Parker V200 User manual

Auto Purger Model V200
Product Bulletin 75-00 J
Contact Information:
Parker Hannin Corporation
Refrigerating Specialties Division
2445 South 25th. Avenue
Broadview, IL 60155-3891
phone (708) 681-6300
fax (708) 681-6306
www.parker.com
Pressure Rating: 21 bar (305 psig)
Purpose:
The Model V200 Auto Purger is
a unique energy-saving device
designed to efciently remove
foreign non-condensable gases from
ammonia refrigeration systems.
Product Features:
Smaller compact design with
•
equivalent capacity of our current
model
Light weight 29.5 kg (65 lbs)
•
Proprietary microprocessor control
•
for all sensing and control functions
Factory calibrated and wired
•
Auto or manual cycling capabilities
•
Up to 20 “Purge Points”
•
Automatically adjusts vent pressures
•
Energy saving sleep mode that
•
will activate with lack of non-
condensables
Electronic level, temperature, and
•
pressure monitoring for improved
performance
Records number of purger cycles
•
and times for each purge point
during a 7 day period
Purger is made of corrosion
•
resistant material

Page 2 / Bulletin 75-00 J
High
Pressure
Receiver
Evaporative
Condenser
Auto Purger
(Model V200)
Evaporator
Liquid Line
Liquid
Refrigerant
Line
Gas
Refrigerant
Line
Foul
Gas
Line
P
P
P
P
P
Purge Points (P)
V200 Auto Purger Multiple Purge Points
High
Pressure
Gas
Refrigerant
Foul
Gas
Liquid
Refrigerant
P
High Pressure Receiver
Purge Point
Liquid
Refrigerant
Foul
Gas
P
Introduction
Non-condensables like air, hydrogen,
nitrogen, and hydrocarbon gases
reduce the overall capacity of
the refrigeration system. Higher
pressures, which in turn causes
longer compressor runtime, longer
condenser fan runtime, higher
compressor discharge temperatures,
increase compressor power costs,
increase wear and tear on equipment,
increase leaks, reduce system
eciency, increase overall system
energy costs are all consequences of
non-condensables in the refrigeration
system.
In a refrigeration system non-
condensables can be introduced by:
• Inadequate system evacuation such
as servicing compressors, strainers,
valves, start-up, etc.
• Refrigerant additions
• Leaks from valve stem packings,
bonnet gasket, compressor shaft
seal, control transducers, etc.
• Separation of ammonia molecules
(hydrogen and nitrogen)
• Compressor oil breakdown
(hydrocarbon gases)
e base V200 Rapid Auto Purger
removes the non-condensable gases
from four purge points. With the
addition of up to two slave units, 36
purge points possible. is leads to
lower condensing pressure, runtime
of the compressors, and operating
costs.
Non-condensable indicators
are excessively high condensing
temperatures/pressures and
saturated temperature/pressure
deviations. One indicator is a higher
saturated condensing pressure/
temperature at the condenser for
the given outdoor air wet bulb
and heat rejection load. Another
indicator is the increasing dierence
between the observed condensing
pressure and the saturation
pressure corresponding to the liquid
refrigerant temperature exiting the
condenser.
Purge Points
e most common purge points
in a refrigeration system are at the
condenser drain, pilot receivers,
thermosyphon receivers, high
pressure receivers, liquid drain
header, equalizing lines, and low
velocity-high side areas.
Purge points should be located to
ensure no liquid refrigerant is drawn
by the purger. e Auto Purger V200
has a liquid drainer at the foul gas
inlet to prevent any liquid refrigerant
from entering the shell side of the
heat exchanger.
Auto Purging
e start of a purge cycle can
commence automatically, manually,
time based, central management,
and/or using the microprocessor. e
Auto Purger V200 can only purge one
point at any given time.
In automatic mode each purge point
is sampled for a minimum of ve
minutes. If the purge conditions are
not met within the sample time limit,
the Auto Purger continues to the next
purge point. When a purge point
meets the purge conditions within
the sample time limit the Auto Purger
starts the purge cycle. e purge
cycle shuts o when the non-purge
conditions are met.
Evaporative Condenser
Purge Point

