Paradox ACM12 User manual

ACM12
Installation Manual V4.5 and higher
Supports EVOHD / EVO192 V4.5 and higher
Description
Thank you for choosing the ACM12 for your access control. The ACM12 is designed to be used with the Paradox EVO system.
It allows you to manage access of one door, via card, pin or both, provide forced door and door left open detection, and arm / disarm
functions. The ACM12 supports full Off-Line functionality, which stores the entire database in memory when the panel connection is lost and
enables full synchronization upon restore. It supports one IN reader and one OUT reader if using 4-wire Paradox readers, or one IN reader
only if using the 7-wire 26-bit Wiegand reader. The ACM12 also supports a REX, a door contact that can be an alarm zone, and a door
locking device.
With accelerated response of up to 999 users, simple and minimal programing, as well as easy installation, the ACM12 is designed to
provide you with a reliable and professional access solution.
Compatibility
ACM12 V4.5 and higher is compatible only with panels EVOHD V4.5 and higher and EVO192 V4.5 and higher.
Upgrade Note
When upgrading to the latest version, it is advisable to upgrade the panel first, and then upgrade the ACM12 module.
Off-Line Feature
The ACM12 V4.5 fully supports Off-Line functionality. In the case of panel connection loss, the ACM12 will switch to Off-Line mode and
will fully function with user access level and schedules; arm / disarm user permissions will be overridden. While resuming
communications with the panel, all programming changes will be updated. In Off-Line mode, events are kept locally in the module and
can be uploaded manually for each ACM12 when communication is restored.
Installation (Figure 1)
Connect the ACM12 as per the drawing below. When powering up, all ACM12 modules will synchronize with the panel and upload all user
and schedule data. Typically, 100 users and 10 schedules will take about 50 seconds to upload. This will also take place upon resuming
connection with the panel. Synchronization is indicated by RX/TX LEDs flashing together at 4 Hz. If an ACM12 V4.5 detects a connection
to a different EVO panel, data will be erased and the new panel data will be synchronized.
POWER: The ACM12 should be powered with a 16 Vac 20Va. Battery should be connected.
Figure 1
AC
AUX BATT
AUX
STAT
RX
TX
BATT
RED BLK
AUX
AC
EVO
BUS
+RED
TRIG BLK GRN YEL
GRN YEL
READER
-PGM
N.O.N.C.COM TMP CT REX DO D1
~~
MANUAL
DOOR
TRIGER
16 VAC
12 VDC
600 mA
*
EOL
DOOR
CONTACT
REX
READER
IN
READER
OUT
*
EOL FOLLOWS
PANEL DEFINITION
AUX ON / OFF SWITCH
FUSE 5A / 28 VDC
EVO
1 2 3
4 5 6
7 8 9
X 0 
1 2 3
4 5 6
7 8 9
X 0 
R1 R2
+
-
BUS SUPPORTS
IN AND OUT READERS
DOOR LOCK
5A / 28 V
MAX
*
1N4007
DIODE
TAMPER
TO
AUX
+
BEEP RED GREEN
OPTIONAL 7-WIRE
26-BIT WIEGAND
CARD READERS
NOTE: IF CONNECTING
TWO READERS TO THE
SAME ACM12 MODULE
ENSURE READERS ARE
THE SAME VERSION
Unlock Device Diode: When connecting a locking device, it is recommended to connect diode 1N4007 as per Figure 1, to keep the relay
contacts reliability.
Firmware Upgrade: Should you need to upgrade the ACM12 firmware, connect the CV4USB A+ to Green and B- to Yellow, and power
Red and Black.
Turning Auxiliary Power ON / OFF (V4.52 and above)
Press and hold the AUX ON / OFF switch for 7 seconds. This toggles the auxiliary power ON or OFF.
IN / OUT Reader Assignment (V4.52 and above)
The reader that is detected first will be considered the IN reader, by default. The reader that is detected second will be considered the
OUT reader.
Changing the Default Reader Assignment (V4.52 and above)
1. Press and hold the AUX ON / OFF switch for 3 seconds. The ERROR, TX and RX LEDs flash for 2-3 seconds.
2. Press any key or present an access card to the reader you want to designate as the IN reader. Automatically, the other reader will be
designated as the OUT reader.
Programming via BabyWare or Keypad
Installer + Section [4003] + Serial Number of the ACM12.
* = Default
Connection Description Connection Description
TRIG Shorting to ground will activate the unlock relay. TMP
Tamper switch follow panel definition Section [3034]
ACM12 programming section [003] option1 to
enable.
COM/NC/NO Unlocking relay, max 5A / 28 VDC
