Onan 3.0 AJ User manual


SAFETY
PRECAUTIONS
The
following
symbols
in
this
manual
signal
poten¬
tially
dangerous
conditions
to
the
operator
or
equip¬
ment.
Read
this
manual
carefully.
Know
when
these
conditions
can
exist.
Then,
take
necessary
steps
to
protect
personnel
as
well
as
equipment.
WARNING
I
Onan
uses
this
symbol
throughout
this
manual
to
warn
of
possible
serious
personal
injury.
This
symbol
refers
to
possible
equipment
damage.
Fuels,
electrical
equipment,
batteries,
exhaust
gases
and
moving
parts
present
potential
hazards
that
could
result
in
serious,
personal
injury
Take
care
in
follow¬
ing
these
recommended
procedures.
•
Use
Extreme
Caution
Near
Gasoline.
A
constant
potential
explosive
or
fire
hazard
exists.
Do
not
fill
fuel
tank
near
unit
with
engine
running.
Do
not
smoke
or
use
open
flame
near
the
unit
or
the
fuel
tank.
Be
sure
all
fuel
supplies
have
a
positive
shutoff
valve.
Fuel
lines
must
be
of
steel
piping,
adequately
secured
and
free
of
leaks.
Use
a
flexible
section
of
fuel
line
between
generator
set
and
stationary
fuel
line
in
the
vehicle.
This
flexible
section
must
be
100%
NON-METALLIC
to
prevent
electrical
currents
from
using
it
as
a
conductor.
Have
a
fire
extinguisher
nearby.
Be
sure
ex¬
tinguisher
is
properly
maintained
and
be
familiar
with
its
proper
use.
Extinguishers
rated
ABC
by
the
NFPA
are
appropriate
for
all
applications.
Consult
the
local
fire
department
for
the
correct
type
of
extinguisher
for
various
applications.
•
Guard
Against
Electric
Shock
Remove
electric
power
before
removing
protec¬
tive
shields
or
touching
electrical
equipment.
Use
rubber
insulative
mats
placed
on
dry
wood
plat¬
forms
over
floors
that
are
metal
or
concrete
when
around
electrical
equipment.
Do
not
wear
damp
clothing
(particularly
wet
shoes)
or
allow
skin
surfaces
to
be
damp
when
handling
electrical
equipment.
Jewelry
is
a
good
conductor
of
electricity
and
should
be
removed
when
working
on
electrical
equipment.
Always
use
an
appropriately
sized,
approved
double-throw
transfer
switch
with
any
standby
generator
set.
DO
NOT
PLUG
PORTABLE
OR
STANDBY
SETS
DIRECTLY
INTO
A
HOUSE
RECEPTACLE
TO
PROVIDE
EMERGENCY
POWER.
It
is
possible
for
current
to
flow
from
generator
into
the
utility
line.
This
creates
ex¬
treme
hazards
to
anyone
working
on
lines
to
restore
power.
Use
extreme
caution
when
working
on
electrical
components.
High
voltages
cause
injury
or
death.
Follow
all
state
and
local
electrical
codes.
Have
all
electrical
installations
performed
by
a
qualified
licensed
electrician.
•
Do
Not
Smoke
While
Servicing
Batteries
Lead
acid
batteries
emit
a
highly
explosive
hydrogen
gas
that
can
be
ignited
by
electrical
arcing
or
by
smoking.
•
Exhaust
Gases
Are
Toxic
Provide
an
adequate
exhaust
system
to
properly
expel
discharged
gases.
Check
exhaust
system
regularly
for
leaks.
Ensure
that
exhaust
manifolds
are
secure
and
not
warped.
Be
sure
the
unit
is
well
ventilated.
•
Keep
The
Unit
And
Surrounding
Area
Clean
Remove
all
oil
deposits.
Remove
all
unnecessary
grease
and
oil
from
the
unit.
Accumulated
grease
and
oil
can
cause
overheating
and
subsequent
engine
damage
and
may
present
a
potential
fire
hazard.
Do
NOT
store
anything
in
the
generator
com¬
partment
such
as
oil
or
gas
cans,
oily
rags,
chains,
wooden
blocks,
propane
tanks,
etc.
A
fire
could
result
or
the
generator
set
operation
(cooling,
noise
and
vibration)
may
be
adversely
affected.
Keep
the
compartment
floor
clean
and
dry.
•
Protect
Against
Moving
Parts
Avoid
moving
parts
of
the
unit.
Loose
jackets,
shirts
or
sleeves
should
not
be
permitted
because
of
the
danger
of
becoming
caught
in
moving
parts.
Make
sure
all
nuts
and
bolts
are
secure.
Keep
power
shields
and
guards
in
position.
If
adjustments
must
be
made
while
the
unit
is
running,
use
extreme
caution
around
hot
manifolds,
moving
parts,
etc.
Do
not
work
on
this
equipment
when
mentally
or
physically
fatigued.

TO
THE
OWNER
Welcome
to
the
growing
family
of
Onan
Power
users
.
.
.
We
are
proud
to
have
you
as
a
customer.
Read
this
manual
carefully
and
observe
all
safety
rules
within.
Operating
instructions,
adjustments
and
periodic
maintenance
procedures
are
given
so
that
you
.
.
,
the
owner,
can
keep
your
unit
running
like
new
and
expect
many
years
of
dependable
service
from
it.
Remember
.
.
.
any
machine,
regardless
of
design
or
type,
will
perform
only
in
relation
to
the
services
it
receives.
If
your
generator
set
needs
special
attention,
ask
your
Onan
dealer
for
assistance;
the
Onan
Parts
and
Service
Organization
has
been
factory-trained
to
provide
up-to-date
know-how
for
keeping
your
RV
electric
generating
set
“on
the
road”,
A
complete
Parts
Catalog
is
available
at
nominal
cost
and
may
be
ordered
under
924-0222.
TABLE
OF
CONTENTS
General
Information.
2
Specifications.
3
Installation
Checks.
4
Operation.
6
Adjustments.
9
Engine
Troubleshooting
Guide.
12
Maintenance.
13
Control
Troubleshooting.
17
Remote
Accessories.
19
Parts
Information.
21
EARNING
TO
PREVENT
FIRE
OR
ACCIDENT
HAZARD.
.
.
THIS
UNIT
MUST
BE
INSTALLED
ACCORDING
TO
THE
MANUFACTURER’S
DETAILED
IN¬
STALLATION
PROCEDURES
OBSERVING
ALL
MINIMUM
CLEARANCES.
TO
AVOID
POSSIBLE
PERSONAL
INJURY
OR
EQUIPMENT
DAMAGE,
ANY
INSTALLATION
AND
ALL
SERVICE
MUST
BE
PERFORMED
BY
QUALIFIED
PERSONNEL.
1

