Ormazabal ekor.rps Instruction manual

LIB
ekor.rps
Multifunctional protection unit
Volume 1 of 3
General instructions
IG-150-EN, version 04, 03/10/16

In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject
to change without prior notice. These characteristics, as well as the availability of components, are subject to confirmation
byOrmazabal.
CAUTION!
When medium-voltage equipment is operating, certain components are live, other parts may be in movement and some may
reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
• Elimination of hazards wherever possible.
• Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
• Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protective equipment.
• Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the
environmental restrictions established by the competent authorities
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of Standard
IEC 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the
requirements of standard EN50110-1 on the safety of electrical installations and standard EN50110-2 on activities in or near
electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other
recommendations of a more general nature which are applicable to the situation according to current legislation[1].
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also
on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
• The equipment must be handled and transported appropriately from the factory to the place of installation.
• All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment
or its essential components.
• Service conditions must be compatible with the equipment rating.
• The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable
operating and safety principles must be clearly understood.
• Maintenance should be performed properly, taking into account the actual service and environmental conditions in
the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Warranty
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual
belongs to Ormazabal.
[1] For example, in Spain the “Regulation on technical conditions and guarantees for safety in high-voltage electrical installations” – Royal Decree
337/2014 is obligatory.

General instructions
ekor.rps
Contents
IG-150-EN version 04; 03/10/16 3
Contents
1. General description ...................................................6
1.1. Scope of the manual .........................6
1.2. Functions....................................6
1.3. Model coding................................7
1.4. User interface...............................10
1.4.1. Local .......................................10
1.4.2. Remote.....................................10
1.5. Hardware configurations ....................11
1.6. Environmental conditions ...................12
1.7. Tests........................................12
1.7.1. Electrical tests ..............................12
1.7.2. Environmental tests.........................12
1.7.3. Mechanical tests ............................12
1.8. CE Conformity ..............................12
1.9. Wiring diagrams ............................13
2. Hardware ..................................................................33
2.1. Constructive characteristics. Horizontal box
(ekor.rps-h).................................33
2.2. Constructive characteristics (ekor.rps-tcp) ...34
2.3. Rear terminals ..............................35
2.4. Options for rear communications ports . . . . . .36
2.5. RS485 connection detail between
some units..................................38
2.6. Connection between fiber optic and
a radio modem .............................39
2.7. Ethernet communication....................40
2.7.1. Ethernet via GOF............................40
2.7.2. Ethernet via RJ45 cable......................40
2.8. Technical characteristics.....................41
2.8.1. Power Supply ...............................41
2.8.2. Output Contacts ............................41
2.8.3. Digital inputs (optoisolated).................41
2.8.4. IRIG-B input.................................42
2.8.5. Analog outputs .............................43
2.8.6. Phase and neutral current circuits
(standard rating 1 A) ........................43
2.8.7. Sensitive neutral or isolated neutral
current circuits (standard rating 0.025 A).....43
2.8.8. Phase and neutral current circuits
(specified rating 1/5 A) ......................43
2.8.9. Sensitive neutral or isolated neutral current
circuits (specified rating 0.25/0.025 A) .......43
2.8.10. Voltage circuits .............................43
2.8.11. Measurements accuracy.....................44
2.9. Operating frequency........................44
2.10. Phase order.................................44
3. Unit configuration ...................................................45
3.1. Programming of digital inputs and
logic inputs .................................45
3.2. Programming of digital outputs .............46
3.3. Programming of LEDs .......................47
3.4. Programming of general settings............47
3.4.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .47
3.4.2. Setting ranges (table 0, single)...............48
3.5. Communication configuration ..............49
3.5.1. Communication via front door (Port 1_1)
and rear port Nr. 2 (Port 1_2) (COM 1) ........49
3.5.2. Communication via rear port Nr. 1
(Port 2) (COM 2).............................49
3.5.3. Ethernet communication....................51
3.6. Other configuration settings ................52
3.6.1. Frequency ..................................52
3.6.2. Language...................................52
3.6.3. Phase order.................................52
3.6.4. Neutral Parameter ..........................52
3.6.5. Calibration..................................52
3.6.6. Test mode ..................................52
3.6.7. Push-buttons/LEDs enabling and locking
by command ...............................53
3.6.8. Power supply supervision enabling ..........53
3.6.9. Power supply enabling......................53
3.6.10. Display contrast setting .....................53
4. Protection functions. Description and settings.....54
4.1. Phase overcurrent protection................54
4.1.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .54
4.1.2. Settings ranges of the timed characteristic
(6 tables) (normal and HIGH2) ...............54
4.1.3. Timing cancellation .........................55
4.1.4. Settings ranges of the instantaneous
characteristic (low level) (6 tables)
(normal and HIGH2).........................55
4.1.5. Settings ranges of the instantaneous
characteristic (high level) (6 tables) ..........56
4.2. Neutral overcurrent protection ..............56
4.2.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .56
4.2.2. Setting ranges of the timed characteristic
(6 tables) (normal and HIGH2) ...............56
4.2.3. Setting range of neutral time inhibition
(6 tables) ...................................57
4.2.4. Settings ranges of the instantaneous
characteristic (low level) (6 tables)
(normal and HIGH2).........................57
4.2.5. Settings ranges of the instantaneous
characteristic (high level) (6 tables)
(normal and HIGH2).........................57
4.3. Instantaneous special operation.............58
4.4. 2nd harmonic restraint .......................60
4.5. Protection functions blocking with
manual closing .............................60
4.6. Directionality of the phase and
neutral overcurrent protections .............61
4.6.1. Phase directional in quadrature (67) .........62