AC - 16V 20 VAC EVO BUS Connect to EVO bus.
Additional Aux (-) CT
Zone for door contact. Can be system zone Section
[0400], EOL will follow panel global EOL panel
section 3033 bit 7.
AUX Use to power the Reader, REX, and other devices.
Max output 600mA, fuseless shutdown. REX Request for exit detector connection, it is connected
without EOL.
PGM 50mA output follow. Some predefined conditions,
see programming Section [011]. D0 Connect to Green wire of the Reader.
CT Door contact is used to monitor door condition and
to identify door left open and forced door status. D1 Connect to Yellow wire of Reader.
Section [001] General Options
Option OFF ON
[1] Tamper Input Disabled* Enabled
[2] Battery Charging Current 350mA* 850mA
[3] AC monitoring Disabled Enabled*
[4] & [5]
[4] [5]
Card only OFF* OFF*
Card or PIN ON OFF
Arm and Access: Card or PIN
Disarm: Card and PIN OFF ON
Card and PIN always ON ON
[6] Unlock door on Fire Alarm Disabled Enabled*
[7] Door forced open Alarm Disabled* Enabled
[8] Card activates door unlocked schedule
(V4.52 and above) Disabled Enabled*
* Follow Panel User Schedules.
LED Feedback
* RX / TX will flash together at a frequency of 4Hz when synchronization takes place.
Error Display
Section Data Description Default
[002] __/__/__ (Seconds) Door Unlocked Period 005
[003] __/__/__ (Seconds) Door Unlocked Period Extension (handicap use) 015
[004] __/__/__ (Seconds) Door Left Open warning delay 060
[005] __/__/__ (Seconds) Door Left Open Alarm delay from warning 060
[006] __/__/__ (Minutes) Safe Unlock delay 00
*[007] __/__/__ (01 - 32) 1st Unlock Door Schedule 00
*[008] __/__/__ (01 - 32) 2nd Unlock Door Schedule 00
*[009] __/__/__ (01 - 32) 3rd Unlock Door Schedule 00
*[010] __/__/__ (01 - 32) 4th Unlock Door Schedule 00
Section Data Description Default
[011] __/__ PGM Activation 00
00 : Arm
01 : Follow Door Unlock Schedule
02 : Follow Access Granted (will be activated for the unlock period)
03 : Follow Door Forced State
04 : Follow Door Left Open Warning / Alarm
05 : Follow access user #999
06 – 99 : Future Use
Section [012]
Option OFF ON
[1] Partition 1 Disabled Enabled*
[2] Partition 2 Disabled* Enabled
[3] Partition 3 Disabled* Enabled
[4] Partition 4 Disabled* Enabled
[5] Partition 5 Disabled* Enabled
[6] Partition 6 Disabled* Enabled
[7] Partition 7 Disabled* Enabled
[8] Partition 8 Disabled* Enabled
AC On (Green) when module has AC power.
BATT On (Green) when charging and during battery tests. Battery test every one minute.
AUX On (Yellow) when auxiliary output is active.
STAT On or flash (Red) when an error occurs. Refer to Error Display table below.
RX Flashes (Green) when receiving information from the panel.
TX Flashes (Green) when transmitting information to the panel.
STAT
(Red)
RX
(Green)
TX
(Green)
Condition
ON OFF OFF EVO bus is shorted / No clock / No data (offline)
ON OFF ON Wrong data / Invalid EVO address, too many modules or incompatible panel version
ON ON ON EVO bus YEL and GRN reversed
FLASH ---- ---- EVO bus voltage is low (less than 9V)
ACM12-EI04 05/2016
Technical Specifications
User Capacity 999
Door Unlock Schedules 4 (total of 8 periods)
User Schedules Capacity 32
User Security Levels 15
Power 16 Vac, 20 VA
Auxiliary Output 12 Vdc, 600 mA, 1A fuseless shutdown
Battery 12 Vdc, Gel Cell. Connection protected with 5A fuse
Door Unlock Form C relay rated at 5A / 28 Vdc
PGM Output 50 mA predefined definitions
Device Connections Two Paradox 4-wire readers or one 7-wire 26-bit Wiegand reader, door contact,
REX device, tamper
Manual Unlock Negative trigger input
Control Panel Compatibility EVOHD Control Panel V4.5 and above
EVO192 Control Panel V4.5 and above
Metal Box (optional) Minimum 20 x 25.5 x 7.6 cm
(8 x 10 x 3 in.) metal box
Dimensions 14 x 9.2 x 2.5 cm (5.5 x 3.6 x 1 in.)
Warranty
Please refer to the Limited Warranty Statement found on the website www.paradox.com or contact your local distributor.
© 2016 Paradox Security Systems (Bahamas) Ltd. All rights reserved. Specifications may change without prior notice.
Patents
One or more of the following US patents may apply: 7046142, 6215399, 6111256, 6104319, 5920259, 5886632, 5721542, 5287111, and
RE39406 and other pending patents may apply. Canadian and international patents may also apply.