GENERAL
INFORMATION
YOUR
MANUAL
This
manual
contains
operation
and
other
informa¬
tion
to
properly
maintain,
service,
and
make
ad¬
justments
on
your
AJ
generator
set.
Study
and
follow
the
instructions
carefully.
A
well-planned
service
and
maintenance
program
will
result
in
longer
unit
life
and
better
performance.
Because
the
most
important
part
of
repair
is
diagnosis,
a
troubleshooting
chart
is
included.
Throughout
the
manual,
engine
end
of
the
generator
set
is
the
front.
Left
and
right
sides
are
determined
when
facing
the
engine
(front)
end.
When
contacting
your
Onan
dealer,
distributor,
orthe
factory
about
the
generator
set,
always
supply
the
complete
model
number
and
serial
number
as
shown
on
the
nameplate
(see
Model
Designation
following).
This
information
is
necessary
to
identify
your
generator
set
among
the
many
types
manufactured
by
Onan.
MODEL
DESIGNATION
The
following
typical
model
number
is
broken
down
into
code
segments
used
by
Onan.
3.0
AJ
-
1
R
16017
S
—I
-
r-
-r
-
\
-
T~
1
2
3
4
5
6
1.
Indicates
kilowatt
rating.
2.
Series
identification.
3.
Voltage
code
of
the
generator,
1
=
120
volts.
4.
Method
of
starting:
R—Remote
electric
starting.
5.
Factory
code
for
designating
optional
equipment,
if
any.
6.
Specification
letter
which
advances
when
the
factory
makes
production
modifications.
FUEL
REMOTE
CONTROL
PUMP
PLUG
GOVERNOR
ADJUSTMENT
VIBRATION
ISOLATOR
FUEL
SOLENOID
SHUTOFF
VALVE
FUEL
INLET
GENERATOR
OIL
DRAIN
OIL
FILL
VACU'FLO
SCROLL
START-STOP
SWITCH
CARBURETOR-
AIR
CLEANER
EXHAUST
OUTLET
CIRCUIT
BREAKER
GENERATOR
COOLING
AIR
IN
BREAKER
BOX
ENGINE
/
DRIP
PAN
TYPICAL
AJ
RECREATIONAL
VEHICLE
GENERATOR
SET
2

SPECIFICATIONS
This
manual
contains
SI
metric
equivalents
that
follow
immediately
in
parentheses
after
the
U.S.
customary
units
of
measure.
GENERAL
Nominal
Dimensions
of
Set
Height.
1
5
.
5
0
in.
(394
mm)
Width.12
in.
(305
mm)
Length.
23.19
in.
(589
mm)
Weight.160
lbs.
(73
kg)
ENGINE
DETAILS
Manufacturer.
Number
of
Cylinders.
Displacement
(cubic
inches)
Cylinder
Bore.
Piston
Stroke.
Compression
Ratio.
Engine
Speed.
Engine
Design.
Starting
System.
GENERATOR
DETAILS
Manufacturer.
OMAN
Design.
Revolving
Armature,
Two
Pole,
Inherently
Regulated,
3600
RPM
Rating
(in
watts)
60
Hertz.
3000
Watts
(3
kW)
Voltage
.120
Current
Rating
.25
Amperes
Phase.Single
Wire.
Two
Power
Factor..
Cranking
Current.
4
0
Amps
Break-away
Current.
225
Amps
CAPACITIES
AND
REQUIREMENTS
Oil
Capacity.
Recommended
Battery,
Electric
Start
Battery
Charge
Rate—Fixed.
Ventilation
Requirements
(total).
TUNE-UP
SPECIFICATIONS
Spark
Plug
Gap
.025
(0.64
mm)
Breaker
Point
Gap
(cold
setting).022
(0.56
mm)
Ignition
Timing
Reference
(cold
setting).22°
BTC
Valve
Tappet
Adjustment
(engine
cold)
Intake.011
(0.28
mm)
Exhaust.018
(0.46
mm)
.2
qts.
(1.89
litres)
12
Volt,
92
Amp/hr
(331.20
kC)
.
1-2
Amps
.50
sq.
in.
(323
cm^)
.
OMAN
.One
.
14.9
(244.16
cm3)
.2-3/4
in.
(69.85
mm)
.2-1/2
in.
(63.50
mm)
.6.25:1
.3600
RPM
Four
Cycle,
Air
Cooled,
L
Head
...
Exciter
Cranking
Generator
3

INSTALLATION
CHECKS
INSTALLATION
Nearly
all
Onan
electric
generating
sets
are
installed
by
the
motor
home
manufacturer.
Although
the
manufacturer
must
follow
safety
codes
when
install¬
ing,
certain
installation
problems
could
ariseafterthe
unit
is
installed
and
subjected
to
vibration.
There
are
a
few
areas
that
you
as
the
operatorshould
be
concern¬
ed
with.
If
in
doubt
aboutany
aspect
ofyourgenerator
set’s
operation
or
safety,
contact
your
nearest
authorized
Onan
Service
Center.
A
daily
inspection
of
your
installation
should
include
the
following;
•
Exhaust
•
Fuel
System
•
Electrical
•
Ventilation
EXHAUST
Check
for
leaks
around
manifolds,
gaskets
and
welds.
Make
sure
exhaust
lines
are
not
heating
surrounding
areas
excessively.
If
so,
have
corrected
immediately.
Remember
EXHAUST
GASES
CONTAIN
DEADLY
CARBON
MONOXIDE.
Be
sure
all
holes
to
the
inside
of
RV
from
set
compartment
are
sealed
to
prevent
poisonous
exhaust
gases
from
entering
vehicles.
FUEL
SYSTEM
With
set
running,
check
for
leaks.
Raw
fuel
will
cause
fumes
which
could
EXPLODE.
Check
around
car¬
buretor
and
fuel
pump
inlets.
Make
sure
fuel
lines
are
not
rubbing
against
anything
which
could
cause
breakage.
Inlet
hose
connection
to
fuel
filter
requires
a
clamp.
ELECTRICAL
AC
Output
Two
AC
leads.
Ml
(hot)
and
M2
(ground),
terminate
in
generator
junction
box.
These
wires
should
be
con¬
nected
to
distribution
box
with
multistrand
wire
enclosed
in
a
flexible
conduit.
Check
all
wires
(to
and
from
the
generator
set)
for
fraying
and
loose
connec¬
tions.
For
information
on
load
connections
refer
to
OPERATION
section
following.
Battery
Connections
Battery
positive
(+)
connection
connects
to
start
solenoid.
Battery
negative
connects
to
location
on
rear
of
generator.
Check
terminals
on
set
and
battery
for
clean
and
tight
connections.
4

