FANOX SIA D User manual

www.fanox.com SIA-D_Rev. 07 1 / 117
ISO 9001:2008
USER MANUAL
SIA D
Overcurrent relay

www.fanox.com SIA-D_Rev. 07 2 / 117
ISO 9001:2008
1.RECEPTION, HANDLING, INSTALLATION....................................................................................6
1.1.UNPACKING .........................................................................................................................................6
1.2.RECEPTION OF RELAYS ........................................................................................................................6
1.3.HANDLING ELECTRONIC EQUIPMENT ......................................................................................................6
1.4.INSTALLATION,COMMISSIONING AND SERVICE........................................................................................6
1.5.STORAGE ............................................................................................................................................7
1.6.RECYCLING..........................................................................................................................................7
2.DIMENSIONS AND CONNECTION DIAGRAMS.............................................................................8
2.1.CASE DIMENSIONS MM .........................................................................................................................8
2.2.KITCOM DIMENSIONS .........................................................................................................................9
2.3.CONNECTION DIAGRAMS ......................................................................................................................9
2.3.1.3 Phase CT and neutral CT Connection (Revision A)..............................................................9
2.3.2.3 Phase CT and residual neutral Connection (Revision A).....................................................10
2.3.3.3 Phase CT and neutral CT Connection (Revision B)..............................................................10
2.4.TERMINALS ..........................................................................................................................................11
2.4.1.Terminals of Revision A models ...............................................................................................11
2.4.2.Terminals of Revision B models ...............................................................................................12
3.DESCRIPTION..................................................................................................................................13
3.1.INTRODUCTION.....................................................................................................................................13
3.2.EQUIPMENT DESCRIPTION.....................................................................................................................13
3.3.FUNCTIONS DIAGRAM...........................................................................................................................16
3.4.PHASE CT AND NEUTRAL CT SELECTION...............................................................................................16
3.5.MODEL LIST SIA-D...............................................................................................................................18
3.6.REVISIONS HISTORIC ...........................................................................................................................20
4.PROTECTION FUNCTIONS AND FEATURES................................................................................21
4.1.POWER SUPPLY ...................................................................................................................................21
4.2.50P FUNCTION.PHASE INSTANTANEOUS PHASE OVERCURRENT .............................................................21
4.3.51P FUNCTION.PHASE INVERSE TIME OVERCURRENT............................................................................22
4.4.50N FUNCTION.NEUTRAL INSTANTANEOUS OVERCURRENT....................................................................22
4.5.51N FUNCTION.NEUTRAL INVERSE TIME OVERCURRENT........................................................................23
4.6.TRIP BLOCKING PROTECTION FOR THE SWITCHGEAR ..............................................................................23
4.7.FUNCTION 52. CIRCUIT BREAKER MONITORING ......................................................................................24
4.7.1.Circuit breaker opening and closing commands.......................................................................25
4.7.2.Counter to register the number of openings.............................................................................26
4.7.3.Accumulated amps counter: I2t ................................................................................................26
4.7.4.Excessive openings in a time window ......................................................................................26
4.8.67N1 AND 67N2 FUNCTION.NEUTRAL DIRECTIONAL OVERCURRENT PROTECTION..................................26
4.9.TRIPPING BUS......................................................................................................................................28

