Calibration Validation
Validate the calibration of the FT1 in the eld using the CAL-V™ test. The goal of Calibration
Validation is to provide operators with the ability to verify that the meter is capturing accurate
data at scheduled recalibration times - or at any time - instead of sending the meter back to
the factory for recalibration. By performing CAL-V™ in the eld, operators can verify that the
meter is running accurately by testing the functionality of the sensor and its associated signal
processing circuitry. This test can be done in the pipe under normal processing conditions.
DDC-Sensor™Technology Description
The 2nd Generation Fox Thermal DDC-Sensor™ is a new state of the art sensor technology
used in the Fox Thermal Model FT1 Thermal Gas Flow Meter. The DDC-Sensor™, a Direct
Digitally Controlled sensor, is unlike other thermal ow sensors available on the market.
Instead of using traditional analog circuitry, the DDC-Sensor™ is interfaced directly to the
FT1 microprocessor for more speed and programmability. The DDC-Sensor™ quickly and
accurately responds to changes in process variables by utilizing the microprocessor to
determine mass ow rate, totalized ow, and temperature.
Fox Thermal’s DDC-Sensor™ provides a technology platform for calculating accurate gas
correlations. The FT1 correlation algorithms allow the meter to be calibrated on a single gas
in the factory while providing the user the ability to select other gases in the Gas-SelectX®
Gas Menu. Fox Thermal’s Model FT1 with its DDC-Sensor™ and state-of-the-art correlation
algorithms provide an accurate, multi-gas-capable thermal gas ow meter.
I/O Description
The FT1 features a galvanically isolated 4-20mA analog output with HART communication
option and a second output for pulse, Modbus RTU (RS485) or BACnet MS/TP (RS485).
There is also a USB port for interfacing with a laptop or computer. The 4-20mA output can
be congured for ow rate or process gas temperature and can be scaled by the user. The
pulse output can be used for pulse or alarm, is programmable to represent ow rate and can
be scaled for maximum ow/maximum frequency, units-per-pulse or pulse-per-units. The
maximum frequency is 100 Hz.
FT1 View™ interfaces to the USB port and is a free PC-based software program that displays
ow meter readings and permits ow meter conguration. The software is available for
download on the Fox Thermal website. Industry standard communication options are available
including optional Modbus RTU (RS485), BACnet MS/TP (RS485), or HART.