Bulletin 75-00 J / Page 3
V200 Auto Purger Fill and Cool Down
Pressure Transducer
Suction
Line
Vent
Solenoid
Bubbler
Water Inlet
Water
Drain
line
Level
Sensor
Heat
Exchanger
Oil
Drain
Foul Gas line
Liquid
Drainer
Check Valve
w/ Orice
Liquid
Refrigerant
Line
Check
Valve w/
Orice
Liquid
Solenoid
w/ Check
Valve
& Orice
Vapor Vent
Flow
Controller
Check Valve
w/ Orice
Flow
Controller
Low Temp. Liquid
High Pressure Gas
Non-Condensable
Gases
Water
A built in feature of the Auto Purger
is sleep mode. Sleep mode allows the
system to bypass purge points after
two cycles of not meeting the purge
conditions within the minimum
sample time of ve minutes. After the
Auto Purger samples each purge point
twice without a vent occurring, the
system will shut o for two hours.
Purge Cycle
e purge cycle consist of three main
operations: ll & pre-cool, separating
non-condensable gases & refrigerant,
and the release of non-condensable
gases.
1. Fill & Pre-Cool
Foul gas enters the V200 Auto
purger at the foul gas line. e
liquid drainer separates the liquid
refrigerant from the foul gas.
Using the suction line; the liquid
refrigerant from the liquid drainer
is transported to the shell side of the
heat exchanger.
Liquid makeup to the heat
exchanger is controlled by the
level sensor. As liquid refrigerant
boils o in the heat exchanger the
level drops. When the refrigerant
reaches a critical level the sensor
energizes the liquid solenoid,
opening the check valve, and letting
liquid refrigerant through to ll up
the heat exchanger. e level sensor
is set on a timer to prevent from over
lling the heat exchanger.

Page 4 / Bulletin 75-00 J
V200 Auto Purger Separating Non-Condensables Gases
WARNING
Do not trap the foul line prior to
entering the purger foul gas line.
is will cause the foul gas to
condense.
!
Pressure Transducer
Suction
Line
Vent
Solenoid
Bubbler
Water Inlet
Water
Drain
line
Level
Sensor
Heat
Exchanger
Oil
Drain
Foul Gas line
Liquid
Drainer
Check Valve
w/ Orice
Liquid
Refrigerant
Line
Check
Valve w/
Orice
Liquid
Solenoid
w/ Check
Valve
& Orice
Vapor Vent
Flow
Controller
Check Valve
w/ Orice
Flow
Controller
Low Temp. Liquid
High Pressure Gas
Non-Condensable
Gases
Water
2. Separating Non-Condensable
Gases & Refrigerant
e foul gas enters the heat
exchanger through a check valve
with an orice and condenses
immediately. e non-condensable
gases remain in a gas state, because
the non-condensable gases require
lower temperatures to condense.
Condensed refrigerant and non-
condensable gases rise through the
heat exchanger and into the vapor
vent. As the liquid rises it lifts an
orice, ow controller, to the top of
the vapor vent allowing pressure to
build. Once the pressure exceeds
the high pressure check valve the
refrigerant then ows back into the
tube side of the heat exchanger.
e high pressure refrigerant
runs through the tubes of the heat
exchanger absorbing heat from the
high temperature foul gas of the
shell side of the heat exchanger. e
refrigerant begins to boil and vapor
refrigerant, free of non-condensable
gases, is returned to the plant by the
suction line.
Any oil that may collect in the V200
purger can be drained o from the
two oil drains. Before draining the
oil, shut-o the purger and close the
liquid and foul gas valves. Allow the
purger to pump out any remaining
refrigerant and close the suction
line valve. Use normal oil draining
precautions to prevent injury or
property damage.