www.fanox.com SIA-D_Rev. 07 3 / 117
ISO 9001:2008
4.10.EQUIPMENT SETTINGS ..........................................................................................................................32
4.11.IEC255-4/BS142 CURVES ..................................................................................................................35
5.MONITORING AND CONTROL........................................................................................................39
5.1.MEASUREMENTS..................................................................................................................................39
5.2.STATUS AND EVENTS ...........................................................................................................................39
5.3.REAL-TIME CLOCK (RTC) .....................................................................................................................44
5.4.OSCILLOGRAPHY AND FAULT REPORTS .................................................................................................44
5.5.DATA DIAGRAM:ALLOCATION OF INPUTS AND OUTPUTS CONFIGURATION .................................................48
5.6.CONFIGURABLE INPUTS ........................................................................................................................49
5.7.CONFIGURABLE OUTPUTS .....................................................................................................................50
5.8.SELF-DIAGNOSIS..................................................................................................................................50
5.9.COMMUNICATION .................................................................................................................................51
5.10.FRONT COMMUNICATION.RS232 .........................................................................................................51
5.11.REAR COMMUNICATION.RS485 ...........................................................................................................52
5.12.MODBUS RTU PROTOCOL....................................................................................................................53
5.13.TEST PROGRAM...................................................................................................................................53
6.TECHNICAL SPECIFICATIONS AND STANDARDS......................................................................55
6.1.TECHNICAL SPECIFICATIONS.................................................................................................................55
6.2.STANDARDS.........................................................................................................................................59
7.USER INTERFACE...........................................................................................................................62
7.1.BISTABLE MAGNETIC INDICATORS..........................................................................................................62
7.2.LED INDICATORS .................................................................................................................................62
7.3.RS232 COMMUNICATIONS PORT...........................................................................................................63
7.4.LCD AND KEYPAD ................................................................................................................................63
7.5.SICOM COMMUNICATIONS PROGRAM ....................................................................................................63
7.6.SETTING-UP THE SESSION:PASSWORD AND ACCESS LEVELS.PROTECTED SETTINGS..............................64
7.7.MENUS..............................................................................................................................................65
7.7.1.Standby mode screen...............................................................................................................65
7.7.2.Accessing the menus................................................................................................................65
7.7.3.Date-time menu ........................................................................................................................65
7.7.4.Versions....................................................................................................................................66
7.7.5.Communication parameters......................................................................................................66
7.7.6.Fault report................................................................................................................................67
7.7.7.Test Menu.................................................................................................................................67
7.7.8.Functions Menu ........................................................................................................................67
7.7.9.Measurements Menu................................................................................................................68
7.7.10.Status Menu..............................................................................................................................68
7.7.11.Settings Menu...........................................................................................................................70
7.7.12.Events Menu.............................................................................................................................72

www.fanox.com SIA-D_Rev. 07 4 / 117
ISO 9001:2008
7.7.13.Counters Menu .........................................................................................................................72
7.7.14.Commands Menu......................................................................................................................73
7.7.15.Input Configuration menu..........................................................................................................73
7.7.16.Output Configuration menu.......................................................................................................74
8.COMMISSIONING.............................................................................................................................76
8.1.CHECKLIST FOR COMMISSIONING..........................................................................................................76
8.2.INSPECTION .........................................................................................................................................76
8.3.ELECTROSTATIC DISCHARGE ................................................................................................................76
8.4.VISUAL INSPECTION .............................................................................................................................76
8.5.EARTHING ...........................................................................................................................................76
8.6.CURRENT TRANSFORMERS ...................................................................................................................76
8.7.AUXILIARY POWER................................................................................................................................76
8.8.RS232 FRONT COMMUNICATIONS PORT ................................................................................................76
8.9.COMMISSIONING ..................................................................................................................................77
9.PROTOCOL ......................................................................................................................................78
9.1.MODBUS PACKAGED FORMAT................................................................................................................79
9.2.FUNCTION CODES ................................................................................................................................80
9.3.EXEMPTIONS AND ERROR ANSWERS......................................................................................................80
9.4.DATA TYPE ..........................................................................................................................................81
9.5.MEMORY MAP OF SIA-D.......................................................................................................................82
9.6.GENERAL STATUS MAP ........................................................................................................................83
9.7.COUNTERS MAP ..................................................................................................................................84
9.8.COMANDS MAP ....................................................................................................................................85
9.9.MEASURES MAP ..................................................................................................................................85
9.10.PROTECTION CRITERIA MAP .................................................................................................................85
9.11.PROTECTION STATUS MAP ...................................................................................................................87
9.12.EVENTS LIST ........................................................................................................................................99
9.13.SETTINGS MAP ....................................................................................................................................101
9.14.EXAMPLES OF MODBUS FRAMES...........................................................................................................106
9.14.1.Writing the access password “5555” to equipment nº 1 ...........................................................106
9.14.2.Reading the 4 measurements from the primary winding to equipment nº 1.............................107
9.14.3.Reading the protection status of equipment nº 1......................................................................108
10.APPENDIX ........................................................................................................................................109
10.1.IDENTIFICATION....................................................................................................................................109
10.2.CHECKS ..............................................................................................................................................111
10.3.TEST MENU..........................................................................................................................................111
10.4.REGISTER OF COMMISSIONING SETTINGS...............................................................................................111
10.4.1.CT Ratio:...................................................................................................................................111
10.4.2.50P:...........................................................................................................................................111