IG-150-EN version 04; 03/10/16
4
Contents General instructions
ekor.rps
4.6.2. Phase directional by sequences (67) .........63
4.6.3. Neutral directional (67N); polarization
by S0(V0)....................................64
4.6.4. Neutral directional (67N); polarization
by S-(V2)...................................65
4.6.5. Neutral directional (67N); polarization
by S0+S-(V0+V2)..........................66
4.6.6. Neutral directional (67N); polarization
by I .........................................66
4.6.7. Neutral directional (67N); polarization
by S0+I(V0+Ipol) ...........................67
4.6.8. Neutral directional (67N); polarization
by S– + I(V2+Ipol)...........................67
4.6.9. Neutral directional (67N); polarization
by S0+ S- + I (V0+ V2 + Ipol)..................68
4.6.10. Neutral directional (67N); watimetric
directional ..................................69
4.6.11. Neutral directional (67N);
I*cos (φ)/I*sen (φ) directional ................70
4.7. Sensitive neutral overcurrent protection .....72
4.7.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .72
4.7.2. Setting ranges of the timed characteristic
(6 tables) (normal and HIGH2) ...............72
4.7.3. Setting ranges of the instantaneous
characteristic (single level) (6 tables)
(normal and HIGH2).........................72
4.7.4. Directionality ...............................73
4.8. Current unbalance protection ...............77
4.8.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .77
4.8.2. Setting ranges of the timed characteristic
(6 tables) ...................................77
4.8.3. Setting ranges of the instantaneous
characteristic (6 tables)......................77
4.9. Broken conductor protection................78
4.9.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .78
4.9.2. Setting ranges (6 tables).....................78
4.10. Phase characteristic voltage control
(function 51 V/50 V) .........................78
4.10.1. Mode 1 (51V)...............................78
4.10.2. Mode 2 (51V)...............................79
4.10.3. Mode 2 (50 V)...............................79
4.10.4. Summary ...................................79
4.11. High current lockout . . . . . . . . . . . . . . . . . . . . . . . .80
4.11.1. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
4.11.2. Setting (table 0, single)......................80
4.12. Cold load pickup............................80
4.12.1. Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
4.12.2. Settings (table 0, single) .....................81
4.13. Isolated neutral protection ..................82
4.13.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .82
4.13.2. Setting ranges ..............................82
4.14. Overvoltage protection .....................83
4.14.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .83
4.14.2. Setting ranges of the timed characteristic
(6 tables) ...................................83
4.14.3. Setting ranges of the Instantaneous
characteristic (6 tables)......................84
4.15. Undervoltage protection ....................84
4.15.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .84
4.15.2. Setting ranges of the timed characteristic
(6 Tables) ...................................84
4.15.3. Setting ranges of the instantaneous
characteristic (6 tables)......................85
4.16. Voltage unbalance protection ...............85
4.16.1. Timed characteristic.........................85
4.16.2. Instantaneous characteristic.................86
4.17. Zero sequence overvoltage protection ......86
4.17.1. Setting range (6 tables) .....................87
4.18. Frequency protection .......................87
4.18.1. Minimum frequency ........................88
4.18.2. Maximum frequency ........................88
4.18.3. Frequency gradient .........................88
4.19. Fuse failure .................................90
4.20. Teleprotection ..............................91
4.20.1. Operation ..................................91
4.20.2. Setting range (6 tables) .....................91
4.20.3. Protection trip mask (6 tables) ...............92
4.20.4. Used signals ................................92
4.21. Thermal image..............................96
4.21.1. General description . . . . . . . . . . . . . . . . . . . . . . . . .96
4.21.2. Settings ....................................97
4.21.3. Trip times...................................97
4.21.4. Heating curves .............................98
4.21.5. Cooling curves..............................98
4.22. Field loss protection.........................99
4.22.1. Overview ...................................99
4.22.2. General settings range ......................99
4.22.3. MHO area settings range ..................100
4.23. Power protection .........................101
4.23.1. General...................................101
4.23.2. Minimum power protection ...............101
4.23.3. Maximum power protection...............102
4.23.4. Reverse power protection .................102
4.23.5. Reactive power reverse protection.........103
4.23.6. Minimum apparent power protection .....103
4.23.7. Maximum apparent power protection ..... 104
4.24. Breaker monitorin......................... 104
4.24.1. General description . . . . . . . . . . . . . . . . . . . . . . . 104
4.24.2. Setting range (6 tables) ...................105
4.24.3. Coil monitoring example .................. 105
4.25. Coil monitoring example ..................106
4.25.1. General description . . . . . . . . . . . . . . . . . . . . . . . 106
4.25.2. Setting range (6 tables) ...................106
4.26. Breaker failure protection .................106
4.26.1. General description . . . . . . . . . . . . . . . . . . . . . . . 106
4.26.2. Setting range (6 tables) ...................107
4.27. Tap changer locking (50TCL function)......107
4.28. Locking of the protection functions .......107
4.29. Fault locator ..............................107
4.29.1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
4.29.2. Programming settings and
collecting results..........................108
4.29.3. Locator operation......................... 109