Other Paradox Computer Hardware manuals

Paradox BUS2SER User manual

Paradox

Paradox BUS2SER User manual

Paradox ZX32D User manual

Paradox

Paradox ZX32D User manual

Paradox PRT3 User manual

Paradox

Paradox PRT3 User manual

Paradox PRT3 User manual

Paradox

Paradox PRT3 User manual

Paradox APR-PRT3 EVO192 User manual

Paradox

Paradox APR-PRT3 EVO192 User manual

Paradox RTX3 User manual

Paradox

Paradox RTX3 User manual

Popular Computer Hardware manuals by other brands

Arbor Technology EmETXe-i90M3 user manual

Arbor Technology

Arbor Technology EmETXe-i90M3 user manual

Teradici Teradici APEX 2800 Server Offload card by quick start guide

Teradici

Teradici Teradici APEX 2800 Server Offload card by quick start guide

Hama SATA PCI 2-Way Raid Controller Instruction guide

Hama

Hama SATA PCI 2-Way Raid Controller Instruction guide

One Stop Systems OSS-412-BP user manual

One Stop Systems

One Stop Systems OSS-412-BP user manual

IOtech DaqBoard/500 Hardware reference manual

IOtech

IOtech DaqBoard/500 Hardware reference manual

Sanus Foundations CAFP2 manual

Sanus Foundations

Sanus Foundations CAFP2 manual

Ross ULTRIX-FM-NS-2RU install guide

Ross

Ross ULTRIX-FM-NS-2RU install guide

Intel T8300 - Core 2 Duo 2.4GHz 800MHz 3MB Socket P Mobile... Documentation update

Intel

Intel T8300 - Core 2 Duo 2.4GHz 800MHz 3MB Socket P Mobile... Documentation update

Abocom LF560TX Specification sheet

Abocom

Abocom LF560TX Specification sheet

Siemens Nixdorf D842 Technical manual

Siemens Nixdorf

Siemens Nixdorf D842 Technical manual

Balluff BIS C-6002 manual

Balluff

Balluff BIS C-6002 manual

AMX AXU-MSP24 Schematic diagram

AMX

AMX AXU-MSP24 Schematic diagram

Keithley 7020-D instruction manual

Keithley

Keithley 7020-D instruction manual

Renesas RL78/G22 user manual

Renesas

Renesas RL78/G22 user manual

SeaLevel SeaLINK+485-DB9 user manual

SeaLevel

SeaLevel SeaLINK+485-DB9 user manual

miniDSP Home Theater Series user manual

miniDSP

miniDSP Home Theater Series user manual

Epson S5U1C63007P manual

Epson

Epson S5U1C63007P manual

Digi Digi JumpStart Kit quick start guide

Digi

Digi Digi JumpStart Kit quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.