Onan
recommends
using
a
separate
battery
for
operation
of
the
generator
set
in
addition
to
the
regular
vehicle
starting
battery.
Refer
to
individual
installation
guide
or
T-012
for
additional
information
on
battery
sharing.
WARNING^
discharged
cooling
air
for
com¬
partment
heating
since
it
could
contain
poisonous
exhaust
gases.
Grounding:
Generator
must
be
effectively
bonded
to
recreational
vehicle
chassis.
For
additional
information
on
installation
contact
your
ONAN
Service
Representative
or
request
In¬
stallation
Guide
#924-0611.
Vehicle
chassis
(frame)
ground
and
the
battery
and
generator
set
ground
should
all
be
electrically
connected
to
be
at
0
ground
potential.
All
Onan
units
are
designed
for
negative
ground
apollcation.
WARNING
ANSI
198.1
AND
recreational
vehicles
I
Insulation
must
not
reduce
the
minimum
I
clearances
as
specified
In
Figure
1
to
meet
CSA
#946
temperature
rise
requirements
for
Do
not
terminate
poisonous
carbon
monox¬
ide
exhaust
gas
under
vehicle.
Direct
exhaust
gases
away
from
window
and
door
openings.
Keep
all
openings
above
or
to
the
rear
of
exhaust
pipes
closed
when
generator
set
Is
operating.
WARNING
\
WARNING
DO
NOT
DISCONNECT
BATTERY
CABLES
FROM
BATTERY
WHILE
GENERATOR
SET
IS
CRANKING
OR
RUNNING;
SPARKS
MAY
CAUSE
AN
EXPLO¬
SION.
WARNING
Mount
the
battery
In
a
separate
compartment
from
the
set
or
any
spark-producing
device
to
prevent
fire
or
explosion.
WARNING
I
being
charged.
Do
not
smoke
while
servicing
batteries.
Lead
acid
batteries
give
off
explosive
gases
while
VENTILATION
The
biggest
enemy
of
electric
generating
sets
in¬
stalled
in
motor
homes
is
excessive
heat.
Make
sure
the
set's
air
inlet
and
outlet
are
not
plugged
with
dust,
dirt,
bugs,
leaves
or
anything
that
could
restrict
cooling
air.
IMPORTANT:
Certain
states
(particularly
California)
have
state
ordinances
pertaining
to
the
type
and
usage
of
exhaust
muffler/spark
arresters
on
internal
combustion
engines
or
engine
driven
equipment
when
used
In
a
recreational
vehicle
such
as
electric
generating
sets.
Be
sure
your
installation
meets
all
Federal,
State
and
local
codes
pertaining
to
your
unit.
Failure
to
provide
and
maintain
a
spark
arrester
may
be
in
violation
of
the
law.
WARNING
i
ENGINE
EXHAUST
GAS
(CARBON
MONOXIDE)
IS
DEADLY!
Carbon
monoxide
Is
an
odorless,
colorless
gas
formed
by
Incomplete
combustion
of
hydrocarbon
fuels.
Carbon
monoxide
is
a
dangerous
gas
that
can
cause
unconsciousness
and
is
potentially
lethal.
Some
of
the
symptoms
or
signs
of
carbon
monoxide
inhalation
are:
•
Dizziness
•
Vomiting
•
Intense
Headache
•
Muscular
Twitching
•
Weakness
and
Sleepiness
•
Throbbing
in
Temples
if
you
experience
any
of
the
above
symptoms,
get
out
into
fresh
air
immediately.
The
best
protection
against
carbon
monoxide
inhalation
is
a
regular
inspection
of
the
complete
exhaust
system.
If
you
notice
a
change
in
the
sound
or
appearance
of
exhaust
system,
shut
the
unit
down
immediately
and
have
it
inspected
and
repaired
at
once
by
a
competent
mechanic.
5

OPERATION
GENERAL
inspection:
Inspect
the
engine
visually
before
star¬
ting.
Check
for
loose
or
missing
partsorany
shipping
damage.
The
unit
may
be
tilted
during
operation
to
any
maximum
angle
not
exceeding
vehicle
operation
limitations.
Rust
inhibitor
oil
has
been
placed
In
the
engine
combustion
chamber
at
the
factory
and
may
foul
the
spark
plug.
If
the
plug
should
foul,
remove
it
and
clean
thoroughly.
Then
dry
and
replace
in
engine.
RECOMMENDED
FUEL
Use
ciean,
fresh,
unleaded
or
regular
grade
gasoline.
Do
not
use
highly
leaded
premium
fuels.
Using
unleaded
gasoline
results
in
reduced
valve
and
carbon
cleanout
maintenance.
If
the
use
of
unleaded
gasoline
is
desired,
use
regular
gasoline
for
the
first
25
hours
to
allow
the
rings
to
seat
well
for
best
performance.
Then
use
unleaded
gas¬
oline
thereafter.
If
regular
gasoline
is
used
continually,
carbon
and
lead
deposits
must
be
removed
from
the
cylinder
heads
as
required
because
of
engine
power
loss.
Unleaded
gasoline
may
be
used
safely
after
lead
deposits
have
been
removed.
Leakage
of
gasoline
in
or
around
the
com¬
partment
is
a
definite
hazard.
The
ventilation
system
should
provide
a
constant
flow
of
air
to
expel
any
accumulation
of
fuel
vapor
while
the
vehicle
is
in
transit.
Com¬
partments
must
be
vapor
tight
to
the
interior
to
keep
fumes
from
within
the
vehicle.
OIL
Check
oil
level
daily
(see
Figure
2).
Be
sure
unit
is
level
when
checking
oil.
Add
oil
to
top
of
fill
hole
if
required.
See
MAINTENANCE
section
of
this
manual
for
type
of
oil,
oil
viscosity
and
crankcase
capacity.
Do
NOT
check
oil
while
the
generator
set
is
operating.
Hot
oil
could
cause
bums
by
blowing
out
of
oil
fill
tube
due
to
crankcase
pressure.
STARTING
Push
the
start-stop
switch
to
the
start
position.
Release
the
switch
when
engine
starts.
If
engine
fails
to
start,
inhibitor
oil
used
at
the
factory
may
have
fouled
the
spark
plugs.
Remove
the
plugs,
clean
in
a
suitable
solvent,
dry
thoroughly
and
re-install.
Heavy
exhaust
smoke
when
the
engine
is
first
started
is
normal
and
caused
by
the
inhibitor
oil.
OIL
DRAIN
FIGURE
2.
OIL
LEVEL
STOPPING
Push
the
start-stop
switch
to
the
stop
position
and
hold
until
unit
stops
completely.
Automatic
Choke
An
electric
choke
provides
proper
choking
for
star¬
ting
and
running
the
generator
set.
BREAK-IN
PROCEDURE
Controlled
break-in
with
the
proper
oil
and
a
con¬
scientiously
applied
maintenance
program
will
help
to
assure
satisfactory
service
from
yourOnan
electric
generating
set.
Break-in
as
follows:
1.
One
half
hourat1/2load
(with
oneairconditioner
running).
2.
One
half
hour
at
3/4
load
(with
one
air
con¬
ditioner)
and
approximately
500
watts
additional
load.
3.
Change
crankcase
oil
after
the
first
25
hours
of
operation.
APPLYING
LOAD
If
practical,
allow
set
to
warm
up
before
connecting
a
heavy
load.
Continuous
generator
overloading
may
cause
high
operating
temperatures
that
can
damage
the
windings.
Keep
the
load
within
nameplate
rating.
BATTERY
CHARGING
The
battery
charge
rate
is
controlled
by
a
fixed
value
resistor
that
allows
a
trickle
charge
rate
of
1
-
2
amps
under
all
conditions.
6