General instructions
ekor.rps
Contents
IG-150-EN version 04; 03/10/16 5
5. Automation functions .......................................... 112
5.1. Recloser ..................................112
5.1.1. General description . . . . . . . . . . . . . . . . . . . . . . . 112
5.1.2. Operation ................................113
5.1.3. Setting range (6 tables) ................... 115
5.1.4. Trips enabling (6 tables) ...................115
5.1.5. Enable of reclosings (6 tables) .............115
5.1.6. Other operation characteristics............ 116
5.2. Sequence coordination ................... 116
5.3. Reclosing after tripping
by minimum frequency ...................117
5.3.1. General description . . . . . . . . . . . . . . . . . . . . . . . 117
5.3.2. Settings ..................................117
5.4. Special recloser to operate with
protections with single-pole trip...........118
5.5. Syncrocheck . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
5.5.1. General description . . . . . . . . . . . . . . . . . . . . . . . 118
5.5.2. Settings ..................................119
5.6. Close locking with presence or
absence of voltage........................119
5.7. Automation function for distribution
substations ...............................120
5.7.1. Unloaded springs automation functions ... 120
5.7.2. Voltage presence ......................... 120
5.7.3. Lockings.................................. 120
6. Other settings........................................................ 121
6.1. Programming of logic outputs ............ 121
6.2. Selectivity logic functions ................. 122
6.3. Measurements chronological record.......122
7. data acquisition functions.................................... 123
7.1. Events reports ............................ 123
7.2. fault records .............................. 124
7.3. Measurements............................125
7.3.1. Measurements at the secondary........... 125
7.3.2. Measurements at the primary ............. 126
7.4. Measurements historical report ........... 127
7.4.1. General description . . . . . . . . . . . . . . . . . . . . . . . 127
7.4.2. Settings range (6 tables)...................127
7.5. Statistical data ............................127
7.6. Protection status.......................... 128
7.6.1. By keyboard/display ...................... 128
7.6.2. Through PC (protections console) ......... 128
7.7. Oscillograph data recorder ................ 128
8. Other functions ..................................................... 129
8.1. Time setting and synchronization ......... 129
8.1.1. Time setting ..............................129
8.1.2. Synchronization ..........................129
8.2. Control messages .........................129
8.3. Mando local/remoto ......................135
8.4. Commands by keyboard and
front push-buttons........................136
8.5. Power supply supervision ................. 136
8.6. External supply supervision ...............136
8.7. Temperature supervision..................137
8.8. Test mode ................................ 137
9. Operation mode.................................................... 138
9.1. Through keyboard/display ................ 138
9.1.1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
9.1.2. Elements of the keyboard/display unit.....138
9.1.3. Operating mode ..........................139
9.2. Through the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
10. Reception, storage, installation and tests .......... 141
10.1. Reception and storage .................... 141
10.2. Connecting procedure ....................141
10.2.1. Power supply ............................. 141
10.2.2. Earth connection ......................... 141
10.2.3. RS232 cable connections to be used
between the PC and the ekor.rps unit ....141
10.3. Unit addressing ...........................142
10.4. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

