7
b). Measurements at 2000MΩ/1000V
Some specifications require testing at 1000V. This voltage must also be selected
where the supply voltage of the installation is between 500V and 1000V. First, set
the range switch to 1000V and then proceed as indicated in a above for 500V
testing. The above note also applies to testing at 1000V. In addition the following
applies.
Note: Make sure that the circuit under does not include components Which will be
damaged by the 1000V applied. Many normal components of an installation are
likely to be damaged if tested at 1000V. Examples are power factor correction
capacitors, low voltage mineral insulated cables, electronic light dimmers,
electronic ballasts and starters for fluorescent lamps etc…
c). Lock power on Feature
For hands free operation a lock power on feature is incorporated on the press to
test button. Set LOCK button to lock test voltage, Pressing it again will tester off.
6. LOW RESISTANCE (CONTINUITY) MEASUREMENTS
a). Set the range switch to 200Ω·))) Position
b). Connect the red test lead to the V Ωterminal and black to the COM terminal.
c). Connect the tips of the test leads to both ends of the circuit under test. read
resistance in Ωon the LCD.
d). When the impedance on circuit is below approximately 40Ω. It will indicate by a
continuous beeper.
7. AC/DC VOLTAGE MEASUREMENTS
a). Set the range switch to ACV or DCV position
b). Connect red test lead to “V Ω” terminal and black test lead to terminal “COM”.
c). Connect test prods of test leads IN PARALLEL to the circuit being measured.
d). Read the voltage value on LCD.
8. POWER TOOLS AND AMALL APPLIANCES
This test would also apply to other similar equipment that has a line cord. For double
insulated power tools, the megohmmeter lead shown connected to the housing would
be connected to some metal part lf the tool(e..g chuck,blade).
Note:The switch of the device must be in the “ON”position and the main power should
be disconnected.
MOTORS
AC-Disconnect the motor from the line by disconnecting the wires at the motor
terminals or by opening the main switch. If the main switch is used and the motor
also has a starter then the starter must be held, by some means, in the “ON” position.
In the latter case, the measured resistance will include the resistance of the motor,
wire and all other components between the motor and the main switch. If a weakness
is in dicated, the motor and other components should be checked individually. If the
motor is disconnected at the motor terminals, connect one megohmmeter lead to the
grounded motor housing and the other lead to One of the motor leads. DC-Disconnect