Parker Hannifin Corporation
Pneumatic Division North America
Richland, Michigan
Pneumatic
5
Baud Rate Setting
This system incorporates an Auto-Baud detect feature,
eliminating the need to set switches.
PROFIBUS-DP
Bus-In Connector
Pin Function
1NC
2NC
3 A Line
4 B Line
5RTS
Bus-Out Connector
Pin Function
1 5V Pocket
2 0V Pocket
3 A Line
4 B Line
5RTS
PVLB10/ PVLC10 Serial Bus Modules V-382P
Technical Specifications
External Power Supply .................................20.4 to 30 VDC
Bus Current ............................................................... 200mA
Maximum Current Per Output ................................... 350mA
Total Output Current ....................................................... 1A
Number of Outputs .......................................................... 16
Baud Rates .................................... 9.6 Kbaud to 12 Mbaud
Degree of Protection ..................................................... IP65
Operating Temperature
60% Rating .......................... 0°C to 55°C (32°F to 130°F)
100% Rating ........................ 0°C to 40°C (32°F to 104°F)
Data I.D. Code .............................................................. 1000
Data Rates
Baud Rate Distance
9.6 Kbaud 9,600m (31,488ft)
19.2 Kbaud 9,600m (31,488ft)
93.75 Kbaud 9,600m (31,488ft)
187.5 Kbaud 8,000m (26,240ft)
500.0 Kbaud 4,000m (13,120ft)
1.5 Mbaud 500m (1,640ft)
12.0 Mbaud 500m (1,640ft)
Note: This device transmits 2 bytes and receives 2 bytes.
The EDS file can be downloaded from our website
http://www.parker.com/pneumatic. Click on Solenoid / Air
Operated Valves and then click on PVLB10 or PVLC10 Valves
and finally click on Service / Maintenance.
Power Connector
Pin Function Comment
1 0 VDC BUS POWER
2 24 VDC
3* Valve Power VALVE POWER
4* Valve Power
5 Ground
Recommended Bus and Power Connector (or equivalent):
Turck female Eurofast #B 8151-0
Turck male Eurofast #BS 8151-0
Module Status Lights (LED's)
Indicator Description
Power-BUS SteadyGreen Normal
OFF No Power Applied
Steady Green Normal
Power-Out OFF
No Power Applied to the Valves
BUS-BA Steady Green Normal
OFF Configuration Problem
BUS-ERR OFF Normal
Steady Red BUS Error
BUS-ON Steady Green Normal
OFF No Power Applied
Node Address Setting Through Rotary Switches
E STOP Feature*
Output power to the solenoids can be wired to allow the user
to turn the outputs off while allowing the communications to
remain on. This can be done by placing the user's
Emergency Stop Switch or other hard wired control contact
between Pin 3 and Pin 4. If this feature is not required, Pin 3
and Pin 4 should be wired together.
Pin 1
Pin 2
Pin 3
Pin 4
Pin 5
0 VDC
24 VDC
Gnd
User's Emergency Stop Switch or
other hard wired control contact.
Tie together if Emergency Stop
Switch is not required.
Power Connector
Last Module Termination
If the PVLB10 or PVLC10 manifold is the last device on the
network, a terminating resistor connector must be connected
on the Bus-OUT connector. If the network baud rate is
higher than 1.5 Mbaud, use a terminating resistor connector
with inductive filters.
21
34
5
21
34 5
21
34
5
Address x 10
Address x 1
M12
Micro BUS-IN Connector
(Male) Face View
M12
Micro POWER Connector
(Male) Face View
M12
Micro BUS-OUT Connector
(Female) Face View
Bus
Power
ERR
BA
ON
ERR
ON