IG-150-EN version 04; 03/10/16
6
General description General instructions
ekor.rps
1. General description
The ekor.rps units are multifunctional protection relays
of numerical technology, and they constitute the basic
element of protection, measurement and control for
cogeneration facilities or for HV/MV electrical bays. They
can be used as autonomous elements of protection, control
and measurement of an electric bay, or integrated within an
integrated protection and control system.
Inside the family dierent models exist that dier to each
other for some hardware aspect or for their functionality.
The Firmware is common for all the models; the available
functions for the user in each model are dened in a circuit
of programmable logic (PLD). The Firmware is chargeable in
the equipment through the serial port, what facilitates the
versions updating.
1.1. Scope of the manual
This manual does not t a certain ekor.rps model, it ts the
whole options (for FW version equal or newer than W). For
each specic model only the physical characteristics and
functions of the model are applied. The manual consists of
two volumes: The rst contains the information regarding
conguration, functions etc. and the second contains the
following appendixes: Curves for the operation of the timed
functions,communicationprotocols,keyboard/displaymenu
structure, etc.
Anyway,eachunitisprovidedwitharesumed“characteristics
sheet”, which describes the functions of the specic model
and its interconnections diagram.
1.2. Functions
1. Protection
Standard functions
a. Three phase overcurrent protection (3 x 50/51, with two
instantaneous levels)
b. Neutral overcurrent protection (50N/51N, with two
instantaneous levels)
c. Phase current unbalance protection (46)
d. Broken conductor protection (46 BC)
e. Breaker monitoring
f. Close and trip circuit monitoring
g. Breaker failure
h. 2nd harmonic restraint
Functions depending on model
a. Sensitive neutral overcurrent (50NS/51NS)
b. Directionality for the phase overcurrent (3 x 67)
c. Directionality for the neutral overcurrent (67N)
d. Isolated neutral directional (67IN)
e. Second directional overcurrent unit (67, 67N), independent
of the first unit
f. Voltage controlled overcurrent (50/51 V), cold load
pickup, high current lockout
g. Special functions (zones, pilot protection, negative
sequence directional, etc.)
h. Phase voltage protection: Overvoltage (3 x 59), undervoltage
(3 x 27), unbalance (47)
i. Zero sequence overvoltage protection (59N, 64)
j. Frequency protection: Maximum (81 M), minimum (81 m),
df/dt (81 R)
k. Power protection (32): Maximum, minimum, reverse
l. Fuse failure surveillance
m. Thermal image (49)
n. Fault locator
o. Field loss
2. Automatisms
Functions depending on model
a. Three-phase recloser (overcurrent trips)
b. Recloser for single-phase overcurrent trips
c. Recloser for restoration after frequency trips
d. Syncrocheck
e. Special automatisms for distribution substations (slack
springs, voltage presence)
3. Measurements
a. Phase and neutral current measurement (optional:
Sensitive neutral)
b. Simple and compound voltage measurement
c. Active, reactive and apparent power measurement
d. Active and reactive energy measurement
e. Power factor measurement
f. Current maximeter
g. Negative sequence measurement (I2/I1) in %

IG-150-EN version 04; 03/10/16 7
General instructions
ekor.rps
General description
4. Data acquisition
a. Events chronological reports
b. Fault chronological reports
c. Maximum and minimum measurement historical
d. Oscillograph data recorder
5. Other characteristics
a. Settings tables. Except for the configuration settings,
which are single table settings, there are 6 tables for the
various setting groups. One of the 4 tables is the active
one in a certain moment. The active table selection
can be done through the keyboard/display (in “change
settings”), or by command through the message from the
protections console or by activation of a digital input.
1.3. Model coding
The ekor.rps protection unit has the following models:
DC: 67+67N+46+46FA+50BF(trif)+74TC/CC+ 67NS+
67NA+49+51V+cold load pickup+50CSC+68FF
The following models are available as an option and
when conrmed by Ormazabal’s technical-commercial
department:
1. Non directional:
NB: 50/51 + 50/51N + 46 + 46BC + 50BF (three-phase) + 74TC/CC
NC: Model NB + 50/51NS + 49 + 51 V + cold load pickup +
50TCL + 68FF
ND: Model NC + 59 + 27 + 47 + 59N + 81 O/U + 81R + 25
NE: Model ND + FL
For all of them, the 79 function is optional.
2. Directional:
DB: 67 + 67N + 46 + 46BC + 50BF (three-phase) + 74TC/CC
DD: Model DC + 59 + 27 + 47 + 59N + 81 O/U + 81R + 25
DE: Model DD + 2nd unit 67/67N + 50BF (single-phase)
DF: Model DE + FL
For all of them, the 79 function is optional.
3. Distributed generation interconnection:
IB: 50/51 + 67N + 46 + 46BC+ 50BF (three-phase) + 74TC/CC +
68FF + 59 + 27 + 47 + 59N + 81 O/o + 81R + 25 + 32 + 79 +
79 (81 m) + high current lockout.
IC: Model IB + 49 + 51 V + cold load pickup + 50TCL + 2nd unit
67/67N + 40.
4. For distribution substations:
CR: 50/51 + 50/51 N + 46 + 46 BC+ 50 BF (three-phase) +
74TC/CC +49+79+ high currentlockout + specialautomatisms.
5. Special models: They are those that, in their
functionality, do not exactly correspond to any of the
families described:
E1: 67 + 67N + 67NS + 46 + 46FA + 50BF (three-phase) +
74TC/CC + 51 V + 79 +High current Lockout + LF.
E2: 67 + 67N +67NS + 51 V + 27 + 59 +59N + FF + 81 + 32 + 49.
E3: 50/51 + 50/51N + 50/51NS + 67NA + 79.
E4: E1: 67 + 67N + 67NS + 46 + 46FA + 50BF (three-phase) +
74TC/CC +51V+79 + highcurrentlockout+coldload pickup+
50CSC + 59N + 25 + LF.