Bulletin 75-00 J / Page 5
V200 Auto Purger Release of Non-Condensable Gases
Pressure Transducer
Suction
Line
Vent
Solenoid
Bubbler
Water Inlet
Water
Drain
line
Level
Sensor
Heat
Exchanger
Oil
Drain
Foul Gas line
Liquid
Drainer
Check Valve
w/ Orice
Liquid
Refrigerant
Line
Check
Valve w/
Orice
Liquid
Solenoid
w/ Check
Valve
& Orice
Vapor Vent
Flow
Controller
Check Valve
w/ Orice
Flow
Controller
Low Temp. Liquid
High Pressure Gas
Non-Condensable
Gases
Water
3. Release of Non-Condensable Gases
As the refrigerant level drops in
the vapor vent the oat will fall
allowing the non-condensable gases
to escape through the orice. Non-
condensable gases will continue to
accumulate, producing an elevated
pressure. Once the pressure of the
non-condensable gases exceed
the set point of the vent solenoid
and vent check valve with orice,
the gases are then released into
the bubbler. At the same time the
vent solenoid is activated the water
supply solenoid is also activated.
Non-condensable gases and
residual amounts of refrigerant
entering the bubbler are diluted
into the water. As the water in the
bubbler rises it will overow the
drain tube and exit the drain line.
Once the vent line pressure drops
below the pressure switch set point
the vent solenoid and water supply
solenoid close.

Page 6 / Bulletin 75-00 J
LIQUID SOL
VENT / WATER SOL
1. BEFORE SETTING PURGER CYCLE
CHECK THAT WATER MAKE-UP
TANK CONTAINS WATER.
PRESS INIT KEY TO FILL.
2.
DEFINE AND SET EACH POINT
REQUIRED IN SYSTEM.
3.
SETUP PURGE CYCLE TYPE
(AUTO, MANUAL, OR TIME)
MENU INIT
ENTER TERM
Controller Start-up Screen
LIQUID SOL
VENT / WATER SOL
MON 01-01-08 01:43PM PRE-COOL
PURE TEMPERATURE OVERLIMIT
ACTUAL TARGET
73°F 0.0 PSIG VENT
7.3 PSIG 0.0 PSIG RESET
CYCLE HISTORY
VENTS 0 TOTAL TIME 0:00:00
MODE : AUTO
Main Menu for the Controller
LIQUID SOL
VENT / WATER SOL
UNIT SETUP
SOFTWARE VERISON 1.0
BRUD: 19200
PARITY: EVEN
TEMPERATURE SCALE: FAHRENHEIT
SLAVE ID: 01
PRESS (MENU) TO CANCEL
Fahrenheit v/s Celsius Menu
WARNING
Because both the water and vent
solenoids are energized at the same
time, this procedure must be done
prior to opening the system to
refrigeration. Failure to do so will
result in a venting of ammonia.
!
Installation
All purgers are packed for a maximum protection. Un-1.
pack carefully. Check the carton to make sure all items
are unpacked. Save the enclosed instruction for the
installer and eventual user.
Do not remove the protective coverings until the purger
is ready to be installed.
Mount the Rapid Auto Purger to a wall or structure that
2.
can easily handle its weight and installation hardware.
Make sure to leave access for servicing the unit if re-
quired. Pipe the unit into the refrigeration system along
with an electrical supply, water, and a water drain as
needed.
Note: Wire only one purge point solenoid to each control-
ler contact relay (See electrical wiring diagram).
Contractors need to follow a WPS (Welding3.
Procedure Specication) for all welding. e
procedure must be qualied and welder doing
the weld qualied to perform that procedure.
For welding the stainless steel 304L body to
carbon steel pipe, E309L and ER309L-15,-16, or
-17 ller metal is a common choice. Contractors
can develop their own standards and have them
qualied based on the equipment they use and
the environment they may encounter.
Before opening the purger to the refrigeration
4.
system turn power on to the controller and open
the water supply ball valve.
is is done by pressing and holding the “Initiate”
5.
(INIT) button on the controller keypad when the
initial start-up screen is displayed. e water
solenoid will energize and water should be seen
lling the tank. e tank is full when water runs
over the overow tube. After the tank is full, release
the “Initiate” (INIT) button to stop the water ow.
Press and release the “Menu” key to bring up the
6.
main menu screen.
Fahrenheit v/s Celsius display readings are user
7.
selectable by following these simple keypad
entries. Press both the up and down arrow keys at
the same time and release.
Note: Timing is critical and may take several tries.
Press the “Enter” key and release several times until the
Temperature Scale reading is highlighted. Use the up/
down arrow keys to select between Fahrenheit and Cel-
sius. Press and Release the “Enter” key twice to save your
selection and return to the main screen.
Screen contrast is adjustable by pressing both the
8.
“Enter” and “Terminate” (TERM) keys at the same
time. As with step 5, timing is critical. Use the up/
down arrow keys to lighten or darken the display
to your liking. Press and release the “Enter” key to

