oventrop R-Tronic RT B User manual

Valves, controls + systems
"R-Tronic RT B / RTF B / RTFC K"
Wireless receiver "R-Con"
Installation and operating instructions
EN
"R-Tronic"
Climate display device/control

Extent of supply "R-Tronic" + "R-Con"
2
Thank you for purchasing this wireless thermostat with wireless receiver for
temperature control of surface heating systems. Please check the delivery
for completeness. It consists of the following components (depending on the
ordered model):
"R-Tronic RT B"
(Temperature)
"R-Tronic RTF B"
(Temperature/Air humidity)
"R-Tronic RTFC K"
(Temperature / Air humidity / CO2)
"R-Tronic RTFC K"
(Temperature / Air humidity / CO2)
Flush-mounted power pack with
wall bracket (Item no.: 1150682)
Battery operation (Item no.: 1150680)
Mains adaptor with table stand
(Item no.: 1150684)
Battery operation (
Item no
.: 1150681)
"R-Con" 4 channel wireless receiver
with logic module
(Item no.: 1150770)
"R-Con" 8 channel wireless receiver
with logic module
(Item no.: 1150772)
"R-Con" 8 channel wireless receiver
without logic module (Item no.:
1150773)
"R-Con" 4 channel wireless receiver
without logic module (Item no.:
1150771)

"R-Tronic" + "R-Con" Accessories
3
Flush-mounted power pack with
wall bracket (Item no.: 1150692)
optional for the models:
"R-Tronic RT B" / "RTF B"
Mains adaptor with table stand
(Item no.: 1150694)
optional for the models:
"R-Tronic RT B" / "RTF B"
Accessories wireless thermostat "R-Tronic":
Accessories wireless receiver "R-Con":
Aktor T 2P 230 V AC or 24 V DC
Valve connection M 30 x 1.5
(Item no.: 1012415 / 1012416)
Wireless repeater RP-C F
(signal amplication,
ush mounting, 230 V/50 Hz)
(Item no.: 1153060)
Wireless repeater RP-S F
(signal amplication, operation in
earthed socket; Item no.: 1150699)

Content "R-Tronic" + "R-Con"
4
1. General information 6
2. Safety notes 8
2.1 Intended use 8
2.2 Residual risks and fundamental dangers 8
2.3 Warnings and their meaning 9
2.4 High-frequency emissions of wireless sensors 9
3. Product description 10
3.1 Summary 10
3.2 Technical data 16
3.3 Note regarding declaration of conformity 18
3.4 General conditions of sales and delivery 18
4. Installation and initial operation 19
4.1 General installation advice 19
4.2 Wall attachment of xing plate "R-Tronic RT B / RTF B" (battery operation) 20
4.3 Wall attachment of xing plate with ush-mounted power pack ("RTFC K") 21
4.4 Installation with table stand and mains adaptor ("RTFC K") 22
4.5 Installation and operation of the wireless receiver "R-Con" 23
4.5.1 Fixing of the wireless receiver "R-Con" to the mounting rail 23
4.5.2 Operation of the rotary switch at the wireless receiver "R-Con" 24
4.5.3 Electrical connection of the wireless receiver "R-Con" with actuators 25
4.5.4 Extension of the wireless receiver by further modules 30
4.5.5 Cabling of the logic module with burner and pump 33
4.5.6 Connection of the wireless receiver to the 230 V network 35
4.5.7 Summary connection diagram 230 V and 24 V 36
4.5.8 Use of antenna, extension and wireless repeater 37
4.6 Creation of radio communication between "R-Tronic" and "R-Con" 38
4.6.1 Setting date and time at wireless thermostat "R-Tronic" 38
4.6.2 Adaptation of "R-Con" channels to "R-Tronic" ("teach in") 39
4.6.3 Termination of the radio communication ("teach out") 42
4.6.4 Factory settings control module "R-Con T 2P" 44
4.6.5 Deletion of individual wireless thermostats "R-Tronic" 45
4.6.6 "Emergency operation" of control module "R-Con T 2P" 46
4.7 Controller settings at the wireless receiver "R-Con" 46
4.7.1 Selection of the operating mode 46
4.7.2 Settings at the logic module 50
4.8 Standard heating proles and temperature setting 53
4.8.1 Switching between different heating proles 53
4.8.2 Setting of the required temperature via NOMINAL SETTING 55