IG-150-EN version 04; 03/10/16
8
General description General instructions
ekor.rps
Model coding:
MODELO PL300
MODEL
NB
NC
ND
NE
DB
DC
DD
DE
DF
IB
IC
BOX TYPE
TCP integrated Note 5
POWER SUPPLY
YdcV06-81
ZdcV082-68
ANALOG INPUTS TERMINALS
Pin type Standard terminals
Closed terminals
EXTENSION MODULE
No module
9 Dls (6 indepen.) + 7 DOs (3 indepen.)
DIGITAL INPUTS VOLTAGE
REAR COMMUNICATION PORTS
AGFO
BPFO
CRS232
DRS485
EGFO (COM-2) + GFO (COM-1)
IGFO (COM-2) + RS232 (COM-1)
JEthernet RJ45 + GFO (COM-2)
KEthernet GFO + GFO (COM-2)
LEthernet RJ45 + RS232 (COM-2)
MEthernet RJ45 + RS485 (COM-2)
TInternal communication for TCP
F
G
H
PFO (COM-2) + PFO (COM-1)
RS232 (COM-2) + RS232 (COM-1)
RS485 (COM-2) + RS232 (COM-1)
SPECIAL FUNCTIONS AND AUTOMATISMS
0No Functions
179 + 79 (81 m) (Included in models IB, IC y CR)
285 (Only for directional PL-300 models)
379 + 79 (81 m) + 85 (Only for directional PL-300 models)
Battery voltage measurement and optional operating temperature
0None
1Battery voltage measurement
2
3
Optional operating temperature
Battery voltage measurement and optional operating temp.
Current polarized 67N
No 0
Yes 1
V0or INcalculation
None 0
1
V0 calculated
2
INcalculated
Both (only for models DD + current polarized 67N,
DE + current polarized 67N, DF + current polarized 67N)
3
Programmable Protocol
Programmable Protocol
Programmable Protocol
Programmable Protocol
Note 1
Note 1
Note 1
Note 1
Note 1
Note 6
Note 6
Note 6
Note 6
Note 5
Note 2
Note 2
Note 3
no direccional
direccional
interconexión
centros de reparto
Note 4
Note 3
ekor.rps
ekor.rps non directional
ekor.rps Directional
ekor.rps Interconnection
T
H
Horizontal
1
2
0
1
Range: 18-160 VdcY
Range: 86-280 VdcZ
CR
ekor.rps Distribution center
Figure 1.1. Model coding
For models with two communication ports,
COM 2 port protocol is programmable, and
COM 1 protocol is always PROCOME.
79 (81 m) (recloser by underfrequency) unit,
only exist for models with 81 U
For the models marked with an * in the
transformer arrangement table
Only for models with 67 N and T9 = Ip
(*olarization current)
With “T” type box, the communication must
be“T”
In this case, the Ethernet port protocol is
encapsulated PROCOME

IG-150-EN version 04; 03/10/16 9
General instructions
ekor.rps
General description
Transformer arrangement:
T4 T5 T9
Model nb IN
Model nc ININS
Model nd*ININS VSYNC V0calculated
Model nd*INV0VSYNC INcalculated
Model ne*Same transformer arrangement as model nd
Model db INV0
Model db + current polarized 67N INV0I0
Model dc ININS V0
Model dc + current polarized 67N* ININS I0V0calculated
Model dc + current polarized 67N* INS V0I0INcalculated
Model dd*ININS VSYNC V0calculated
Model dd*INS V0VSYNC INcalculated
Model dd + current polarized 67N INS I0VSYNC INand V0calculated
Model de*Same transformer arrangement as model dd
Model de + current polarized 67N Same transformer arrangement as model dd + current polarized 67N
Model df*Same transformer arrangement as model dd
Model df + current polarized 67N Same transformer arrangement as model dd + current polarized 67N
Model ib INV0VSYNC
Model ib + current polarized 67N* INI0VSYNC V0calculated
Model ib + current polarized 67N* V0I0VSYNC INcalculated
Model ic Same transformer arrangement as model ib
Model ic + current polarized 67N* Same transformer arrangement as model ib + current polarized 67N
Model cr IN
See transformer arrangement examples in the wiring diagrams.
Table 1.1. Transformer arrangement

IG-150-EN version 04; 03/10/16
10
General description General instructions
ekor.rps
1.4. User interface
1.4.1. Local
The front board has:
1. 16 key keyboard
2. 4 signaled push-buttons
a. : Breaker closure
b. : Breaker opening
c. : Local/remote
d. :It validates the other three pushbuttons, to avoid
unwished maneuvers. It must be pushed at the same time
you push the other buttons for them to have effect
These pushbuttons must be pushed at least for 0.5 s to be
considered active.
Moreover, the pushbuttons to be eective, “push-
button enable” setting must be set as “YES” (see “other
conguration settings”chapter).
3. 2 line, 16 character LCD
4. 7 red LEDS and one green/red
5. RS232 connector for direct connection with a PC.
PROCOME protocol
1.4.2. Remote
Depending on model the rear board has one or two ports
which can be glass ber optic (ST type connector), plastic
ber optic, RS232 or RS485 for connection to PC, modem or
substation control unit (in integrated systems).The protocol
can be PROCOME, DNP 3.0, MODBUS or IEC 870-5-101 or
IEC870-5-103.
There are also models with one Ethernet port (ber optic or
RJ45), with PROCOME TCP/IP protocol.