Bulletin 75-00 J / Page 7
V
LIQUID SOL
VENT / WATER SOL
MAIN MENU
START UP
SETUP
HISTORY
OTHER SETTINGS
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
Main Menu Options
V
LIQUID SOL
VENT / WATER SOL
SETUP
SET TIME AND DATE
PURGE OPTIONS
CALIBRATE PRESURE INPUT
TRIM TEMPERATURE READING
CHANGE LIQUID FEED SETTINGS
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
Setup Menu
SET TIME/DAY
WHAT IS THE DAY? TUE
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
V
LIQUID SOL
VENT / WATER SOL
Time / Date Setup Screen
PURGE DURATION
01 05 MIN
02 05 MIN
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
V
LIQUID SOL
VENT / WATER SOL
Purge Point Duration Setup Screen
PURGE OPTION
AUTO
MANUAL
TIME BASED
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
V
LIQUID SOL
VENT / WATER SOL
Purge Option Menu
return to the main menu.
Control Features Setup
is includes date, time, purge type (automatic, manual,
etc.), and the number of purge points being sampled
1. Press and release the “Menu” button on the keypad. e
rapid purger setup main menu will appear.
Use the up/down arrow buttons to select the “Setup” op-
tion. Press and release the “Enter” key.
Press and release the “Enter” key a second time to enter
the current date. Use the up/down arrow keys to select
the correct month. Press and release the “Enter” button
to move to the next eld. Repeat these steps to enter the
day and year. When nished, press, and release the “En-
ter” key. Enter the current day of the week by again using
the Up/down arrow keys. Next, enter the current time
using the same set of key strokes. Don’t forget to select
between AM and PM in this screen. When you’re done,
press the “Enter” key to return to the main menu.
2. When in the main operating screen press and release the
“Menu” button. Use the up/down arrow buttons to select
the “Setup” option. Press and release the “Enter” button.
Use the up/down arrow keys to select the “Purge Op-
tions” eld. Press and release the “Enter” button, “Setup
Points” will be highlighted. Press and release the “Enter”
key on the keypad. Using the up/down arrow keys, select
how many purge points are being used. When done,
press and release the “Enter” key. Now we must enter the
time (in minutes) each purge point is sampled. is set-
ting is less important when the “Automatic” purge mode
is selected. In this mode, sample times will change up or
down based on vent cycle history. With the point and du-
ration highlighted (darkened bar across the eld), press
and release the “Enter” key. An arrow will appear to the
left of the time to be changed. Using the up/down arrow
keys, select a time from 5 – 20 minutes in 5 minute incre-
ments. Press and release the “Enter” key when done. Use
the up/down arrow key to select the next point and dura-
tion to be set. Follow the same procedure for each of the
purge points being used. When done, press and release
the “Menu” key to return to the purge options screen.
3. Use the up/down arrow keys to select the “Purge Type”
option and press and release the “Enter” key. 3 Purge Op-
tions are available to you in this screen.
To select “Auto”, press and release the “Enter” key. is
is all that is required to operate in the “Auto” mode (as
dened in this manual). Press and release the “Menu”
key to return to the main screen. If you need to terminate
the active point being sampled and move to the next,
press and release the “Terminate” (TERM) key. Termi-
nate Active Point (1-20) should be highlighted. Press and
release the “Enter” key to move to the next purge point.