"R-Tronic" + "R-Con" Content
5
5 Operation and menu structure of the wireless thermostat "R-Tronic" 56
5.1 Menu "Time prole" 57
5.2 Menu "Temperatures" 62
5.2.1 Setting of the general temperature range 63
5.3 Menu "Functions" 64
5.3.1 Vacation function (setback temperature during absence) 64
5.3.2 "Party mode" (required temperature during a dened period) 66
5.3.3 Child-proof lock (operation lock) 67
5.3.4 Valve protection 67
5.4 Menu "Settings" 68
5.4.1 Installation (radio communication between "R-Tronic" and "R-Con") 68
5.4.2 Date and time 69
5.4.3 Language 69
5.4.4 Default view display 70
5.4.5 OFFSET TEMPERATURE control "R-Tronic" 70
5.4.6 Combined control of surface heating circuit and radiator 71
5.4.7 Summer-/winter time 72
5.4.8 Display lighting (ON/OFF) 72
5.4.9 Assignment of the room designation to the "R-Tronic" 72
5.4.10 Factory settings "R-Tronic" 73
5.4.11 Restart "R-Tronic" 73
5.5 Menu "Room climate" (only "R-Tronic RTFC K") 74
5.6 Menu "Information" 75
5.7 Battery replacement "R-Tronic" 77
6 Disposal 78
7 Display notes and error messages 79
8 Schematic menu overview 82
9 Air humidity and "comfort diagram" 83
10 Illustration index 84

General information "R-Tronic" + "R-Con"
6
1. General information
These installation and operating instructions refer to the different models of
the Oventrop climate display device/control "R-Tronic" and the associated
wireless receiver "R-Con".
The installation and operating instructions which are intended for installers
and nal consumers, serve to install the wireless thermostats "R-Tronic RT B",
"R-Tronic RTF B" and "R-Tronic RTFC K" and the wireless receiver "R-Con"
professionally, to put them into operation and to use them correctly. The same
applies for the optional accessories.
NOTE
Read installation and operating instructions in their entirety before installing
the climate display device/control "R-Tronic" and the wireless receiver
"R-Con". This will allow an (energy) efcient use of the products.
Advice for installers: The installation and operating instructions as well as
all other valid documents have to be handed over to the nal user.
Please complete the handover report supplied with the product.
This documentation has to be kept for later reference and has to be handed
over to the new owner in case of resale.
The installation and operating instructions are copyrighted!
Please contact your specialist heating company or the company Oventrop if
malfunctions or further questions occur.
Manufacturer and contact
Oventrop GmbH & Co. KG
Paul-Oventrop-Straße 1
D-59939 Olsberg, Germany
Technical Support
Phone: +49 (0) 29 62 82-234 (Mo.-Fr. 7:30-16:30 h)
Fax: +49 (0) 29 62 82-602
Mobile box: +49 (0) 29 62 82-333
E-mail: [email protected]

"R-Tronic" + "R-Con" General information
7
NOTE regarding storage and packaging
The following instructions regarding storage of the climate display device/
control "R-Tronic", wireless receiver "R-Con" and optional accessories must
be observed:
• Do not store the components in open air, keep dry and free from dust.
• Do not expose to aggressive uids or heat sources.
• Protect from direct sunlight and mechanical agitation.
• Storage temperature: -10 °C … +65 °C
• Max. relative air humidity: 70% RH ("relative humidity")
• Packaging material is to be disposed of environmentally friendly.
• Keep the packaging material out of reach of children.

Safety notes "R-Tronic" + "R-Con"
8
2. Safety notes
2.1 Intended use
The wireless thermostat "R-Tronic" and wireless receiver "R-Con" are used for
the wireless temperature control of rooms with surface heating circuits. The
wireless thermostats "R-Tronic" are not only used for menu navigation and
setting of heating programmes but temperature, air humidity and CO2 values
(depending on the model) are also displayed.
Safety in operation is only guaranteed if the wireless thermostats "R-Tronic"
and the wireless receiver "R-Con" are used correctly. Please observe that only
Oventrop accessories (power packs etc.) must be installed. Any use of the
wireless thermostats "R-Tronic RT B", "RTF B", "RTFC K" and the wireless
receiver "R-Con" outside the above applications will be considered as non-
compliant and misuse.
2.2 Residual risks and fundamental dangers
Even though the product combination "R-Tronic + R-Con" is in accordance
with the latest technical status and the approved safety rules and regulations,
dangers do still exist. For this reason, the following safety notes must be
observed:
• The ush-mounted power pack of the "R-Tronic" has to be connected to
the 230 V network. Connection must only be carried out by a qualied
electrician. Switch off the current supply before cabling! Avoid dangers
from electricity!
• The occupational health and accident prevention regulations must be
observed during installation.
• Distributor/collector components for surface heating systems may
present a risk of scalding (hot surfaces, hot water). Avoid mechanical
risks and risk of re.
• The wireless thermostat and wireless receiver must only be installed in
dry, closed rooms.
• Provide protective equipment (safety gloves and similar) during
installation, if required.
• Keep small components and accessories out of reach of children (risk of
ingestion).
• Please observe that excessive room temperatures may cause health
problems (cardiovascular problems or similar).
• Please avoid any contact with the products if allergies against the used
material are known.
• Avoid frost damages caused by too low ow temperatures.

