Patterson ABB ACS355 THREE-PHASE VFD User manual

1) Status LED:
a. Green – Normal Operation
b. Blinking Green – Fan drive is in alarm.
Consult the drive’s User Manual for alarm
conditions.
c. Red – Fan drive has faulted. Consult
the drive’s User Manual for fault conditions.
2) LOC/REM Indicator: Indicates whether the
drive in local or remote control. See
LOC/REM button entry below for more detail.
3) Rotation Indicator: Indicates rotation of the
fan motor shaft (and fan blades). See item #2
in the section entitled Additional Information.
4) Fan Speed Set Point: Indicates fan speed
as a percent of maximum (%). This
percentage corresponds to a read-only RPM
reading (see #5 below). Can be adjusted
using the up and down arrows (see #7 below).
5) Read-Only Parameters: Give real-time
readouts of the following conditions:
a. Fan speed – Expressed in RPM (see
#4 above)
b. Fan motor amperage – Indicates the
current being drawn by the fan motor,
expressed in Amperes (A)
c. Fan motor torque – Indicates fan motor output torque, expressed in percentage (%)
6) Soft Keys: Located directly below functions displayed in the lower corners of the keypad screen.
Right Soft Key is generally not used during basic fan operation. Left Soft Key controls fan direction.
See section entitled Additional Information.
7) Up/Down Arrows: Allow for adjustment of the Fan Speed Set Point (either while the fan is stopped
or in motion). See section entitled Fan Operation.
8) LOC/REM Button: Toggles between local and remote control of the fan drive. If LOC is displayed
in the upper left corner of the keypad screen, control of the drive is initiated locally (i.e. from the
keypad). If REM is displayed, control is initiated from an external source (i.e. another drive or
fieldbus).
9) Help Button: Provides more information during drive programming. Not used for fan operation.
10) Start/Stop Buttons: Used to start and stop the fan. See section entitled Fan Operation.
1
2 3
5a
5b
5c
4
7
9
6
8
10
THE AUTHORITY IN
AIR MOVEMENT
pattersonfan.com
800.768.3985
HIGH-5 CONTROL KEYPAD
ABB ACS355 THREE-PHASE VFD
IMAGE 1

FAN ROTATION: Proper rotation is achieved when the directional
indicator (#3 in Image 1) is clockwise and the blade flaps are
trailing. If rotation is not correct, swap two of the wires on the
output (motor) side of the VFD (U2, V2, or W2).
FAN OPERATION
STARTING THE FAN:
1) Make sure the LOC/REM Indicator shows the fan drive is in local (LOC) mode. The fan will not
respond to inputs from the keypad if the drive is in remote (REM) mode. Use the LOC/REM Button
as needed to ensure local control.
2) Using the Up/Down Arrow keys, adjust the Fan Speed Set Point. Remember, the Fan Speed Set
Point is based on percentage of maximum speed. This percentage corresponds to the
read-only RPM indicator.
3) Press the START button, and allow the fan to ramp up to speed. This may take a few seconds. To
prevent damage to the gearbox, it is recommended that the fan reach its Set Point speed before
making any further adjustments.
4) If the initial Set Point adjustment is unsatisfactory, refer to the section below entitled “Adjusting Fan
Speed While in Motion” to achieve the desired fan RPM.
ADJUSTING FAN SPEED WHILE IN MOTION:
1) Ensure local (LOC) control of the drive (see above).
2) Use the Up/Down Arrow keys to adjust the Fan Speed Set Point as desired. For best results, use
the Read-Only Fan Speed indicator (in RPMs) as a gauge for your desired setting. The fan will then
ramp up or down in response to the changing input.
Caution: DO NOT adjust the Fan Speed up and down repeatedly in large increments. Allow
the fan to reach the new speed before making any further adjustments.
STOPPING THE FAN:
1) Ensure local (LOC) control of the drive (see above).
2) Press the STOP button. The fan will then ramp down to a complete stop. This may take a few
seconds. Allow the fan to stop COMPLETELY before restarting.
HIGH-5 CONTROL KEYPAD
ABB ACS355 THREE-PHASE VFD
THE AUTHORITY IN
AIR MOVEMENT
pattersonfan.com
800.768.3985

ADDITIONAL INFORMATION
1) Fan drives are programmed prior to shipment. In order to ensure continuity, drive parameters are
locked by means of a three-digit passcode. Should troubleshooting of the drive become necessary,
contact Patterson at (800) 768-3985. A passcode can then be given to unlock the drive’s
parameters. It is highly recommended that the parameters be relocked (using the same passcode)
prior to putting the fan back in service.
2) Patterson’s High-5 fans are designed to maximize air movement while spinning in the FORWARD
direction. However, they can be run in REVERSE. Follow these steps:
a. If the fan is stopped, press the left Soft Key with the letters “DIR” above it. When the fan is
started, it will run in the reverse direction.
b. If the fan is running, press the STOP button, and allow the fan to come to a complete stop.
Then press the left Soft Key with the letters “DIR” above it. When the fan is started, it will run
in the reverse direction.
3) Please be aware that each fan is programmed to have a minimum fan speed, set at some level
above 0%. This is to protect the fan motor. The minimum speed will vary depending on the size of
the fan.
THE AUTHORITY IN
AIR MOVEMENT
pattersonfan.com
800.768.3985
HIGH-5 CONTROL KEYPAD
ABB ACS355 THREE-PHASE VFD
ABB ACS355
THREE-PHASE VFD
Table of contents
Popular Keypad manuals by other brands

SunVote
SunVote M52Plus-2.4G user manual

FEKER
FEKER JJK-21 user manual

ADEMCO
ADEMCO Galaxy Keyprox Installation and programming instructions

SECOLink
SECOLink KM20B Short programming manual - basic information

CDVI
CDVI Digicode PROFIL100EC instruction manual

CDVI
CDVI PROMI E Wiring Diagram and Instruction Manual