Page 8 / Bulletin 75-00 J
TERMINATE PURGE
TERMINATE ACTIVE POINT 1
TERMINATE PURGE CYCLE
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
V
LIQUID SOL
VENT / WATER SOL
Terminate Purge Menu
POINT DAY VENTS TIME
SUN 00 00:00
MON 00 00:00
TUE 00 00:00
01 WED 00 00:00
02 THR 00 00:00
FRI 00 00:00
SAT 00 00:00
SELECT WITH V PRESS (ENTER)
PRESS (MENU) TO CANCEL
V
LIQUID SOL
VENT / WATER SOL
Time Based Type Setup Menu
Purger Safety Features
e temperature controller and sensor are wired in series
with the pressure switch. is prevents venting of non-
condensed refrigerant to the water bubbler before the heat
exchanger reaches temperature.
If you need to stop all Purging in the “Auto” mode, select
the Terminate Purge Cycle by using the up/down arrow
keys. Press “Enter” and release to make your selection. In
order to release the system from Purge Hold, re-select the
“Auto” purge option again as explained at the beginning
of this step.
“Manual” To select the “Manual” mode, use the uup/
down arrow key to highlight the manual option. Press
and release the “Enter” key to save your selection. To ini-
tiate a purge cycle in the Manual mode, press and release
the “Initiate” (INIT) key. Using the Up/down arrow keys,
select the point that you wish to purge. Press the “Enter”
key. e point selected along with the duration of time
this point will be sampled is shown toward the top of
the display. To terminate a purge in the manual mode,
press and release the “Terminate” (TERM) key. Using
the up/down arrow key, select either of the two options
displayed. Press and release the “Enter” key to terminate
the purge.
“Time Based” To select the “Time Based” mode, use the
up/down arrow key to highlight the Time Based option.
Press and release the “Enter” key to save your selection.
e next step is to enter the time the purge cycle will
start. Use the up/ Down arrow keys to select the hour.
Press and release the “Enter” button to move to the next
eld. Repeat these steps to enter minutes and AM v/s PM.
When nished, press and release the “Enter” key. Using
the same steps, enter the time of day the purge cycle will
stop. Don’t forget to select between AM and PM.
When nished, press and release the “Enter” key. If you
have already set the number of purge points needed,
press and release the “Enter” key again to bring you back
to the main menu. If you haven’t yet selected how many
purge points are needed, refer back to step 2 for instruc-
tion.
To initiate a purge cycle in the Time Based mode, press
and release the “Initiate” (INIT) key. Using the up/down
arrow keys, select the point that you wish to purge. Press
the “Enter” key. e point selected along with the dura-
tion of time this point will be sampled is shown toward
the top of the display. To terminate a purge in the Time
Based mode, press and release the “Terminate” (TERM)
key. Using the up/down arrow key, select the Terminate
Active Point (#) and press and release the “Enter” Key.
e selected point will terminate and the next pro-
grammed purge point will become active and move to
the next active purge point.
To stop all purging while in the “Time Based” mode,
select Terminate Purge Cycle. Using the up/down arrow
key, select Terminate Purge Cycle and press and release
the “Enter” key. is will put the controller in a Purge
Hold mode that is displayed in the upper right corner
of the display. In order to release the system from Purge
Hold, you will have to re-select the “Time Based” purge
option again as explained at the beginning of this step.

Bulletin 75-00 J / Page 9
V200 Auto Purger Electrical Wiring Diagram for a 4 Point Purger
V200 Auto Purger Compact Design Dimensions
1
2
3
16
4
9
7
8
6
11
10
5
12
13
14
15
17
18
19
20
21
12
10
3
10