"R-Tronic" + "R-Con" Safety notes
9
NOTICE
Signal warning (without a symbol) indicating a possible damage to
property.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could
result in death or serious injury.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, may
result in minor or moderate injury.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will
result in death or serious injury.
2.3 Warnings and their meaning
This manual shows warnings for a safe installation and operation of the
product, especially at text passages with action-related information. These
warnings must be observed to avoid accidents, damage to property and
malfunctions. The below hazard classi cation is, amongst others, based on
the ISO 3864 standard and the international ANSI standard Z536.6.
2.4 High-frequency emissions of wireless sensors
Under normal conditions (use in residential areas), the use of this product does
not constitute a hazard to health. The high-frequency emissions of wireless
switches and sensors with wireless technology are much lower than the
emissions of conventional switches which also emit electromagnetic elds.
Please observe that special regulations and standards apply for the
medical sector (such as hospitals). The wireless thermostat "R-Tronic"
with the wireless receiver "R-Con" is not suitable for use in the medical
sector.

Product description "R-Tronic" + "R-Con"
10
3. Product description
3.1 Summary
The wireless thermostat "R-Tronic" and wireless receiver "R-Con" are used for
the programmable temperature control of rooms with surface heating circuits.
The radio communication between the "R-Tronic" and "R-Con" is wireless.
One wireless thermostat may communicate with the wireless receiver via a
maximum of 8 channels (mains operation).
Depending on the model, the "R-Tronic" is powered by two batteries, a ush-
mounted power pack or a mains adaptor (100-240 V ~/50-60 Hz). The wireless
thermostats requires a 230 V alternating voltage.
"R-Tronic" models:
• "R-Tronic RT B":
Temperature display and programmable temperature control, battery
operation by default, power supply can also be carried out via a ush-
mounted power pack or a mains adaptor which are available as optional
accessory (item no. 1150692 or 94).
• "R-Tronic RTF B":
Temperature display, programmable temperature control and air
humidity measurement, battery operation by default, power supply can
also be carried out via a ush-mounted power pack or a mains adaptor
which are available as optional accessory (item no. 1150692 or 94).
• "R-Tronic RTFC K":
Temperature display, programmable temperature control and air
humidity and CO2 measurement powered by a ush-mounted power
pack or a mains adaptor by default.
• "R-Con" 8 channel wireless receiver with logic module:
Control of 8 independent heating circuits (a maximum of 32 actuators
230 V or 24 V can be connected to the distributor/collector for surface
heating, a maximum of 32 heating circuits may thus be controlled). The
number of channels can be increased by extending the wireless receiver
by further control modules.
Integrated burner logic for heat demand to a boiler.
Integrated pump logic with adjustable lead time and follow-up time.
Depending on the spatial conditions, an antenna extension for
improvement of reception and/or a repeater (item no. 1153060 / 1150699)
for amplication of the "R-Tronic" radio signals are used.

"R-Tronic" + "R-Con" Product description
11
(Illustration 1)
Application showing the wireless receiver with wireless thermostats "R-Tronic"
and heating system (exemplary sketch):
"R-Tronic"
Room 2
Repeater (opt.)
"R-Tronic"
Room 1
"R-Con"
Distributor/collector
with actuators
Pump Burner

Product description "R-Tronic" + "R-Con"
12
Operating mode and time prole (above display):
Operation mode
AUTO/MANU
Day of
the week
Time
Setting of comfort temperature
Operating mode
andtimeprole
Display:
Symbols and
display units
Menu-button:
Navigation and
nominal setting
by turning (to the left/right)
and pressing for
conrmation
Text line supplies
information on:
-Measured values
-Menu structure
-Diagnostic
(error/advice)
Return-button: Previous menu
level; keep pressed for 3 seconds:
return to default view
Auto/Manu
button:
Switching between
the standard
heating proles
(Illustration 2)
NOTE regarding display lighting:
The display lighting of the battery operated "R-Tronic" models (RT B / RTF B)
is deactivated by default. Activation of the display lighting is described under
paragraph 5.4.8.
The display lighting of the mains operated "R-Tronic RTFC K" is activated by
pressing one of the three buttons.