SET
EXERCISING
Establish
an
exercise
program
if
unit
is
not
used
for
long
periods
of
time.
Start
and
run
unit,
with
a
full
load
connected
if
possible,
for
at
least
30
minutes
every
week.
This
exercise
program
will:
•
Lubricate
internal
engine
parts.
•
Assure
proper
starting
when
set
is
needed.
•
Remove
moisture.
•
Keep
carburetor
filled
with
fuel.
•
Bring
engine
up
to
operating
temperature.
•
Recharge
battery.
ELECTRICAL
OUTPUT
The
generator
set’s
wiring
provides
for
120
volts,
with
the
total
electrical
load
not
to
exceed
25
amperes.
install
any
outlets
between
generator
^distribution
panel.
120
VOLT.
2
WIRE
UNGROUNDED
LOAD
WIRE
30
AMP
^
BLACK
120
V
(FULL
NAMEPLATE
RATING)
y
WHITE
GROUNDED
LOAD
WIRE
IM1
GENERATOR
LEADS
M2
FIGURE
3.
SINGLE-PHASE,
“1R”
VOLTAGE
CODE
GENERATOR
CONNECTIONS
POWER
REQUIREMENTS
FOR
APPLIANCES
Appliance
or
Tool
Approximate
Running
Wattage*
Refrigerator.
600-1000
Electric
broom
.
200-500
Coffee
percolator.
550-700
Electric
frying
pan.
1000-1350
Hair
dryer.
350-500
Electric
stove
(per
element).
350-1000
Electric
iron.
500-1200
Radio.
50-200
Electric
water
heater.
1000-1500
Space
heater.
1000-1500
Electric
blanket.
50-200
Television.
200-600
Electric
drill.
250-750
Battery
charger.
Up
to
800
Electric
water
pump
.
500-600
Air
Conditioner.
1400-2200
Converter.
300-350
Microwave
oven.700-1500
'
-
Starting
wattages
for
motors
can
be
three
to
four
times
more
than
the
approximate
running
wattages.
HIGH
OPERATING
TEMPERATURES
1.
See
thatnothingobstructs
air
flow
to
and
from
the
set.
2.
Keep
cooling
fins
clean.
Air
housing
should
be
properly
installed
and
undamaged.
3.
Keep
ignition
timing
properly
adjusted.
LOW
OPERATING
TEMPERATURES
1.
Use
co;
•
:t
SAE
oil
for
temperature
conditions.
Change
oil
only
when
engine
is
warm.
If
an
unexpected
temperature
drop
causes
an
emergency,
move
vehicle
to
a
warm
location.
2.
Use
fresh
gasoline.
Protect
against
moisture
condensation.
Below
0°
F
(-18°
C),
adjust
car¬
buretor
main
jet
for
a
slightly
richerfuel
mixture.
3.
Keep
ignition
system
clean,
properly
adjusted
and
batteries
in
a
well
charged
condition.
4.
Partially
restrict
cool
airflow,
but
use
care
to
avoid
overheating.
EXTREMELY
DUSTY
OR
DIRTY
1.
Keep
unit
clean.
Keep
cooling
surfaces
clean.
2.
Service
air
cleaner
as
frequently
as
necessary.
3.
Change
crankcase
oil
every
50
operating
hours.
4.
Keep
oil
and
gasoline
in
dust-tight
containers.
5.
Keep
governor
linkage
clean.
6.
Clean
generator
brushes,
slip
rings,
and
com¬
mutator:
do
not
remove
normal
dark
brown
film.
Do
not
polish.
HIGH
ALTITUDE
OPERATION
For
operation
at
altitudes
of
2500
feet
(775
m)
above
sea
level,
close
carburetor
main
jet
adjustment
slight¬
ly
to
maintain
proper
air-to-fuel
ratio
(refer
to
the
ADJUSTMENTS
section).
Maximum
power
will
be
reduced
approximately
four
percent
for
each
1000
feet
(310
m)
above
sea
level
after
the
first
1000
feet.
Do
not
use
discharged
air
from
blower
scroll
for
compartment
heating.
Poisonous
gas
fumes
may
be
present.
OUT-OF-SERVICE
PROTECTION
Protect
a
generator
set
that
will
be
out
of
service
for
more
than
30
days
from
damage
caused
by
rust
or
corrosion.
Use
the
following
procedure
to
properly
protect
the
set.
1.
Run
the
generator
set
with
at
least
a
50
percent
load
until
thoroughly
warm
(usually
about
1
hour).
2.
Turn
off
fuel
supply
and
allow
the
engine
to
run
out
of
fuel.
Also
operate
the
choke
manually
as
the
engine
stops
to
help
drain
the
carburetor
completely.
warning!
7