Bulletin 75-00 J / Page 11
Item Kit Description Kit Number
1 Purger Controller (4 points) 208783
2 Slave Controller Unit (16 points) 208784
--- Relays - Qty 4 208785
3 Unibody, 1/4” Globe 106621
4 Unibody, 1/4” Angle 106620
6 Vent Solenoid 208786
5Water Solenoid Valve - Brass 120 volt (1/4” Threaded Connection) 208787
Water Solenoid Valve - Brass 240 volt (1/4” Threaded Connection) 208788
7 Differential Check Valve (50 psid) 206536
8 1/2” SV2, Liquid Ammonina Solenoid Valve (1/2” Threaded Connection) 501941
9 Plug Pkg, Pipe 1/8” Purger Orice 0.032 208666
10 Strainer, Disc 200912
11 Plug Pkg, Pipe 1/8” Purger Orice 0.040 208667
12 1/2” CK-4A-2, Check Valve 101047
13 Plug Pkg, Pipe 1/8” Purger Orice 0.026 208665
14
Water Bubbler, Clear PVC V200 Top Inlet 208789
Conversion Kit, Steel Tube to Nylon 208669
Conversion Kit, Steel Tube Cabinet Style to Nylon 208670
15 Liquid Drainer (1/2” Threaded Connection) 309625
16 Gage, 30” - 150 psig (R717) 309401
Gage, 760mm - 10.5 bar (R717) 309403
17 Optical Level Sensor 208790
18 Pressure Transducer 206826
19 Temperature Probe, E4 Temp Controller 208022
20 Tubing, Bubbler Nylon 208668
21 Pressure Regulator (1/2” Threaded Connection) 506206
22 Pin Connector, Slave Unit (4 Point Kit) 208694
23 Gasket Package, Flange 13mm (1/2”) - Qty 12 202078
V200 Auto Purger Parts Kit
Item Kit Description Kit Number
5Coil, 120V / 60Hz or 110V /50Hz 8W 208791
Coil, 240V / 60Hz or 220V /50Hz 8W 208792
6Coil, 120V / 60Hz or 110V /50Hz 10W 208793
Coil, 240V / 60Hz or 220V /50Hz 10W 208794
8Coil, 120V / 60Hz or 110V /50Hz 10.5W COMM 202940
Coil, 240V / 60Hz or 220V /50Hz 10.5W COMM 202941
V200 Auto Purger Coil Parts Kit
Purge Points 120 V Purger 240 V Purger
4 109221 109223
8 109269 109270
12 109271 109272
16 109273 109274
20 109222 109224
V200 Auto Purger Assemblies

Page 12 / Bulletin 75-00 J
V200 Auto Purger Electrical Wiring Diagram for the Slave Unit (16 Additional Purge Points)
Note:
Common shown on the purge point solenoids connections are common to the relay. Incoming line power (120/240
volts) should be supplied to these terminals. An incoming natural should be supplied to one of each of the coil
leads. e other coil lead should be attached to the N.O. terminal for each independent purge point solenoid (S6N,
S8F).

Bulletin 75-00 J / Page 13
Symptom Possible Cause Solution
Water bubbler
cloudy.
Water supply turned off.
Hard water.
Venting ammonia.
Open water supply ball valve supplied with purger.
Check water solenoid coil for proper operation (Loose wire,
burned out). Replace if necessary.
Used treated water (softened). Clean bubbler on regular bases to
prevent severe clouding.
Check vent solenoid for proper operation. If bubbles are seen in
the water bubbler when idol, vent solenoid is leaking. Clean or
replace solenoid if needed.
Purger stays in
“Pre-Cool” mode,
will not purge.
Suction too high.
Liquid NH3supply off or obstructed.
RTD (#19) not reading accurately or no
display.
Verify Suction is below 4.4oC (40oF) - 4.0 bar (58.4 psig) for
R-717.
Adjust the A2 (#21) suction regulator to maintain 3 psig (If in or
near a vacuum). If suction is above 3 psig, remove setting from
A2 regulator by turning stem counter clock wise until it stops.
Check liquid ammonia solenoid, SV2 (#8), for proper operation
(Loose wire, burned out). Replace if necessary.
Check controller display for “Liquid Solenoid” pilot light.
Segment should be darkened if liquid is required. This is located
on the upper left side of the front panel (#1).
Check optical level sensor (#17) for proper operation (Loose wire,
defective sensor). Replace if necessary.
Check liquid supply orice (#11) for obstructions. Clean or
replace if necessary.
Note: RTD is factory calibrated and no eld adjustment is
required.
If the main controller displays “_ _ _” rather than an actual
temperature reading, check for loose wires. Check wire
loom from main board to cover for loose or damaged wires/
connections.
Replace RTD if necessary.
No temperature
reading on
controller display.
Loose RTD (#19) wire on main terminal
block.
Loose or damaged wire loom
connecting front panel to main board.
Faulty RTD.
Check for loose wires connecting the RTD to the main controller
board.
Check wire loom from main board to cover for loose or damaged
wires/ connections.
Check resistance range of the RTD (100 ohm +/- 0.1%) Replace
RTD if necessary.
No pressure
reading on
controller display.
Loose wire on main terminal block.
Faulty pressure transducer.
Note: pressure transducer (#18) is factory calibrated and no eld
adjustment is required.
Check for loose wires connecting the pressure transducer to the
main controller board.
Replace pressure transducer if necessary.
Note: all items with a (#) can be located in the V200 auto purger parts diagram.
V200 Service Pointers

