Section
4.
Ventilation
GENERAL
Theinstallationofboatventilationsystemsmustmeetall
Coast Guardand
NFPA
requirements. Establishingthe
correct
air
flow quantity
is
particularlyimportantwith
small compartments under 1000cubicfeet
(28
m3), or
installationsinclosequarters. Ventilationsystemsmeet-
ingCoast Guard requirements for gasolineengines in
passenger vessels (Table 4-1) will normally suffice,
however specialconsiderationmust begivento com-
partment conditionsduring operation.
TABLE
4-1.
PASSENGERVESSEL
VENTILATION REQUIREMENTS
SIZE
OF
MINUTESREQUIRED
COMPARTMENT TO EXCHANGETOTAL
Cu.
Ft.
(m3)
AIR VOLUME
Less
than
500
(14)
2
500
to
1000 (14
to
28)
1000
to
1500(28
to
42)
1500
and
Up
(42
and
Up)
3
4
5
REQUIREMENTS
Marinegeneratorsetsmusthaveairventilationforthree
very important reasons:
1.
Toremoveflammableorotherharmfulgases.
Coast
Guard regulations require power blowers in the
generator set and propulsionengine rooms be run
atleastfourminutespriortostartingtheengineand
during operation. The operator must also inspect
the engine room
for
the presence
of
fuel vapors
prior to starting, especially when gasoline fueled
equipmentisused(seetextunderCoastGuardand
NFPA
Requirements).
2.
To
provide engine combustion
air
and generator
coolingair.
CoastGuardregulationsrequirepower
exhausters in all installations, and one blower in
each exhaust duct. Exhausters must have an air
capacity
1-1
/2
to
2
timesthe minimum generator
set total air requirements. The
MCE
generator set
requiresatotaloperationminimumof 146cubicfeet
perminute
(4.2
m3/min).
3.
To
control compartment temperature during
gensetoperation.
Thiswillavoidoverheatingwhich
can resultinshutdownfromvapor lock,engineand
related control component damage, and power
loss.
As
a general rule, the operating environment
for a gasoline genset should not be higher than
14OOF (60OC) maximum. Lower temperatures are
recommended. Often an operating power blower
mayberequiredto maintaintemperaturewhenthe
gensetisoperating, especiallywhen theboat isnot
moving.
The compartment must have air inlets and outlets to
providethis air. Inletducts shouldhave cowlsor equi-
valentfittings of twicethearea of the duct, largerifthe
opening
is
screened.
Do
not use recessed
or
flushed
inlets,or louveredtransom outlets.
Ifthegasolinefueltankisinaseparatecompartment,
it
also must beventilated.
COAST
GUARD
AND NFPA
REQUIREMENTS
Bothorganizationsrequireat least
two
inletductsand
two
outlet ducts extending to the bilge for gasoline
generator set installations in
a
closed Compartment.
When not in a closed compartment, at leastone duct
shouldbe installedinthe fore section of the boat and
another aft. The
NFPA
recommends a vent size of at
least
two
square inches per foot
(42.3
cm2/m) of boat
beamfor totalinletarea andtotaloutetarea.
BoatsclassifiedaspleasurevesselsbytheCoastGuard
musthavesufficientventilationto eliminateaccumula-
tionofflammablegases. Boatsunder
65
feet
(20
m) long
classifiedas passenger vessels requireventilationbe
sufficienttochangethe compartmentairwithinagiven
time interval(Table 4-1).
Forpassengervessels,theCoastGuardrecommendsa
mechanicalexhaustingsystemtomeettherequirement
in Table 4-1. The exhaust blower motors should be
outsidethe compartment.
If a gasolinefuel tank is in aseparate compartment, it
must be ventilated to the same requirements as the
enginecompartment.
4-1