F-1000 Series Turbine Flow Meters
MAINTENANCE AND CLEANING
727.447.6140 Page 3 onicon.com
ON
I
CON
Flow and Energy Measurement
F-1134 AND F-1101 INLINE STYLE METERS
The F-1134 and F-1101 meters are in-line style, access to the turbine assembly is not possible without removing the
turbine assembly from the meter brass body. Cleaning should be done without removing the turbine assembly from the
meter body. If the turbine assembly needs to be removed, please contact ONICON for assistance.
1. Use a ashlight to visually inspect the turbine for debris, dirt or damage.
2. Use tweezers to remove any foreign material stuck or wrapped in the turbine.
3. Flush water through the ow meter brass body to wash out smaller debris and dirt.
CAUTION
Use care not to get water in or on the electronics housing of the meter.
4. To remove additional dirt, place the ow meter body in a shallow pan and ll to the top of the body opening with
cleaner. Let the meter soak for anywhere between 5 minutes to a few hours.
• If using household cleaners, soak between ve minutes to a few hours, depending on scale build up.
• If using Muriatic Acid and water solution, soak 1 - 5 minutes maximum.
• After soaking and rinsing, put some of the cleaning solution or soap on a small brush and lightly brush around the
For hard to remove mineral deposits and excessive dirt:
1. Place enough cleaning solution into a container to cover the entire turbine assembly.
2. Place the assembly into the solution and let soak.
• If using household cleaners, soak between ve minutes to a few hours, depending on scale build up.
• If using Muriatic Acid and water solution, soak 1 - 5 minutes maximum.
• After soaking and rinsing, put some of the cleaning solution or soap on a small brush and lightly brush around the
ends of the turbines, exposed bearings & shaft, and the turbine support brackets.
• After cleaning the ow meter, rinse thoroughly to remove all cleaner and dirt from the meter stem and turbine
assembly. Use a wire brush to clean pipe dope or thread tape out of the threads on the hot tap adapter and ush
with water to rinse.
CAUTION
Use caution not to get water in or on the electronics housing of the meter.
3. With the turbines exposed, blow the excess water o of the turbine assembly. Hold the ow
meter so the turbines are as a ship’s propeller would be and blow gently on the turbines to
see if they turn freely. If not, clean again. If they spin freely, the turbine assembly has been
successfully cleaned.
4. Apply a small amount of silicone grease to the meter stem and slide the hot tap adapter up
and down to lubricate the o-ring seal in the hot tap adapter and reinstall the ow meter in
the pipe. For more information on installation and removal, read F-1000 Series Installation
and Removal Instruction
IMPORTANT NOTE
The meter will not generate a ow signal unless the turbine is in water.
F-1100 AND F-1200 INSERTION STYLE METERS (CONTINUED)