MANUAL
CONNECTION
SUSA conguraon
Aer connecng the AP01, the output must be
acvated in the SUSA. To do this, navigate to the
“Acousc Alarm” secon in the SUSA display menu.
There, choose “ENABLED”. The SUSA unit’s own internal
audible alarm is acvated at the same me.
AP01 funcon
A and B alarms in the re protecon area belonging to
the SUSA and its system are forwarded to the AP01.
An audible alarm in all AP01 units sounds and the red
LED goes on at the same me to indicate the fault. The
audible alarm can be muted on the AP01 by pressing
the buon on the front (MUTE). The RED stays on as
long as the system fault connues or unl the alarm is
muted in the SUSA master unit.
The green LED indicates that the AP01 has power.
Recommended cable
The unit can be connected using EKKX 1×4×0.5 for
example, with a total length of up to 100 metres.