"R-Tronic" + "R-Con" Product description
13
Explanation of "R-Tronic" display symbols:
Child-proof lock
activated
Window open
(sensor controlled)
Recommendation for
room ventilation (only
"R-Tronic RTFC K"
Battery status
(fully charged,
low, empty)
Wireless control
active (at least) one
"teached in" channel
Current supply
via external
power pack
Heating
period
active
Display of
notes and
error messages
Cooling active
-in preparation-

Product description "R-Tronic" + "R-Con"
14
(Illustration 4)
Front view of wireless receiver "R-Con": (Illustration 3)
Cable with coaxial plug
for antenna connection
(radio communication with
"R-Tronic")
Plastic Cover
Wireless receiver
"R-Con"
Type plate
Fixing clips for
mounting rail
Rear view of wireless receiver "R-Con":

"R-Tronic" + "R-Con" Product description
15
(Illustration 5)
Summary "R-Con" 8 channel system with logic module:
(Illustration 6)
Power supply "R-Con"
(230 V / 50-60 Hz)
LN
Power supply
channels 1-4
L
Switching outputs
channels 1-4
Selector switch
Operation/Con guration
Selector switch
Controller settings
Selection channels 1-4 ("teach in")
Switch-on
delay pump
Connection
pump
Connection
burner
LED Switch-off
delay pump
Switch-off
delay burner
Logic module for
pump and burner
4 actuators can be connected to each channel
(Illustration 5)
Empty
casing,
e.g. for
handover
report
Control modules "R-Con T 2P"
(4 channels each)
"R-Con"
Wireless module &
12 V DC power pack
12 V 12 V 12 V
Power supply of the individual
models via12 V plug-in jumper
12 V
Bus terminal
"N module"

Product description "R-Tronic" + "R-Con"
16
3.2 Technical data
"R-Tronic RT B / RTF B / RTFC K"
Power supply: "RTFC K" with external power pack
(100-240 V / 50-60 Hz)
"RT B", "RTF B" battery operated
(AA 1.5 V, Mignon LR6), optional mains operation
Display: LC-Display
Radio frequency: 868.3MHz
Transmitting power max.: 10 mW
Radio range within building:
Depending on materials and interference sources
Transmission interval: 150 seconds
Operation mode: Type 1 (EN 60730-1)
Protection: IP20 (EN 60529)
Protective system: III - Protective low voltage
Ambient temperature: +5 °C up to +50 °C
Measuring range T (°C): +0 °C up to +50 °C
Accuracy at +25 °C: ± 1 K
Measuring range RH (%): 0 up to 100 % RH, only for "RTF B" and "RTFC K"
Accuracy at +25 °C
and 20-80% RH: ± 4,5% RH
Measuring range CO2
(PPM): 0 up to 2000 PPM, only for "RTFC K"
Accuracy at 25 °C
and 1013 mbar: < ± 50 PPM +2% of measured value
Temperature dependence: typ. 2 PPM CO2/°C (0…50 PPM)
Long-term stability: typ. 20 PPM/a
Casing: ABS (ASA), trafc white similar to RAL 9016
Casing dimensions: 85 x 85 x 35 mm (W x H x D)
Type plates
Subjecttotechnicalmodicationwithoutnotice!

"R-Tronic" + "R-Con" Product description
17
"R-Con" Bidirectional wireless module
Interfaces: RS 485 bus
Radio frequency: 868 MHz
Transmitting power max.: 10 mW
Radio range within building:
Depending on materials and interference sources
Power supply: 230V / 50-60Hz
Secondary supply: 12V DC-1A (RS 485 Bus)
Stand-by loss: 1 Watt
Ambient temperature: -20 °C up to +50 °C
Storage temperature: -25 °C up to +70 °C
Casing: Plastic, pure white RAL 9003, for installation on
mounting rail DIN EN 60715 TH35
Dimensions (H x W x D): 82 x 36 x 58 mm
"R-Con T 2P" Control module heating and cooling
Interfaces: RS485 bus
Supply voltage: 12V DC
Contact: 4 closing contacts (4A/250 V AC) isolated from
the supply voltage
Number of radio channels: 4
Connection of a maximum of 16 actuators
(4 actuators per channel)
Temperature control: Pulse-width modulation (PWM)
Two point control (2-PT)
Stand-by-loss: 0,1 Watt
Casing: Plastic, pure white RAL 9003, for installation on
mounting rail DIN EN 60715 TH35
Dimensions (H x W x D): 82 x 18 x 58 mm