IG-150-EN version 04; 03/10/16 11
General instructions
ekor.rps
General description
1.5. Hardware configurations
Next are the Hardware possibilities that dene a specic
model:
1. Box type:
a. Horizontal
2. Terminal type:
a. For pin tipy terminals
b. For closed terminals
3. Power supply:
a. 125/220Vdc
b. 24/48Vdc
4. Digital inputs voltage range:
a. Extended (low): 18 up to 160 Vdc. They are single-
directional inputs (with polarity).
b. Extended (high): 86 up to 280 Vdc. They are single-
directional inputs (with polarity).
c. Restricted 24 Vdc: 18 up to 34 Vdc. They are single-
directional inputs (with polarity).
d. Restricted 48 Vdc: 36 up to 60 Vdc. They are single-
directional inputs (with polarity).
e. Restricted 125 Vdc: 85 up to 150 Vdc. They are single-
directional inputs (with polarity).
f. Restricted 220 Vdc: 165 up to 264 Vdc. They are single-
directional inputs (with polarity).
5. Number of digital inputs/outputs:
a. Standard:
8 inputs (5 independent, 3 with a common point).
7 outputs (4 independent, 3 with a common point).
b. Extended: Adds to the standard:
9 inputs (6 independent, 3 with a common point).
7 outputs (4 independent, 3 with a common point).
c. Extended (option 2): adds to the standard:
5 independent inputs.
6 outputs (4 independent, 2 with a common point).
2 analog outputs (0 to 5 mA); for other ranges please
consult Ormazabal’s technical–commercial department.
6. Rear communication:
a. Glass optical fiber (GOF)
b. Plastic optical fiber (POF)
c. RS232
d. RS485
e. GFO + GFO
f. PFO + PFO
g. RS232 + RS232
h. RS485 + RS232
i. GFO + RS232
j. GOF + Ethernet (RJ45)
k. POF + Ethernet (OF)
l. RS232 + Ethernet (RJ45)
m. RS485 + Ethernet (RJ45)
In case of having two rear ports, the one mentioned in second
place is in parallel with the front RS232 (they occupy the same
port).
7. Analogue inputs:
The unit can have up to 9 analog inputs (through
transformer).– Preferential option.
Inputs 1, 2 and 3 are used for phase currents measurement.
Input 4 is used for neutral current measurement.
Input 5 depends on model. There are the next possibilities:
a. No input
b. Sensitive neutral or isolated neutral current
measurement
c. Zero sequence voltage measurement V0
Inputs 6,7 and8 areused for thephase voltagesmeasurement.
Input 9 depends on model. There are the next possibilities:
a. No input
b. Zero sequence voltage measurement V0for the
Syncrocheck function

IG-150-EN version 04; 03/10/16
12
General description General instructions
ekor.rps
1.6. Environmental conditions
1. Operating temperature: -10 up to 55 °C
2. Storage temperature: -40 up to 85 °C
3. Relative humidity: Up to 95 % without condensation
1.7. Tests
1.7.1. Electrical tests
1. Measurement of dielectric rigidity: Acc. to/IEC 255-5,
series C (2 kV, 1 min)
2. Measurement of insulation resistance: Acc. to/IEC255-5,
>10GΩ at 500 Vdc
3. Pulse (shock wave): Acc. to/IEC 255-5, appendix E, classIII
4. HF disturbances: Acc. to/IEC 255-22-1, class III
5. Fast transients: Acc. to/IEC 61000-4-4, class IV
6. Immunity to electrostatic discharges: Acc. to/IEC61000-4-2,
class IV
7. Voltage pulses: Acc. to/IEC 61000-4-5, class IV
8. Micro-cuts: Acc. to/IEC 60255-11, 100ms a 125Vdc
9. Radiated electromagnetic interference:
Acc. to/EN 61000-6-4
10. Immunity to radiated elds: Acc. to/IEC 61000-4-3,
class III
11. Immunity to conducted: Acc. to/IEC 61000-4-6, class III
radiofrequency signals
12. Immunity to low frequency: Acc. to/IEC 61000-4-8
radiated elds
1.7.2. Environmental tests
1. Cold: Acc. to/IEC 68-2-1 (-40 °C)
2. Dry heat: Acc. to/IEC 68-2-2 (+85 °C)
3. Humid heat: Acc. to/IEC 68-2-3 (+70 °C, 93 % relative
humidity)
4. Change of temperature: Acc. to/IEC 68-2-14 (-20°/70°C
two 4-hour cycles)
5. Operating range: -10 °C. up to 55 °C
1.7.3. Mechanical tests
1. Vibration test: Acc. to/IEC 255-21-1 class II 2. Shock and bump test: Acc. to/IEC 255-21-1 class I
1.8. CE Conformity
This product complies with the European Union directive
2014/30/EU on electromagnetic compatibility, and with
the IEC 60255 international regulations. The unit has been
designed and manufactured for use in industrial areas,
in accordance with EMC standards. This conformity is a
result of the test carried out in accordance with article 7 of
the Directive.