3.
Drain
the
oil
from
oil
base
while
engine
is
still
warm.
Replace
the
oil
filter
if
so
equipped.
Replace
drain
plug
and
refill.
Attach
a
warning
tag
stating
type
and
viscosity
of
oil
used.
4.
Remove
spark
plug.
Spray
1
ounce
of
rust
in¬
hibitor
oil
(or
SAE
#10)
into
the
cylinder.
(Spray
cans
work
well
for
this
application.)
Turn
engine
over
by
hand
at
least
2
complete
revolutions.
Replace
the
spark
plug.
5.
Replace
the
air
cleaner
at
least
on
an
annual
basis.
6.
Plug
the
exhaust
outlet
to
prevent
entrance
of
moisture,
dirt,
bugs,
etc.
7.
Clean
and
oil
all
exposed
engine
parts
including
carburetor
and
governor
linkage.
8.
Wipe
generator
brushes,
slip
rings,
housing,
etc.
Do
not
apply
any
lubricant
or
preservative.
9.
Remove
the
battery
and
store
in
a
cool
dry
place.
Coat
the
battery
terminals
and
cable
connections
with
vasoline
or
grease
to
prevent
any
corrosion.
Recharge
the
battery
at
least
monthly
or
maintain
with
a
trickle
type
battery
charger.
10.
P
r
ovide
a
suitable
cover
if
the
unit
is
exposed
to
the
elements.
RETURNING
THE
UNIT
TO
SERVICE
1.
R
e
m
o
v
e
the
cover
and
all
protective
wrapping.
Wipe
the
oil
film
off
all
exposed
engine
parts.
Remove
the
plug
from
the
exhaust
outlet.
2.
Visually
inspect
the
unit
for
any
damage.
Check
to
be
sure
the
carburetor
and
governor
linkage
are
free.
Remove
the
generator
end
bell
band
and
check
to
be
sure
the
brushes
work
freely
in
their
holders.
3.
Check
the
tag
to
ensure
oil
of
the
proper
brand
and
grade
has
been
installed.
Check
the
oil
level.
4.
Install
the
battery
(be
sure
battery
is
fully
charg¬
ed),
observing
proper
polarity.
Ground
is
negative.
5.
Remove
spark
plugs,
clean
and
gap.
Turn
the
engine
over
by
hand
several
times.
Reinstall
spark
plugs.
6.
Remove
all
load
and
start
the
generator
set
at
the
unit.
Initial
start
may
be
slow
due
to
oil
or
rust
inhibitor
in
the
cylinders.
Excessive
smoke
and
rough
operation
will
occur
until
the
oil
or
rust
inhibitor
is
burned
off.
7.
Apply
a
50
percent
load
after
the
set
runs
smooth.
Allow
the
generator
set
to
warm
up
(1
hour)
with
the
load
connected.
Check
speed
and
voltage.
8.
Unit
is
now
ready
for
service.
GENERATOR
MAINTENANCE
The
generator
normally
needs
little
care
other
than
a
periodic
check
of
the
brushes,
commutator
and
collector
rings.
If
a
major
repair
job
on
the
generator
should
become
necessary,
have
the
equipment
checked
by
a
competent
electrician
who
is
thorough¬
ly
familiar
with
the
operation
of
electric
generator
equipment.
8

ADJUSTMENTS
TIMING
AND
BREAKER
POINTS
Ignition
points
should
break
contact
at
22°BTC
(see
Figure
4).
Proper
22°
BTC
timing
is
obtained
by
setting
breaker
points
and
checking
with
a
timing
light.
22°
BTC
timing
can
be
checked
at
timing
hole
on
the
front
of
blower
housing
("D")
or
at
another
timing
hole
on
the
side
of
the
blower
housing
(“C”)
just
above
the
governor
adjustment.
Breaker
point
setting
may
vary
from
.017-.024
inch
to
get
proper
22°
BTC
timing.
1.
Turn
engine
over
slowly
in
a
clockwise
direction
until
the
TC
mark
appears
in
the
middle
of
the
window
“D”
(Figure
4).
Turn
slightly
beyond
this
point
to
ensure
points
are
fully
open.
2.
Remove
cover
on
breaker
point
box,
loosen
screws
“A”
and
turn
cam
“B”
to
obtain
.020
inch
setting.
Use
a
clean,
flat
feeler
gauge.
3.
Retighten
screws
“A”,
replace
breaker
box
cover
and
connect
a
timing
light.
With
unit
running
and
warmed
up,
notch
should
appear
In
timing
reference
hole
“C".
(If
front
of
blower
scroll
is
accessible,
direct
the
timing
light
to
small
hole
"D”.
22°
BTC
mark
should
appear
in
this
hole.)
CARBURETOR
Initial
Adjustment
Adjust
initially
by
turning
idle
and
main
(load)
adjustment
screws
gently
onto
their
seats.
Then
back
off
idle
screw
1-1/4
turn
and
main
screw
1-1/4
turns.
This
adjustment
will
allow
initial
starting
of
the
generator
set.
Adjustment
1.
Start
unit
and
allow
it
to
warm
up.
2.
Remove
all
AC
loads
from
the
generator
set.
3.
Connect
a
voltmeter
to
the
AC
leads
or
use
a
plug¬
in
voltmeter
inserted
into
one
of
the
receptacles.
Hold
governor
arm
to
minimum
speed
and
adjust
the
throttle
stop
screw
so
voltmeter
indicates
75-
80
volts.
4.
With
voltmeter
still
connected,
hold
governor
arm
against
throttle
stop
and
turn
idle
adjustment
screw
in
until
voltage
drops.
Then
turn
it
out
until
the
highest
voltage
is
obtained.
Release
governor
arm.
Engine
should
accelerate
to
governed
speed
and
become
stable.
NOTCH
REFERENCE
TIMING
HOLE
FIGURE
4.
IGNITION
AND
TIMING
ADJUSTMENTS
9

FIGURE
5.
CARBURETOR
ADJUSTMENTS
5.
Connect
a
full
rated
load
to
the
generator
set.
(Use
RV
appliances
or
Onan
load
test
panel.)
6.
Adjust
main
(load)
adjustment
screw
to
get
the
highest
voltage.
Remove
load
and
hold
governor
arm
to
minimum
speed.
Release
governor
arm
and
observe
acceleration.
If
surging
occurs
at
governed
speed,
open
the
main
jet
slightly.
If
surging
continues,
adjust
governor
sensitivity.
Some
units
do
not
have
a
main
(load)
adjustment.
Setting
is
factory
fixed.
ELECTRIC
CHOKE
Normal
choke
setting
is
1/8
inch
from
its
fully
closed
position
at
70°
F.
If
temperature
changes
occur,
requiring
choke
adjustment,
proceed
as
follows;
1.
Loosen
two
outer
screws
at
“A”
(Figure
6).
2.
Turn
the
cover
assembly
counterclockwise
to
decrease
choking
(leaner
mixture).
3.
To
increase
choking
(richer
mixture),
turn
cover
assembly
clockwise.
4.
Tighten
both
screws
to
lock
cover
in
place.
FIGURE
6.
ELECTRIC
CHOKE
ADJUSTMENT
10

GOVERNOR
The
governor
controls
engine
speed
by
opening
or
closing
the
throttle
according
to
the
load
taken
off
the
set
(Figure
7).
The
engine
speed
also
determines
voltage
and
frequency
of
the
generator
current.
Before
readjusting
the
governor
linkage,
check
for
binding
at
the
linkage
or
throttle.
1.
With
unit
stopped,
disconnect
governor
control
rod
from
hole
(E)
on
throttle
shaft.
While
holding
throttle
wide
open,
adjust
length
of
governor
control
rod
so
center-to-center
distance
is
1/8
inch.
Change
governor
control
rod
length
by
turning
the
threaded
rod
(A)
near
the
ball
joint.
When
1
/8
inch
distance
is
reached,
reconnect
rod
at
point
E.
2.
Run
the
set
with
a
load
to
thoroughly
warm
it
up.
3.
Connect
a
voltmeter
across
the
generatoroutput.
With
the
set
operating
at
no
load,
adjust
the
speed
nut
(C)
until
voltmeter
reads
126volts.
When
afull
rated
load
is
applied,
voltage
should
not
fall
below
110
volts.
4.
If
voltage
falls
below
108
volts
(with
full
load),
loosen
the
hex
nuts
on
sensitivity
spring
stud
and
screw
stud
(D)
inward
(clockwise)
or
recheck
step
1.
If
voltage
is
within
limits,
buttendsto
surge
(alternately
increases
and
decreases),
turn
the
spring
stud
outward
(counterclockwise)
until
voltage
stabilizes.
5.
Retighten
nuts
on
lowerspring
stud
while
holding
stud
in
position
with
a
screwdriver.
Turning
sensitivity
stud
(D)
in
or
out,
usually
requires
a
correspon¬
ding
change
in
speed
adjustment
nut
(C).
Table
in
Figure
7
shows
proper
voltage
speed
and
frequency
ratings.
r
/
I
\
^
j
/
(
I
1
\
\
\
\
^
.
\
^
V-
226
FIGURE
7.
GOVERNOR
ADJUSTMENTS
11