www.fanox.com SIA-D_Rev. 07 5 / 117
ISO 9001:2008
10.4.3.50N:...........................................................................................................................................111
10.4.4.51P:...........................................................................................................................................112
10.4.5.51N:...........................................................................................................................................112
10.4.6.67N1..........................................................................................................................................112
10.4.7.67N2..........................................................................................................................................112
10.4.8.Breaker:.....................................................................................................................................112
10.4.9.Circuit breaker...........................................................................................................................113
10.4.10.Tripping Bus..............................................................................................................................113
10.5.INPUT CONFIGURATION .........................................................................................................................113
10.6.OUTPUT CONFIGURATION .....................................................................................................................114
10.7.COMMENTS..........................................................................................................................................115
10.8.NOTES: .............................................................................................................................................116

www.fanox.com SIA-D_Rev. 07 6 / 117
ISO 9001:2008
1. RECEPTION, HANDLING, INSTALLATION
1.1. Unpacking
Relays must only be handled by qualified personnel and special care must be taken to protect all of
their parts from any damage while they are being unpacked and installed. The use of good
illumination is recommended to facilitate the equipment visual inspection.
The facility must be clean and dry and relays should not be stored in places that are exposed to dust
or humidity. Special care must be taken if construction work is taking place.
1.2. Reception of relays
It is necessary to inspect the equipment at the time it is delivered to ensure that the relays have not
been damaged during transport.
If any defect is found, the transport company and FANOX should be informed immediately.
If the relays are not for immediate use, they should be returned to their original packaging.
1.3. Handling electronic equipment
Relays contain an electronic component that is sensitive to electrostatic discharges.
Just by moving, a person can build up an electrostatic potential of several thousand volts.
Discharging this energy into electronic components can cause serious damage to electronic circuits.
It is possible that this damage may not be detected straight away, but the electronic circuit reliability
and life will be reduced. This electronic component in the equipment is well protected by the metal
housing, which should not be removed as the equipment cannot be adjusted internally.
If it is necessary to disassemble the electronic component, this must be carried out with care and
contact with electronic components, printed circuits and connections must be avoided to prevent an
electrostatic discharge that could damage one of the components. If the electronic components are
stored outside the metal housing, they must be placed in an antistatic conductive bag.
If it is necessary to open a module, care must be taken to preserve the equipment reliability and the
duration of the life cycle as designed by the manufacturer by taking the following actions:
•Touch the housing to ensure that you have the same potential
•Avoid touching the electronic components and handle the module by its edges.
•Remember that everyone who handles the module must have the same potential.
•Use a conductive bag to transport the module.
For more information about how to handle electronic circuits, consult official documents such as the
IEC 147-OF.
1.4. Installation, commissioning and service
The personnel in charge of installing, commissioning and maintaining this equipment must be
qualified and must be aware of the procedures for handling it. The product documentation should be
read before installing, commissioning or carrying out maintenance work on the equipment.
Personnel should take specific protection measures to avoid the risk of electronic discharge when
access is unlocked on the rear part of the equipment.

www.fanox.com SIA-D_Rev. 07 7 / 117
ISO 9001:2008
In order to guarantee safety, the crimp terminal and a suitable tool must be used to meet isolation
requirements on the terminal strip. Crimped terminations must be used for the voltage and current
connections.
It is necessary to connect the equipment to earth through the corresponding terminal, using the
shortest possible cable. As well as guaranteeing safety for the personnel, this connection allows high
frequency noise to be evacuated directly to earth.
The following checks must be performed before the equipment is supplied:
•The rated voltage and polarity.
•The power rating of the CT circuit and the integrity of the connections.
•The integrity of the earth connection.
The equipment must be used within the stipulated electrical and environmental limits.
Note: Regarding the current transformer circuits: Do not open a live CT secondary circuit. The high
voltage produced as a result could damage the isolation and threaten lives.
1.5. Storage
If the relays are not going to be installed immediately, they must be stored in a dust- and humidity
free environment after the visual inspection has been performed.
1.6. Recycling
Before recycling the equipment, the capacitors should be discharged through the external terminals.
All electrical power sources should be removed before performing this operation to avoid the risk of
electrical discharge.
This product must be disposed of in a safe way. It should not be incinerated or brought into contact
with water sources like rivers, lakes, etc…