IG-150-EN version 04; 03/10/16 13
General instructions
ekor.rps
General description
1.9. Wiring diagrams
All the following wiring diagrams show one of the possible
digital input and output programming (very simple). See
all the possibilities in “programming of digital inputs” and
“programming of digital outputs”sections.
In the outputs with change-over contact the common point
is the middle one.
Phase sequence order is settable by keyboard/display
(See “other settings”-“protection denition”).
C
B
A
Front
RS232
Port COM1
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
X3
11
8
7
6
5
4
3
2
1
XFA
23
Power Supply Vdc
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD 6
SD 5
SD 4
SD 3
SD 2
SD 1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (VA)
T7 (VB)
T8 (VC)
AX1
ED17
X3
BC
CBA
52
General trip
Close
Phase trip
Ground trip
Free
Free
52 state
Close command
Open command
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD 7
25
SD 14 26
14
SD 8
SD 9
SD 10
SD 11
SD 12
SD 13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
Free
Free
Free
Synchronization
OPTIONAL
HW status
1
Free
Free
or Ethernet
Rear
Port COM2
Rear
Port COM1
OPTIONAL
RJ45 4
6
8
7
5
1
2
3
Tx+
Tx -
Rx+
Rx-
RS485
3
2
4
1
5
+
-
GND
Glass O.F.
Plastic O.F.
Tx
Rx
0V 5
RTS 7
Tx 3
DTR 4
Rx 2
RS232
Figure 1.2. nb and cr models

IG-150-EN version 04; 03/10/16
14
General description General instructions
ekor.rps
C
B
A
Front
RS232
Port COM1
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
X3
11
10
9
8
7
6
5
4
3
2
1
XFA
23
Power Supply Vdc
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD 6
SD 5
SD 4
SD 3
SD 2
SD 1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (VA)
T7 (VB)
T8 (VC)
A
X1
ED17
X3
BC
CBA
52
T5 (INS)
General trip
Close
Phase trip
Ground trip
Free
Free
52 state
Close command
Open command
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD 7
25
SD 14 26
14
SD 8
SD 9
SD 10
SD 11
SD 12
SD 13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
Free
Free
Free
Synchronization
OPTIONAL
HW status
1
OPTIONAL
Free
Free
or Ethernet
Rear
Port COM2
Rear
Port COM1
OPTIONAL
RJ45 4
6
8
7
5
1
2
3
Tx+
Tx -
Rx+
Rx-
RS485
3
2
4
1
5
+
-
GND
Glass O.F.
Plastic O.F.
Tx
Rx
0V 5
RTS 7
Tx 3
DTR 4
Rx 2
RS232
Figure 1.3. nc model

IG-150-EN version 04; 03/10/16 15
General instructions
ekor.rps
General description
C
B
A
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
18
17
16
15
14
13
12
X3
11
10
9
8
7
6
5
4
3
2
1
XFA
23
Power Supply Vdc
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD6
SD5
SD4
SD3
SD2
SD1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (TA)
T7 (TB)
T8 (TC)
T9 (SYN)
A
X1
ED17
X3
BC
CBA
52
T5 (INS)
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD7
25
SD14 26
14
SD8
SD9
SD10
SD11
SD12
SD13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
OPTIONAL
1
Plastic O.F.
Rx
RS232
Tx 3
Rx 2
0V 5
RTS 7
DTR 4
Glass O.F.
Tx
OPTIONAL
OPTIONAL
HW status
Free
Free
Ground trip
Phase trip
Close
General trip
Port COM1
RS232
Front
OPTIONAL
Port COM1
Rear
Port COM2
Rear
Open command
Free
Synchronization
Free
Free
Free
Free
Close command
52 state
RS485
3
2
4
1
5
+
-
GND
RJ45 4
6
8
7
5
1
2
3
Tx+
Tx -
Rx+
Rx-
or Ethernet
Figure 1.4. nd, ne, dd, de and df modelos (with V0calculated, cod. ** **1*****01)
Although it is not represented, the Ethernet connection is also available in other diagrams.
“port 1”is COM 1 and“port 2” is COM 2.

IG-150-EN version 04; 03/10/16
16
General description General instructions
ekor.rps
C
B
A
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
8
7
6
5
4
3
2
1
XFA23
Power supply Vdc
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD6
SD5
SD4
SD3
SD2
SD1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (INS)
T6 (TA)
T7 (TB)
T8 (TC)
AX1
ED17
X3
BC
CBA
52
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD7
25
SD14 26
14
SD8
SD9
SD10
SD11
SD12
SD13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
OPTIONAL
1
X3
10
9T5 (V0)
Open command
Free
Synchronization
Free
Free
Free
Free
Close command
52 state
Rx
Glass O.F.
RS232
Plastic O.F.
Tx
Rx 2
DTR 4
RTS 7
0V 5
Tx 3
Port COM1
RS232
Front
Port COM1
Rear
OPTIONAL
Port COM2
Rear
HW state
Free
Free
Neutral trip
Phase trip
Close
General trip
RS485
3
2
4
1
5
+
-
GND
OPTIONAL T9 (SYN)
18
17
X3
Optional
Figure 1.5. nd, ne, dd, de and df models (with Ircalculated, , cod. ** **1*****02)