Product description "R-Tronic" + "R-Con"
18
3.3 Note regarding declaration of conformity
The company Oventrop GmbH & Co. KG hereby declares that the climate
display device/control "R-Tronic" and the wireless receiver "R-Con" comply
with the basic requirements and other relevant provisions of the guidelines
2014/53/EU (RED).
The declaration of conformity can be obtained from the manufacturer.
3.4 General conditions of sales and delivery
Oventrops general conditions of sales and delivery valid at the time of supply
are applicable.
"R-Con Logic" Logic module
Interfaces: RS485 bus
Supply Voltage: 12V DC
Connections: Pump connection, burner connection
Switching voltage: max. 250 V / 0-60 Hz (per closing contact)
Switching current: 10A (per closing contact)
Contacts: 2 closing contacts volt free 10 A / 250 V AC
Stand-by-loss: 0,1 - 0,6 Watt
Casing: Plastic, pure white RAL 9003, for installation on
mounting rail DIN-EN 60715 TH35
Dimensions (H x W x D): 82 x 18 x 58 mm

"R-Tronic" + "R-Con" Installation & initial operation
19
4. Installation and initial operation
4.1 General installation advice
The climate display device/control "R-Tronic" should be installed at a location
where a good circulation of air is guaranteed. If possible, the "R-Tronic" should
be mounted onto an inner wall or a pillar at a height of 140 cm to 170 cm.
Please make sure that the wireless thermostat is not affected by other heat
sources (such as sunlight or heating devices next to it).
The wireless thermostat cannot only be mounted onto a wall, but can also be
placed on a table stand which is available as optional accessory for all models.
The table stand should be set up freestanding, for instance on tables, side-
boards or similar and should not be covered.
The communication between the "R-Tronic" and the receiver "R-Con" is ra-
dio-based. Please observe that the radio range can be impaired by spatial
factors such as room geometry, existing objects, materials and interference
sources and so-called "radio shadows", for in-stance behind metal objects,
may develop.
Reduction of radio range compared with an unobstructed visual contact:
Material Radio range reduction
Wood, gypsum, uncoated glass 0 - 10%
Brickwork, wooden or gypsum
walls or walls made of press boards 5 - 35%
Armoured concrete 10 - 90%
Metal up to 100%
Note regarding radio communication between
"R-Tronic" and wireless receiver "R-Con"
It might therefore become necessary to re-position the wireless thermos-
tat to guarantee an uninterrupted radio communication to the receiver
"R-Con". Alternatively, technical measures, such as the use of an antenna
extension at the wireless receiver or of a wireless repeater might become
necessary. For more detailed information see paragraph 4.6.

Installation & initial operation "R-Tronic" + "R-Con"
20
4.2 Wallattachmentofthexingplate
"R-Tronic RT B / RTF B" (battery operation)
For the models "R-Tronic RT B" and "R-Tronic RTF B", power is either sup-
plied by batteries, a ush-mounted power pack or a mains adaptor with table
stand (available as accessories). The "R-Tronic RTFC K" is always operated
with a ush-mounted power pack or a mains adaptor.
If the "R-Tronic" models "RT B" and "RTF B" shall be used for battery opera-
tion, i.e. for standard operation, please proceed as follows:
1. Insert two AA 1.5 Mignon batteries into the battery case. The position of
the batteries is specied by the markings +/-.
(Illustration 7)
2. Screw the supplied xing plate horizontally onto the wall.
3. Insert the wireless thermostat into the xing plate from the top.
XThe "R-Tronic" is now ready for the "teach in" process (see paragraph 4.6).
Fixing plate
"R-Tronic
RT B
RTF B"
(battery
operation)
(Illustration 8)
Other manuals for R-Tronic RT B
3
This manual suits for next models
2
Table of contents
Other oventrop Temperature Controllers manuals

oventrop
oventrop Regudis W-HTU Operating instructions

oventrop
oventrop Unibox TQ vario User manual

oventrop
oventrop Unibox TQ RTL vario User manual

oventrop
oventrop Unibox T vario User manual

oventrop
oventrop Unibox E BV vario User manual

oventrop
oventrop Unibox TQ RTL User manual

oventrop
oventrop PT1000 User manual

oventrop
oventrop Unibox TQ-RTL R-Tronic User manual

oventrop
oventrop PT1000 User manual

oventrop
oventrop Unibox T User manual