DESCRIPTION
The RTD7AL temperature sensor is a three-wire platinum RTD
(resistance temperature detector) typically used with monitoring
and control systems when accurate temperature control is
required. The sensor is explosion proof and approved for Division
1 and 2 hazardous locations. The RTD7AL can be used with a wide
variety of Raychem monitoring and control systems.
These installation instructions detail the installation of the
RTD7AL in conjunction with existing Raychem component kits.
TOOLS REQUIRED
• 3.5mmflat-bladescrewdriver
ADDITIONAL MATERIALS REQUIRED
• Pipestrap
• Conduitwith16–22AWGshieldedinstrumentcableorequivalent
armored cable
APPROVALS
TheRTD7ALisCSACertifiedforuseinNorthAmerica by the
manufacturer for use in Division 1 and Division 2 hazardous loca-
tions as follows:
KIT CONTENTS
Qty Description
1 RTDTemperatureSensor
SPECIFICATIONS
Sensorhousing Zinc-plated cast-iron body with aluminum
cap;NEMA4,7
Sensorsheath 316stainlesssteel
Range –100to900°F(–73to482°C)max
Accuracy ±1°F(0.5°C)at32°F(0°C)
Resistance 100ohmsat0°Cα=0.00385ohms/ohm/°C
Connection 3/4in.NPTconduithub
Class I, Division 1, Groups C, D
Class II, Division 1, Groups E, F, G
Class I, Division 2, Groups A, B, C, D
Class II, Division 2, Groups E, F, G
This component is an electrical device. It must be installed
correctly to ensure proper operation and to prevent shock or
fire. Read these important warnings and carefully follow all the
installation instructions. Component approvals and performance
are based on the use of specified parts only. Do not use substitute
parts or vinyl electrical tape to make connections.
4.25 in.
(108 mm)
3/4 in NPT
conduit
opening
3 in. (76 mm)
2 in. (51 mm)