IG-150-EN version 04; 03/10/16 17
General instructions
ekor.rps
General description
C
B
A
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
11
8
7
6
5
4
3
2
1
XFA23
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD6
SD5
SD4
SD3
SD2
SD1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (TA)
T7 (TB)
T8 (TC)
AX1
ED17
X3
BC
CBA
52
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD7
25
SD14 26
14
SD8
SD9
SD10
SD11
SD12
SD13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
1
X3
10
9T5 (V0)
Trip direction
RS232
Tx
Rx
Rx 2
DTR 4
RTS 7
0V 5
Tx 3
RS485
3
2
4
1
5
+
-
GND
Power supply Vdc
OPTIONAL
Open order
Not configured
Synchronization
Not configured
Not configured
Not configured
Not configured
Close order
52 status
Glass O.F.
Plastic O.F.
Port 1A
RS232
Front
Port 1B
Rear
OPTIONAL
Port 2
Rear
HW status
Not configured
Not configured
Neutral trip
Phase trip
Close
General trip
Optional
Figure 1.6. db model (cod. DB **1*****00)

IG-150-EN version 04; 03/10/16
18
General description General instructions
ekor.rps
C
B
A
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
X3
11
10
9
8
7
6
5
4
3
2
1
XFA
23
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD 6
SD 5
SD 4
SD 3
SD 2
SD 1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (VA)
T7 (VB)
T8 (VC)
A
X1
ED17
X3
BC
CBA
52
T5 (V0)
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD 7
25
SD 14 26
14
SD 8
SD 9
SD 10
SD 11
SD 12
SD 13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
1
Rx
RS232
Tx 3
Rx 2
0V 5
RTS 7
DTR 4
Tx
T9 (I0) polarization
17
18
RS485
3
2
4
1
5
+
-
GND
Power supply Vdc
OPTIONAL
Open command
Not configured
Synchronization
Not configured
Not configured
Not configured
Not configured
Close command
52 status
Glass O.F.
Plastic O.F.
Port 1A
RS232
Front
Port 1B
Rear
OPTIONAL
Port 2
Rear
HW status
Not configured
Not configured
Neutral trip
Phase trip
Close
General trip
OPTIONAL
Figure 1.7. db model with polarization by 67N current (cod. DB **1*****10)

IG-150-EN version 04; 03/10/16 19
General instructions
ekor.rps
General description
C
B
A
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
X3
11
10
9
8
7
6
5
4
3
2
1
XFA
23
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD6
SD5
SD4
SD3
SD2
SD1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (VA)
T7 (VB)
T8 (VC)
A
X1
ED17
X3
BC
CBA
52
T5 (INS)
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD7
25
SD14 26
14
SD8
SD9
SD10
SD11
SD12
SD13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
1
Rx
RS232
Tx 3
Rx 2
0V 5
RTS 7
DTR 4
Tx
17
18 T9 (V0)
RS485
3
2
4
1
5
+
-
GND
Power supply Vdc
OPTIONAL
Open command
Not configured
Synchronization
Not configured
Not configured
Not configured
Not configured
Close command
52 status
Glass O.F.
Plastic O.F.
Port 1A
RS232
Front
Port 1B
Rear
OPTIONAL
Port 2
Rear
HW status
Not configured
Not configured
Neutral trip
Phase trip
Close
General trip
OPTIONAL
Figure 1.8. dc Model (cod. DC **1*****00)

IG-150-EN version 04; 03/10/16
20
General description General instructions
ekor.rps
C
B
A
X2
32
31
30
29
27
25
23
21
X1
19
17
10
9
8
7
6
5
4
3
2
1
11
10
9
8
7
6
5
4
3
2
1
16
15
14
13
12
X3
11
10
9
8
7
6
5
4
3
2
1
XFA
23
+-
ED16
ED15
ED14
ED13
ED12
ED11
ED10
ED9
ED6
ED5
ED4
ED3
ED2
ED1
0V 5
Tx 3
Rx 2
SD6
SD5
SD4
SD3
SD2
SD1
DC/DC
T1 (IA)
T2 (IB)
T3 (IC)
T4 (IN)
T6 (VA)
T7 (VB)
T8 (VC)
A
X1
ED17
X3
BC
CBA
52
T5 (INS)
ED7
ED8
12
13
14
15
16 IRIG-B
+
-
11
13
12
SD7
25
SD14 26
14
SD8
SD9
SD10
SD11
SD12
SD13 23
24
22
21
19
20
17
18
15
16
X2
18
20
22
24
26
28
1
Rx
RS232
Tx 3
Rx 2
0V 5
RTS 7
DTR 4
Tx
17
18
RS485
3
2
4
1
5
+
-
GND
Power supply Vdc
OPTIONAL
Open command
Not configured
Synchronization
Not configured
Not configured
Not configured
Not configured
Close command
52 status
Glass O.F.
Plastic O.F.
Port 1A
RS232
Front
Port 1B
Rear
OPTIONAL
Port 2
Rear
HW status
Not configured
Not configured
Neutral trip
Phase trip
Close
General trip
T9 (I0) polarization
Figure 1.9. dc model with polarization with 67N current (V0calculated, cod. DC **1*****11)
Table of contents
Other Ormazabal Relay manuals