Page 14 / Bulletin 75-00 J
Symptom Possible Cause Solution
Strong Ammonia
smell coming
from bubbler
(#14).
Water make up closed or restricted.
Leaking vent solenoid (#6).
Make sure the fresh water supply to the bubbler is not turned
off or being restricted. The purger is supplied with a shutoff ball
valve that should be in the full open position to start, and then
throttled back to control the ow rate into the bubbler.
Check the operation of the water makeup solenoid (#5). Verify
that the coil is energized when the vent cycle is active. The
magnetic eld can be veried with a small screwdriver touching
the top of the solenoid tube. It should be drawn to the tube if the
coil is powered and functioning properly. If the coil functions and
water still does not ow to the bubbler, check the supply lines for
obstructions.
Replace the water solenoid (#5) if necessary.
If bubbles are seen in the bubbler well after a vent has occurred,
the vent solenoid may be leaking.
Replace the solenoid if necessary.
Slave unit (#2)
not functioning (5
purge points and
up).
Master, slave communication cable
missing or damaged.
No power supplied to slave board.
Verify that the communications cable connecting the main purger
controller to the slave board is present, attached to the proper
terminals and is not damaged.
Check to make sure the green LED at the top of the slave unit
(#2) circuit board is ashing.
Verify the proper communication setting. This is done by pressing
the up & down arrow keys on the main controller (#1) at the same
time. Several attempts may be required as timing is critical. After
successfully completing this step, you should see a menu screen
that displays; Baud Rate, Parity, Temperature Scale and Slave ID.
(See step #7 under installation instructions)
Make sure the “baud” rate is set for 19200, “parity” even and
“slave ID” 01. Use the same keypad strokes to move and enter
settings as described in the bulletin under “Setup Instructions”.
Press the menu key to get back to the main screen. Check the
operation of the slave unit.
Make sure the power cable from the main purger controller to the
slave board is present, not damaged and properly connected.
Replace slave unit if necessary. (See both 4 point purger and
slave unit wiring diagram for proper wiring terminals)
Controller in
“sleep mode”, will
not purger
No foul gas present in system.
Damaged main controller board.
The purger controller will automatically go into “Sleep Mode” if
it has sampled every programmed purge point twice without a
vent occurring. It will stay in sleep mode for 2 hours then resume
its programmed cycle. You can override the sleep mode cycle
by simply pressing the “Enter” key on the controller. The sleep
mode feature will not be disabled and will repeat again if no vent
occurs.
Replace controller if necessary.
Note: all items with a (#) can be located in the V200 auto purger parts diagram.
V200 Service Pointers Continued