nHDHaH
■■□
■
■
a
■■□
■
■
□
I
■■
i
Shho
■■■
■
■
□
I
■
■
□
iUI
■■
■
n
i
^mmD~
'
'
"
*
V
FUEL
SYSTEM
riL
E3C1HH
!«
■
■■
■
■
■
D
D
B
Broken
Valve
Spring
_
Valve
or
Valve
Seal
Leaking
Wrone
Bearinc
Clearance
COOLING
SYSTEM
(AIR
COOLED)
COOLING
SYSTEM
(WATER
COOLED)

MAINTENANCE
Regularly
scheduled
maintenance
is
the
key
to
lower
operating
costs
and
longer
service
life
for
the
unit.
The
following
schedule
can
be
used
as
a
guide.
However,
actual
operating
conditions
under
which
a
unit
is
run
should
be
the
determining
factor
in
establishing
a
maintenance
schedule.
When
operating
in
very
dusty
or
dirty
conditions,
some
of
the
service
periods
may
have
to
be
reduced.
Check
the
condition
of
the
crankcase
oil,
the
*
filters,
etc.
frequently
until
the
proper
service
time
periods
can
be
established.
For
any
abnormalities
in
operation,
unusual
noises
from
engine
or
accessories,
loss
of
power,
overheating,
etc.,
contact
your
nearest
dealer.
I
WARNING
I
Always
allow
generator
set
to
cool
off
before
performing
any
maintenance
or
installation
work
on
the
set.
Working
on
a
hot
set
could
cause
severe
burns.
PERIODIC
MAINTENANCE
SCHEDULE
SERVICE
THESE
ITEMS
AFTER
EACH
CYCLE
OF
INDICATED
HOURS
8
50
100
200
400
General
Inspection
X1
Check
Oil
Level
X
Check
Battery
Water
Level
x2
Blow
Out
Generator
with
Dry
Air
x2
Change
Crankcase
Oil
(10W40)
x2
Replace
Air
Cleaner
x2
Replace
Spark
Plug—Gap
.025"
x3
Clean
Crankcase
Breather
x2
T
une-Up
x4
Check
Breaker
Points
x4
Check
Ignition
Timing
x4
Clean
Cooling
Fins
x2
Remove
Carbon
&
Lead
from
Cylinder
Head
x4
Adjust
Tappets
x4
Replace
Fuel
Filter
X
Check
Generator
Brushes
(Replace
if
Necessary)
As
Required
x1
-
Check
for
exhaust
leaks,
fuel
leaks,
proper
mounting,
etc.
x2
-
Perform
more
often
in
extremely
dusty
conditions.
x3
-
Replace
at
beginning
of
season
or
every
100
hours.
x4
-
For
detailed
maintenance,
contact
your
nearest
authorized
Onan
Service
Center.
All
exhaust
system
connections
MUST
be
checked
regularly
for
any
leaks
and
tightened
as
necessary.
Do
NOT
terminate
exhaust
pipe
under
vehicle
or
near
any
window
or
door
openings.
Inspect
the
vapor
tight
seals
around
all
openings
made
in
the
set’s
compartment
for
wiring,
conduit,
etc.,
to
prevent
entrance
of
any
noxious
fumes
to
motor
home
interior.
WARNING
i
13

OIL
LEVEL
Check
the
oil
level
daily
or
at
least
every
eight
operating
hours.
Oil
should
just
start
to
overflow
from
fill
hole
when
crankcase
is
full.
Check
oil
when
set
(or
vehicle)
is
level.
OIL
CHANGE
The
oil
drain
valve
is
located
on
the
side
(near
the
bottom)
of
the
oil
base.
Change
oil
initially
at
25
operating
hours;
change
every
50
hours
after
that.
Extremely
dusty
conditions
require
more
frequent
oil
changes.
See
Figure
8.
Be
sure
to
fill
the
crankcase
with
oil
to
the
“FULL”
mark
on
the
oil
level
indicator.
Use
oil
with
the
API
(American
Petroleum
Institute)
designation
SE
or
SE/CC.
Oil
should
be
labeled
as
having
passed
MS
Sequence
Tests
(also
known
as
having
passed
ASTMG-1V
Sequence
Tests).
Refer
to
oil
chart
for
recommended
viscosity
and
temperature.
The
engine’s
oil
capacity
is
2
quarts.
1°C
-30
-20
-10
6
10
20
30
40
TEMPERATURE
RANGE
YOU
EXPECT
BEFORE
NEXT
OIL
CHANGE
Oil
consumption
may
be
higher
with
a
multigrade
oil
than
a
single-grade
oil
if
both
oils
have
comparable
viscosities
at
210°F
(99°C).
Therefore,
single
grade
oils
are
generally
more
desirable
unless
anticipating
a
wide
range
of
temperatures.
Use
the
proper
grade
oil
for
the
expected
conditions.
When
adding
oil
between
FIGURE
8.
OIL
FILL
AND
DRAIN
changes,
use
the
same
brand
as
in
the
crankcase.
Various
brands
of
oil
might
not
be
compatible
when
mixed.
Use
of
the
same
grade
and
quality
of
oil
as
that
used
in
your
recreational
vehicle
engine
is
acceptable
as
long
as
unit
is
serviced
regularly
and
oil
meets
re¬
quirements
shown
in
chart.
WARNING
I
check
oil
while
the
generator
set
is
whhhhhJ
operating.
Hot
oil
could
cause
bums
by
blowing
out
of
oil
fill
tube
due
to
crankcase
pressure.
FUEL
FILTER
An
inline
fuel
filter
mounts
on
inlet
side
of
fuel
pump.
Replace
at
least
every
100
hours
or
when
poor
performance
is
suspected.
When
removing
or
replacing
fuel
solenoid
)
.
.
.
.
.
.
.
.
1
always
use
wrench
on
hex
(A),
Figure
9.
Do
not
exert
turning
force
on
B
because
solenoid
will
be
damaged
internally.
FIGURE
9.
INLINE
FUEL
FILTER
FUEL
SOLENOID
Evaporative
control
systems
on
late
model
motor
homes
require
a
positive
fuel
shutoff
valve
to
prevent
the
generator
set
from
flooding
when
not
in
use.
AIR
CLEANER
Replace
air
cleaner
every
100
hours
(sooner
in
dusty
conditions).
Element
used
is
a
dry
type
and
requires
no
oil.
Some
dirt
can
be
removed
by
tapping
element
against
a
flat
surface.
AIR
CLEANER
COVER
ELEMENT
BASE
PLATE
FIGURE
10.
AIR
CLEANER
ELEMENT
14

