[email protected]System-30 BTU Measurement System Manual 09/12 - 0667-1 / 18335 Page 6
1.3 STANDARD FEATURES AND SPECIFICATIONS
• SinglemodeBTUcalculations,ineithertheheatingorcoolingmode,aretotalizedand
reported.
• Two-pipedualmodeBTUcalculationsinboththeheatingmodeandthecoolingmodeare
totalizedandreportedseparately.
CALIBRATION
Flowsensorandtemperaturesensorsareindividually
calibrated, followed by a complete system calibration.
Fieldcommissioningisalsoavailable.
ACCURACY
Differentialtemperatureaccuracy±0.15°Fovercalibrated
range
Computingnon-linearitywithin±0.05%
Flowsensoraccuracy:
±0.5%OFREADINGatcalibratedvelocity
±1%OFREADINGfrom3to30ft/s(10:1range)
±2%OFREADINGfrom0.4to20ft/s(50:1range)
TEMPERATURE SENSORS
SolidstatesensorsarecustomcalibratedusingN.I.S.T.
traceable temperature standards.
PROGRAMMING
Factoryprogrammedforeachspecicapplication
MEMORY
NonvolatileEEPROMmemoryretainsallprogram
parametersandtotalizedvaluesintheeventofpowerloss.
OUTPUT SIGNALS
Isolatedsolidstatedrycontactsformode1andmode2
energy total
Contactrating:100mA,50V
Contactduration:0.5,1,2or6secselectable
OPTIONAL OUTPUT SIGNALS
One isolated analog output, factory selectable for ow rate,
energyrateordelta-T
(Availableas4-20mA,0-10Vor0-5Vsignal)
OR
Serialconnectionfor:BACnetMS/TP,MODBUSRTU,
JCIN2-Metasys,SiemensP1-Apogee,or
LONWORKS®networks
OPTIONAL LOCAL DISPLAY:
AlphanumericLCDdisplaystotalenergy,totalow,energy
rate, ow rate, supply temperature and return temperature
Alpha:16characters,0.2”high
Numeric:6digit,0.4”high
MAINTENANCE:
ONICONrecommendsperiodicinspectionandrecalibration.
Nootherperiodicmaintenanceisrequired.
TEMPERATURE RANGE:
Liquidtemperaturerange:32°Fto200°F
Ambienttemperaturerange:40°Fto120°F
MECHANICAL
OVERALLDIMENSION:
9.25”Lx5”Wx6.5”H
TEMPERATURETHERMOWELL:
Brassthermowell(½”sweator¼”NPT)
ELECTRICAL
ThisequipmentisintendedforINSTALLATION
CATEGORY(OVERVOLTAGECATEGORY)II
applications
INPUTVOLTAGE: 24V±10%AC50/60Hzor
24V±4DC
INPUTCURRENT: 200mAmaximum
TERMINALSCONNECTIONS:Use18-22ga.copper
wire.Donotexceed4.5in-lb(0.5Nm)oftorque
when tightening.
WIRING:
CONDUIT:UsePVCjacketedcoppercablewitha
wiregaugesuitableforthelengthofrunandrequired
maximumcurrentcarryingcapacity.Theinstallation
must comply with all local, state and federal codes.
PLENUMAREA:(withoutconduit)Useplenumrated
copper cable with a wire gauge suitable for the length
ofrunandrequiredmaximumcurrentcarrying
capacity. The installation must comply with all local,
state and federal building codes.
Note:Specicationsaresubjecttochangewithoutnotice.