Bulletin 75-00 J / Page 15
1. Remove check valve assembly.
Remove lower tting and
replace with NPT reducer
supplied in kit. Install 90
degree plastic tting from kit as
shown in cutaway view.
2. Remove and discard short tube.
Turn vent tting 90 degrees to
rack. Install tube/ferrules and
tube clamp from kit, along with
check valve assembly as shown
in the cutaway view. (Tubing
ends may need to be trimmed
back for proper t)
3. Remove and discard steel lines,
ttings, and bubbler.
4. Reinstall new bubbler with
plastic lines and ttings
provided in kit - one line form
the bubbler cap goes to the
tting / orice assembly and
the other goes to the water
valve Use a standard steel
tubing cutter to cut plastic line.
1.
2.
V200 Auto Purger - Bubbler Replacement Instructions

© 2008 Parker Hannin Corporation
ISO 9001 CERTIFIED
309643 ECN: 8999 03/17/2009
Replaces Prior Versions:
75-00 A
75-00 B
75-00 C
75-00 D
75-00 E
75-00 F
75-00 G
75-00 H
Safe Operation (See Bulletin RSBCV)
People doing any work on a refrigeration system must be
qualied and completely familiar with the system and the
Refrigerating Specialties Division valves involved, or all other
precautions will be meaningless. is includes reading and
understanding pertinent Refrigerating Specialties Division
Product Bulletins and Safety Bulletin RSB prior to installation
or servicing work.
Where cold refrigerant liquid lines are used, it is necessary
that certain precautions be taken to avoid damage which
could result from liquid expansion. Temperature increase in a
piping section full of solid liquid will cause high pressure due
to the expanding liquid which can possibly rupture a gasket,
pipe or valve. All hand valves isolating such sections should
be marked, warning against accidental closing, and must
not be closed until the liquid is removed. Check valves must
never be installed upstream of solenoid valves, or regulators
with electric shut-o, nor should hand valves upstream of
solenoid valves or downstream of check valves be closed until
the liquid has been removed.
It is advisable to properly install relief devices in any section
where liquid expansion could take place. Avoid all piping
or control arrangements which might produce thermal or
pressure shock.
For the protection of people and products, all refrigerant
must be removed from the section to be worked on before a
valve, strainer, or other device is opened or removed. Flanges
with ODS connections are not suitable for ammonia service.
Warranty
All Refrigerating Specialties products are under
warranty against defects in workmanship and materials
for a period of one year from date of shipment from
factory. is warranty is in force only when products
are properly installed, eld assembled, maintained,
and operated in use and service as specically stated
in Refrigerating Specialties Catalogs or Bulletins for
normal refrigeration applications, unless otherwise
approved in writing by the Refrigerating Specialties
Division. Defective products, or parts thereof returned to the
factory with transportation charges prepaid and found to be
defective by factory inspection, will be replaced or repaired at
Refrigerating Specialties option, free of charge, F.O.B. factory.
Warranty does not cover products which have been altered,
or repaired in the eld, damaged in transit, or have suered
accidents, misuse, or abuse. Products disabled by dirt or
other foreign substances will not be considered defective.
e express warranty set forth above constitutes the only
warranty applicable to Refrigerating Specialties products, and
is in lieu of all other warranties, expressed or implied, written
including any warranty of merchantability, or tness for a
particular purpose. In no event is Refrigerating Specialties
responsible for any consequential damages of any nature
whatsoever. No employee, agent, dealer or other person is
authorized to give any warranties on behalf of Refrigerating
Specialties, nor to assume, for Refrigerating Specialties, any
other liability in connection with any of its products.
1. Remove tting / orice form
ange and replace with reducer
and 0.026 orice in kit (DO
NOT reuse old orice - new
bubbler requires smaller orice
form kit).
2. Remove and discard steel line,
ttings. and bubbler.
3. Replace bubbler clamps with
those provided in kit
4. Reinstall new bubbler with
plastic lines and ttings
provided in kit - one line form
the bubbler cap goes to the
tting / orice assembly and
the other goes to the water
valve Use a standard steel
tubing cutter to cut plastic line.
Cabinet Mounted Auto Purger - Bubbler Replacement Instructions
Step Kit Description Kit Number
3 - 4 Conversion Kit, Bubbler SS Tube to Nylon CS 208670
Cabinet Mounted Auto Purger Parts Kit
Other manuals for V200
1
Other Parker Auto-purger manuals