BATTERY
CARE
To
increase
battery
life,
the
operator
can
perform
a
number
of
routine
checks
and
some
preventive
maintenance.
1.
Keep
the
battery
case
clean
and
dry.
2.
Make
sure
the
battery
cable
connections
are
clean
and
tight.
Use
a
terminal
puller
when
removing
cables
for
any
reason.
3.
Coat
the
battery
terminals
with
a
mineral
grease
or
petroleum
jelly
to
reduce
corrosion
and
oxida¬
tion.
4.
Identify
each
battery
cable
to
be
positive
or
negative
before
making
any
connection.
Always
connect
the
ground
(negative)
cable
last.
5.
Maintain
the
electrolyte
level
by
adding
water
(drinking
quality
or
better)
as
needed
for
filling
to
split
level
marker.
The
water
ingredient
of
the
electrolyte
evaporates,
but
the
sulphuric
acid
ingredient
remains.
Therefore,
add
water,
not
electrolyte.
6.
Avoid
overcharging
when
recharging.
Stop
the
boost
charge
when
the
specific
gravity
is
1.260
and
the
electrolyte
is
80°F
(26.7°C).
GOVERNOR
LINKAGE
Check
linkage
periodically
for
freedom
of
movement.
Disconnect
ball
joint
and
clean.
SPARK
PLUG
Replace
spark
plug
every
100
hours
or
at
least
once
a
year.
A
badly
leaded
plug
will
cause
misfiring,
poor
operation
or
stopping
when
a
load
is
applied.
•
Black
deposits
indicate
a
rich
mixture.
•
Wet
plug
indicates
misfiring.
•
Badly
or
frequently
fouled
plug
indicates
the
need
for
a
major
tune-up.
COOLING
SYSTEM
Check
cooling
fins
and
shrouds
at
least
every
200
hours
or
annually.
Remove
all
foreign
material
(bugs,
dirt,
oil,
leaves).
Also
check
generator
air
inlet
and
air
outlet
for
restrictions
which
can
cause
overheating.
{
CAUTION
1
operate
unit
without
the
cooiing
shrouds
instalied;
overheating
wiii
occur
causing
engine
damage.
BREATHER
VALVE
Every
100
hours
check
the
breather
valve
by
removing
breather
tube
and
examining
the
valve
in
the
crankcase.
The
ball-check
valve
must
move
freely
in
the
valve
housing
chamber.
If
there
is
any
excessive
accumulation
of
sludge
or
dirt,
replace
the
breather
valve.
BREATHER
TUBE
FIGURE
12.
CRANKCASE
BREATHER
GENERATOR
After
approximately
500
hours
of
operation,
remove
the
generator
brushes
and
inspect
for
wear
and
scoring.
To
remove
the
brushes,
unscrew
the
brush
retainers
(Figure
13)
and
pull
the
brush
and
spring
assembly
out
of
the
bell
housing.
The
four
smaller
retainers
hold
the
slip
ring
brushes,
and
the
two
larger
retainers
secure
the
commutator
brushes.
15

WORN
NEW
FIGURE
14.
BRUSH
REPLACEMENT
FIGURE
13.
BRUSH
LOCATION
The
brush
faces
should
have
a
smooth,
shiny
surface
to
them,
with
no
deep
grooves
present.
If
serious
grooves
are
noted,
the
commutator
and
slip
rings
should
be
inspected
to
determine
the
cause
for
correction
purposes.
If
slip
ring
and
commutator
dressing
is
required,
your
nearest
Onan
Service
Center
is
best
equipped
to
handle
the
job.
If
brushes
appear
to
be
in
satisfactory
condition,
and
are
at
least
5/8
inch
in
length,
replace
them
in
the
holders
from
which
they
were
removed.
Work
the
brushes
up
and
down
in
the
holders
to
be
sure
there
is
no
sticking
or
binding.
If
they
bind,
clean
out
the
holders
with
air
pressure
or
a
small
bristle
brush
until
the
brushes
slide
freely
in
the
holders.
Replace
the
brush
retainer
screws.
If
brushes
are
worn
to
less
than
5/8
inch
length,
replace
with
new
brushes
(see
Figure
14).
Every
500
hours,
remove
the
brushes
and
blow
out
the
dust
in
the
generator
by
blowing
compressed
air
(not
over35
psi)
into
allthebrush
holders
with
the
brushes
removed.
Service
more
often
if
operating
in
extremely
dusty
conditions.
Replacement
brushes
are
shaped
to
fit
the
curvature
of
the
commutator
and
seldom
need
sanding
to
seat
properly.
If
sparking
does
occur,
run
set
at
light
loads
until
new
brushes
are
properly
seated.
Never
use
emery
cloth
or
metal
files
to
seat
brushes.
Use
only
brushes
of
correct
part
number
(see
your
Onan
Service
Center).
Replace
brushes
in
the
same
position
in
holder
as
they
were
originally.
EXHAUST
SPARK
ARRESTER
Exhaust
spark
arresters
are
necessary
for
SAFE
OPERATION.
All
require
periodic
clean-out
(every
50
to
100
operating
hours)
to
maintain
maximum
ef¬
ficiency.
Some
state
and
federal
parks
require
them.
To
clean
spark
arrester
remove
pipe
plug
in
bottom
of
muffler.
Run
set
under
load
for
5
minutes.
Replace
plug.
ASSEMBLY
TORQUES
LB-FT
N*m
Gearcase
Cover
10-13
(13.6-
17.6)
Cylinder
Head
Stud
Nuts
(Cold)
24-26
(32.5
-
35.3)
Rear
Bearing
Plate
Screws
15-20
(20.3
-
27.1)
Connecting
Rod
Bolt
10-12
(13.6
-
16.3)
Flywheel
Mounting
Screw
35-40
(47.5
-
54.2)
Oil
Base
Mounting
Screws
25-30
(33.9
-
40.7)
Generator
Through
Stud
Nut
12-15
(16.3
-
20.3)
Armature
Through
Stud
Nut
25-30
(33.9
-
40.7)
Crankshaft
Blower
Housing
20-25
(27.1
-
33.9)
Fuel
Pump
Mounting
Screw
10-15
(13.6
-
20.3)
Intake
Manifold
Mounting
Screw
15-20
(16.3
-
27.1)
Oil
Pump
Mounting
Screw
7-9
(9.5-12.2)
16

