2
Thank you for purchasing your
Hydromatic®pump. To help
ensure years of trouble-free
op er a tion, please read the
fol low ing manual carefully.
Before Operation:
Read the following in struc tions
care ful ly. Reasonable care and
safe meth ods should be practiced.
Check local codes and
requirements before installation.
Attention:
This manual contains important
information for the safe use of
this product. Read this manual
completely before using this
product and refer to it often for
con tin ued safe product use.
DO NOT THROW AWAY OR
OSE THIS MAN U A . Keep it
in a safe place so that you may
refer to it often.
Unpa king Pump:
Remove pump from carton. When
un pack ing unit, check for
con cealed damage. Claims for
damage must be made at the
receiving end through the delivery
carrier. Dam age cannot be
processed from the factory.
WARNING: Before handling
these pumps and ontrols,
always dis onne t the power
first. Do not smoke or use
sparkable ele tri al devi es or
flames in a septi (gaseous) or
possible septi sump.
Pumps Not Operating or
in Storage:
Pumps with carbon ceramic seals
must have impellers manually
rotated (6 rev o lu tions) after
setting non-op er a tion al for 3
months or longer and prior to
electrical start-up.
Pump:
The S3S/SB3S submersible pumps
are sup plied for 1 and 3 phase and
for 200, 230, 460 or 575 volts.
Pump is sup plied with 15 feet of
power cord. ong er ca ble lengths
can be furnished but must be
specified at time of order. Power
ca ble is 4 wire with the green wire
for ground. Be sure green wire is
connected to a ground lug in the
control panel and the control
panel must be connected to a
ground rod or ground wire from
supply service.
NOTE: All single phase pumps
require properly sized start
apa itor, start relay and run
apa itor in the panel.
Sump Level Control:
Sump level is controlled by
Hydromatic 3900 mercury switch
level controls. The 3900 level
controls is a metal case
mercury switch sealed in a solid
polyurethane float. The float is
held in position by a weight
at tached to the power cord above
the float. The cord supports the
float and is adjusted for height
from the sur face.
Typical duplex systems use three
floats: the lowest float turns the
pumps off, the next higher float
starts the lead pump, and the next
higher float (override) starts the
lag pump. The pumps alternate
on successive cycles.
General
Informat on
Two pumps operate together only
if sump level rises to the third or
over ride float. The override float
also brings on the sec ond pump in
case of failure of the first pump.
Extra floats with ap pro pri ate
con trols can be sup plied for alarm
functions. Triplex sys tems use
four floats. The fourth highest
float brings on the second lag
pump. Three pumps operate
together only if sump level rises to
the fourth float (sec ond override).
This float also brings on the third
pump in case of fail ure of either or
both of the first two pumps.
Alarm Controls:
The alarm float is usually set
above the override level so the
alarm will sig nal only if the
override level is ex ceed ed.
How ev er, some engineers pre fer
to have the alarm float set be low
the override lev el as it is pos si ble
for one pump to fail and the other
pump to operate on the over ride
level with the sump level never
reach ing the alarm level. This is
par tic u lar ly true in cases of low
inflow capacity.
Ele tri al Control Panel:
It is recommended that the
Hydromatic con trol panel be
used with all pumps as proper
start com po nents and pump
protection are fur nished.
NOTE: All single phase pumps
require properly sized start
apa itor, start relay, and run
apa itor in the ontrol panel.
IMPORTANT: If Hydromati
ontrol panel is not used and
the motor fails be ause of
im prop er omponents, the
motor guar an tee is void.