www.fanox.com SIA-D_Rev. 07 8 / 117
ISO 9001:2008
2. DIMENSIONS AND CONNECTION DIAGRAMS
2.1. Case Dimensions mm

www.fanox.com SIA-D_Rev. 07 9 / 117
ISO 9001:2008
2.2. KITCOM Dimensions
2.3. Connection Diagrams
2.3.1. 3 Phase CT and neutral CT Connection (Revision A)

www.fanox.com SIA-D_Rev. 07 10 / 117
ISO 9001:2008
2.3.2. 3 Phase CT and residual neutral Connection (Revision A)
2.3.3. 3 Phase CT and neutral CT Connection (Revision B)

www.fanox.com SIA-D_Rev. 07 11 / 117
ISO 9001:2008
2.4. Terminals
2.4.1. Terminals of Revision A models
A1 A-phase current input for metering D1 Input common
A2 A-phase current output for metering D2 Input 1
A3 B-phase current input for metering D3 Input 2
A4 B-phase current output for metering D4 Input 3

www.fanox.com SIA-D_Rev. 07 12 / 117
ISO 9001:2008
A5 C-phase current input for metering D5 Input 4
A6 C-phase current output for metering E1-E2 Output 1
A7 Neutral current input for metering E3-E4 Output 2
A8 Neutral current output for metering E5-E6 Output 3
B1 RS485 – gnd E7-E8 Output 4
B2 RS485 – B- V1 Auxiliary voltage +
B3 RS485 – A+ V2 Auxiliary voltage -
C1 Voltage neutral input ╧Grounding bolt
C2 Neutral voltage output
2.4.2. Terminals of Revision B models
A1 A-phase current input for metering D1 Input common
A2 A-phase current output for metering D2 Input 1
A3 B-phase current input for metering D3 Input 2
A4 B-phase current output for metering D4 Input 3
A5 C-phase current input for metering D5 Input 4

www.fanox.com SIA-D_Rev. 07 13 / 117
ISO 9001:2008
A6 C-phase current output for metering E1-E2 Output 1, NC contact
A7 Neutral current input for metering E3-E4 Output 2
A8 Neutral current output for metering E5-E6 Output 3
B1 RS485 – gnd E7 Output 4, NO contact
B2 RS485 – B- E8 Output 4, common contact
B3 RS485 – A+ E9 Output 4, NC contact
C1 Voltage neutral input V1 Auxiliary voltage +
C2 Neutral voltage output V2 Auxiliary voltage -
╧Grounding bolt
3. DESCRIPTION
3.1. Introduction
Worldwide, the energy sector is currently undergoing a profound change as a result of high levels of
energy demand; more distribution lines and advanced supervision systems are required. Given the
need for creating intelligent infrastructure, FANOX has developed the SIA family of products to carry
out this function.
The family of SIA relays is designed to protect the secondary transformation and distribution centres
of electricity grids. Protection features include protection against instantaneous and inverse time
overcurrent (for the phases and the neutral), and it also has external trip support (temperature,
pressure, etc.) depending on the characteristics of each model.
The protection functions can be enabled selectively by using both the front panel and the
communications links to the SIcom program, allowing for precise coordination with other equipment.
Additional benefits include that all of the models have been designed to be supplied from an external
battery. This is aimed at facilitating event management and the commissioning of centres, as well as
allowing it to operate properly under adverse conditions.
3.2. Equipment description
The SIA-D equipment is a protection relay designed for secondary distribution.
It is supplied with 110-230 Vac / 90-300 Vdc auxiliary voltage. It is possible to choose 24-48 Vdc
auxiliary for each model. As for the rest of the SIA family, it can be supplied through its front RS-232
communications port via an external battery, using the KITCOM adapter. This facilitates the start-up
of the centres and the management of events. The operation of the outputs is not guaranteed when
the SIA-D equipment is supplied from an external battery.
As well as the functions to protect against instantaneous phase and neutral overcurrents and phase
and neutral inverse time overcurrents, it is possible to choose two neutral directional units or one
isolated neutral directional unit for each model. It is also equipped with a trip blocking to protect the
switchgear in centres that combine switchgear and fuses.
All models include a breaker management block, which monitors the switch condition, the number of
breaks and the accumulated amps. It generates an indication if these are excessive, it determines
whether or not an Opening fault has occurred and allows the breaker close and open commands
from the HMI and via the communications port (either locally or remotely).
Revision B includes in all the models two new characteristics:

www.fanox.com SIA-D_Rev. 07 14 / 117
ISO 9001:2008
•A general states bit which monitories 48 Vdc power source
•Tripping Bus (which requires two inputs and two outputs)
The SIA-D equipment has four inputs and four outputs
that can be configured by the user.
In order to facilitate the analysis of events, it is fitted
with two oscillographic records, each one with 33
cycles: 3 prefault cycles and 30 postfault cycles.
The oscillograph start can be configured by the user.
Each oscillographic record shows the phase and
neutral currents, the neutral voltage and up to 64 digital
channels, which include pick-ups and trips of the
protection functions, inputs, outputs, etc. The
COMTRADE format is used (IEEE C37.111-1991).
The SIA-D equipment is housed in a metal box with
galvanic isolation on all of its measurement or digital
inputs and outputs (with the exception of ports for
communications and battery power supply, as these are
sporadic connections). This allows the equipment to
have the best possible level of electromagnetic
compatibility, both in terms of emission of, and immunity from, radiated and conducted interferences.
These levels are the same as those established for primary substations.
The equipment has a LCD with two lines and twenty columns and a membrane keyboard with six
buttons. These allow the display of the equipment status, the current measurements in the primary
and the events or incidents associated with the equipment, and adjustments to be made to the
protection criteria. Depending on the model, these events can be saved in a non-volatile memory to
save them in case of power failures.
There are three bistable magnetic indicators on the front of the SIA-D equipment. These indicate the
causes of trips, and continue to signal the indication even if the relay loses power. It is also fitted with
three LED indicators, which blink to show the type of supply that is being used at any time.
The equipment has storage for up to 500 events, allowing any recorded incidents to be analysed. All
SIA-D models are equipped with a real-time clock (RTC).
Current measurements are performed using RMS values, with an accuracy of 2%. Standard 5 A and
1 A current transformers (CTs) are used.
The equipment has two communication ports: a front port (RS232) and an optional rear port
(RS485). The RS232 port allows a PC to be connected, which can be used to monitor the equipment
using the SICom communications program (supplied by FANOX). A 12V battery can also be used to
power the equipment through this front port by using the adapter (KITCOM). The rear port RS485
allows the equipment to be integrated as part of a system (SCADA). The Modbus RTU protocol is
used in both ports. Setting-up a session allows four levels of access to be set up with passwords that
can be configured by the user.
The protective functions provided, easy-to-use interface, low amount of maintenance and simple
integration make the SIA-D a precise and practical solution for protecting both industrial and public
electrical grids and transformation and distribution centres. It even provides these protective
functions in situations where auxiliary power sources are not available or not reliable. The protection
offered by the SIA-D against earth faults is sensitive enough to be used in electric systems where the
earth fault current is low. It can be set to 0.2 times the rated neutral current and, depending on the
model, the rated neutral current can go as low as 0.1 A.
The main features of the equipment are listed below, and these features will be explained in the rest
of the manual:
Function Description SIA-D
Protection

www.fanox.com SIA-D_Rev. 07 15 / 117
ISO 9001:2008
50P Phase instantaneous overcurrent protection function 1
50N Neutral instantaneous overcurrent protection function 1
51P Phase inverse time overcurrent protection function 1
51N Neutral inverse time overcurrent protection function 1
Fuse + Switchgear Trip blocking to protect the switchgear 1
67N Neutral directional overcurrent protection 2 (optional)
67NA Isolated neutral directional overcurrent protection 1 (optional)
Circuit breaker
Status and control of the circuit breaker 9
Number of breaks 9
Accumulated amps 9
Function Description SIA-D
Measurements
Phase and neutral RMS measurement with 2% accuracy 9
Inputs and Outputs
Configurable Inputs 4
Configurable outputs 4
Communication and HMI
Front port: RS232 (ModBus, RTU 19200) 9
Rear port: RS485 (ModBus, RTU 19200) Optional
SICom Program 9
Login in: 4 access levels with configurable passwords 9
Control and signalling
HMI: LCD, 20x2 and 6 keys + 1 reset button 9
Bistable magnetic indicators Up to 3
LED Indicators Up to 3
Tripping Bus (2 inputs and 2 outputs) (3*) 9
Power supply
Auxiliary voltage 110-230 Vac / 90-300 Vdc 9
Auxiliary voltage: 24-48 Vdc Optional
Battery power: 12V with an RS232 adapter (2) 9