CONTROL
TROUBLESHOOTING
PROBLEM
PROBABLE
CAUSE
REMEDY
FAILS
TO
CRANK
1.
Bad
Battery
Connection
1
Clean
and
tighten
all
battery
and
cable
connections.
2.
Low
Battery
2A
Check
specific
gravity.
Recharge
or
replace
battery
if
necessary.
2B
Reverse
current
diode
(CR1)
may
be
shorted
or
open
causing
a
drain
on
the
battery.
R2
may
be
open.
3.
Faulty
Start
Solenoid
(K1)
3
Push
start
switch.
Check
start
solenoid
“SI"
terminal
voltage
to
ground.
When
battery
voltage
at
start
solenoid
'‘B
+
'’
terminal
is
present,
battery
voltage
should
also
appear
at
"SI
’’
terminal;
if
not,
replace
start
solenoid
4.
Faulty
Start
Switch
4.
Jumper
switch
(#3
terminal)
to
ground.
If
solenoid
energizes,
replace
switch.
CRANKS
SLOWLY
1.
Bad
Battery
Connection
1
See
1
above
(FAILS
TO
CRANK)
2.
Low
Battery
2
See
2
above
(FAILS
TO
CRANK)
CRANKS
BUT
WONT
START
1
Blown
Fuse
(F2)
1.
Replace
fuse
(F2)
on
control.
2.
Faulty
Fuel
Solenoid
Or
Fuel
Pump
On
later
models,
fuel
solenoid
is
an
integral
part
of
fuel
pump.
2,
Fuel
solenoid
must
open
during
cranking
and
running.
Check
by
removing
steel
line
from
carburetor
and
crank
engine.
If
fuel
solenoid
isopen.
fuel
will
pulsateout
of
this
line.
If
itdoes
not.
the
fuel
solenoid
and
fuel
pump
must
be
checked
separately
to
determine
defective
part
1
WARNING
^
extreme
care
for
this
test.
Direct
fuel
sure
area
is
well
ventilated
to
prevent
accumulation
of
gasoline
fumes.
3.
Faulty
Ignition
3.
Check
to
see
if
points
open
and
close
during
cranking.
If
they
do
not
open
and
close,
adjust
and
set
points.
Plug
and
plug
wires
must
be
in
good
condition
Voltage
at
ignition
coil
negative
terminal
(-)
must
alternate
from
+12
volts
to
zero
volts
as
points
open
and
close
during
engine
cranking.
4
Inoperative
Choke
4
With
engine
not
running,
check
choke
vane
movement
by
pushing
choke
lever
arm.
Choke
must
be
in
closed
position
with
cold
engine,
and
must
be
free
to
move
against
bimetal
spring
As
engine
warms
up,
bi-metal
spring
relaxes
and
allows
choke
vane
to
open
fully.
The
lever
will
pulsate
as
engine
warms
up.
See
ADJUSTMENT
section
5
Faulty
Crank
Ignition
Relay
(K2)
5
Check
voltage
from
relay
terminal
"4
“
to
ground
while
cranking
unit
Battery
voltage
should
appear
at
this
terminal.
If
not.
check
for
voltage
at
relay
terminals
“I
'
and
'‘2’
If
battery
voltage
is
present
at
terminals
1
and
2,
but
not
at
4.
replace
relay.
If
not
voltage
appears
at
terminals
1
and
2
on
relay
while
cranking,
check
wiring
between
start
solenoid
(K1)
and
crank
ignition
relay
(K2).
UNIT
STARTS,
BUT
STOPS
IMMEDIATELY
AFTER
RELEASING
START
SWITCH
Si
1
Resistor
R1
may
be
open.
2
Run
Ignition
Relay
K3
3
Low
Oil
Level
4
S3
Low
oil
pressure
switch
may
be
defective.
1
Check
voltage
on
both
sides
of
R1
With
set
running
voltage
should
be
24-32
volts
DC
2
Check
voltage
on
both
sides
of
K3
Should
be
12
volts
3
Check
oil
level.
If
low
or
empty,
refill
to
proper
level
4
Check
S3.
Switch
should
close
with
set
running
at
10
lbs.
minimum
oil
pressure
UNITSRUNSTHEN
STOPS
1.
Low
Oil
Level
1.
Check
oil
level.
If
low
or
empty,
refill
to
proper
level.
UNITS
RUNS
BUT
SURGES
1
Stuck
Choke
1.
See
4
above
(CRANKS
BUT
WONT
START)
2
Governor
Not
Adjusted
Properly
2.
Readjust
governor.
UNITS
STOPS
1.
Faulty
Ignition
1
See
3
above
(CRANKS
BUT
WONT
START)
2.
Out
of
Fuel
2.
Refill
fuel
tank.
3.
Low
Oil
Level
3.
Check
oil
level.
If
low
or
empty,
refill
to
proper
level.
REMOTE
RUNNING
TIME
METER
OR
GENERATOR
LAMP
INOPERATIVE
1.
Blown
Fuse
(FI)
1
Replace
FI
fuse
on
control
i;

A1.Control
Assembly
A2.Delux
Remote
Control
A3.Standard
Remote
Control
S1.Start-Stop
Switch
F1,
F2.
Fuse
(5-amp,
32
Volt)
K1.
Start
Solenoid
K2.Relay-Crank
Ignition
K3.Relay-Run
Ignition
E1.Choke
-
Onan
E2.Spark
Plug
E4.Fuel
Shut
Off
Solenoid
T1.Ignition
Coil
52
.
B
r
eaker
Points
Assembly
53
.
S
w
i
t
ch
-
Low
Oil
Pressure
G1.
Generator
CB1
.30
Amp
Circuit
Breaker
R2.Resistor
(10-Ohm,
45
Watt)
BT1.Battery
-
12
Volt
FIGURE
15.
CONTROL
SYSTEM
SCHEMATIC
18
Table of contents
Other Onan Portable Generator manuals

Onan
Onan 50.0DDB-15R Series Instruction Manual

Onan
Onan CCK Series User manual

Onan
Onan GenSet NHL User manual

Onan
Onan BGE User manual

Onan
Onan MDJF Series Instruction Manual

Onan
Onan DYD Series User manual

Onan
Onan NH User manual

Onan
Onan aj series User manual

Onan
Onan MCCK Instruction Manual

Onan
Onan Protec Series User manual

Onan
Onan HDCAC User manual

Onan
Onan CCK User manual

Onan
Onan MGKBC Series User manual

Onan
Onan Emerald Plus BGE Series User manual

Onan
Onan JB Series User manual

Onan
Onan MJA Series User manual

Onan
Onan UF Series Instruction Manual

Onan
Onan KVC Series User manual

Onan
Onan RDJF Series User manual

Onan
Onan K5000 User manual