www.fanox.com SIA-D_Rev. 07 16 / 117
ISO 9001:2008
Monitoring and Recording
Events saved in the volatile RAM* memory (1) 9
Events saved in the non-volatile FRAM* memory Optional
Real-Time Clock (RTC) 9
Oscillographic records 2 (optional)
Test menu 9
Self-diagnosis 9
(1) Events stored in the RAM are deleted in the case of electrical power failure. Events recorded in the FRAM are
saved if there is a power failure, as it is a non-volatile memory. A maximum of 500 events can be stored.
(2) The operation of the outputs is not guaranteed when battery power is used.
(3*) Available only in Revision B models.
3.3. Functions Diagram
3.4. Phase CT and neutral CT selection
The following table shows a summary of phase and neutral CT combinations:
Model Phase Neutral Phase range Neutral range

www.fanox.com SIA-D_Rev. 07 17 / 117
ISO 9001:2008
SIAD55 CT 5 A Residual phase connection 1-150 A 1-150 A
SIAD11 CT 1 A Residual phase connection 0,2-30 A 0,2-30 A
SIAD51 CT 5 A CT 1 A 1-150 A 0,2-30 A
SIAD5A CT 5 A CT 0,1 A 1-150 A 0,02-3 A
SIAD1A CT 1 A CT 0,1 A 0,2-30 A 0,02-3 A
SIAD5B CT 5 A CT 0,2 A 1-150 A 0,04-6 A
SIAD1B CT 1 A CT 0,2 A 0,2-30 A 0,04-6 A
In order to assure a correct running of the relay, it is necessary to use the proper current
transformer. Therefore, the load of measurement circuits of the relay and the load of connection
cables between CT’s and relay must be taken into account.
PRECISSION
BURDEN
RELAYS
5P100,5VASIA‐D/1
5P200,5VASIA‐D/1
5P300,5VASIA‐D/1
5P101VASIA‐D/5
5P201VASIA‐D/5
5P301VASIA‐D/5
LOAD CURVE FOR RELAY SIA-D/1

www.fanox.com SIA-D_Rev. 07 18 / 117
ISO 9001:2008
LOAD CURVE OF RELAY SIA-D/5
3.5. Model list SIA-D
TYPE
PHASE MEASURE
NEUTRAL MEASURE
NET PREQUENCY
SUPPLY
EXTRA FUNCTION
COMMUNICATIONS
INPUTS/ OUPTUTS
EVENTS
LANGUAGE
REVISION
D 50P + 51P + 50N + 51N + 52
1
2
5
1 A
2 A
5 A
A
B
1
5
0,1 A
0,2 A
1 A
5 A
5
6
7
8
50 Hz + Breaker
50 Hz + Circuit Breaker
60 Hz + Breaker
60 Hz + Circuit Breaker
2
3
110-230 Vac 90-300 Vdc
24-48 Vdc

www.fanox.com SIA-D_Rev. 07 19 / 117
ISO 9001:2008
0
1
2
Without 67N
With 67N1 and 67N2
With67NA (isolated neutral)
0
1
ModBus (RS 232)
ModBus (RS 232) and(RS 485)
2 4O + 4I
0
1
2
With volatile RAM memory
With non-volatile RAM memory
With non-volatile RAM (events + osc)
A
B
C
English, Spanish, French
English, Spanish, French, Turkish
English, Spanish, French, Polish
-
A
B
First Revision
Second Revision
Third Revision

www.fanox.com SIA-D_Rev. 07 20 / 117
ISO 9001:2008
3.6. Revisions Historic
Revisions Hardware Software
A All the models with RTC Multilanguage
B Output 4 of revision A was normally open and
in revision B provides the contact normally
open and the contact normally closed.
All the models with Tripping bus
and one bit for power supply
monitoring.
Table of contents
Other FANOX Relay manuals

FANOX
FANOX SIA-C User manual

FANOX
FANOX SIL-A User manual

FANOX
FANOX SIL-A User manual

FANOX
FANOX D30 User manual

FANOX
FANOX SIA B User manual

FANOX
FANOX DM30 User manual

FANOX
FANOX SIA-C User manual

FANOX
FANOX SIL-A A Series User manual

FANOX
FANOX SIL-D00 User manual

FANOX
FANOX SIA-B Standard Series User manual