manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pepperl+Fuchs
  6. •
  7. Industrial Monitor
  8. •
  9. Pepperl+Fuchs RM-320P User manual

Pepperl+Fuchs RM-320P User manual

This manual suits for next models

2

Other Pepperl+Fuchs Industrial Monitor manuals

Pepperl+Fuchs VisuNet GMP RM/PC 200 series User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet GMP RM/PC 200 series User manual

Pepperl+Fuchs VisuNet EX2 GMPRM/PC 3700 Series User manual

Pepperl+Fuchs

Pepperl+Fuchs VisuNet EX2 GMPRM/PC 3700 Series User manual

Pepperl+Fuchs DA5-IU-C User manual

Pepperl+Fuchs

Pepperl+Fuchs DA5-IU-C User manual

Popular Industrial Monitor manuals by other brands

Regin E3-DSP Instruction

Regin

Regin E3-DSP Instruction

SWEDX SWSS156 user manual

SWEDX

SWEDX SWSS156 user manual

JUMO mTRON T operating manual

JUMO

JUMO mTRON T operating manual

Saia PCD7.D410VTCF manual

Saia

Saia PCD7.D410VTCF manual

weintek EasyView MT-608S Installation instruction

weintek

weintek EasyView MT-608S Installation instruction

Advantech FPM-212 Series user manual

Advantech

Advantech FPM-212 Series user manual

Siemens INOX PRO SIMATIC IFP1900 Quick install guide

Siemens

Siemens INOX PRO SIMATIC IFP1900 Quick install guide

Simrad NSS12 EVO3S quick guide

Simrad

Simrad NSS12 EVO3S quick guide

eSID 03-06 user guide

eSID

eSID 03-06 user guide

Samsung UD55E-P Quick setup guide

Samsung

Samsung UD55E-P Quick setup guide

HIS HIS-ML12-Series D user manual

HIS

HIS HIS-ML12-Series D user manual

Acnodes APM 5084 Specifications

Acnodes

Acnodes APM 5084 Specifications

BenQ TL650 user manual

BenQ

BenQ TL650 user manual

Kontron FlatClient ECO user guide

Kontron

Kontron FlatClient ECO user guide

AllSee AB49HD7 Hardware user manual

AllSee

AllSee AB49HD7 Hardware user manual

Pentair Raychem ECW-GF-DP Installation and operating instructions

Pentair

Pentair Raychem ECW-GF-DP Installation and operating instructions

Siemens INOX PRO SIMATIC IFP1900 Compact operating instructions

Siemens

Siemens INOX PRO SIMATIC IFP1900 Compact operating instructions

IEI Technology ISDM-084G user manual

IEI Technology

IEI Technology ISDM-084G user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Instruction Manual
1. Marking
VisuNet FLX – Panel Mount
RemoteMonitorRM-320P-*
PersonalComputerPC-320P-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2479X
ATEXmarking:1II3GExec[ic]IICT4Gc
IECExcertificate:IECExULD22.0017X
IECExmarking:Exec[ic]IICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2480U
ATEXmarking:1II3DExtc[ic]IIICDc
IECExcertificate:IECExULD22.0018U
IECExmarking:Extc[ic]IIICDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL),ControlDrawing116-0478
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB
ClassIII,Zone22,GroupIIIA
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Division2,GroupsA-D
ClassII,Division2,GroupsE,F,G
ClassIII
Associatedapparatuswithintrinsicallysafecircuitsfor:
ClassI,Zone2,GroupIIC
ClassII,Zone22,GroupIIIB
ClassIII,Zone22,GroupIIIA
VisuNet FLX – Panel Mount
DirectMonitorDM-320P-*
EquipmentprotectionlevelGc
ATEXcertificate:UL22ATEX2479X
ATEXmarking:1II3GExecIICT4Gc
IECExcertificate:IECExULD22.0017X
IECExmarking:ExecIICT4Gc
EquipmentprotectionlevelDc
ATEXcertificate:UL22ATEX2480U
ATEXmarking:1II3DExtcIIICDc
IECExcertificate:IECExULD22.0018U
IECExmarking:ExtcIIICDc
NorthAmericaCertifcates:
OrdLoc:E223772(UL)
HazLoc:E492874(UL)
Devicesuitableformountingin:
ClassI,Division2,GroupsA-D,T4
ClassII,Division2,GroupsE,F,G
ClassIII
Devicesuitableformountingin:
ClassI,Zone2,GroupIIC,T4
ClassII,Zone22,GroupIIIB
ClassIII,Zone22,GroupIIIA
The*-markedlettersofthetypecodeareplaceholdersforversionsofthe
device.
Pepperl+FuchsGroup
Lilienthalstraße200,68307Mannheim,Germany
Internet:www.pepperl-fuchs.com
2. Validity
Specificprocessesandinstructionsinthisinstructionmanualrequire
specialprovisionstoguaranteethesafetyoftheoperatingpersonnel.
Duetoconstantrevisions,documentationissubjecttopermanentchange.
Pleasereferonlytothemostup-to-dateversion,whichcanbefoundunder
www.pepperl-fuchs.com.
3. Target Group, Personnel
Responsibilityforplanning,assembly,commissioning,operation,
maintenance,anddismountinglieswiththeplantoperator.
Thepersonnelmustbeappropriatelytrainedandqualifiedinordertocarry
outmounting,installation,commissioning,operation,maintenance,and
dismountingofthedevice.Thetrainedandqualifiedpersonnelmusthave
readandunderstoodtheinstructionmanual.
4. Reference to Further Documentation
Observelaws,standards,anddirectivesapplicabletotheintendeduse
andtheoperatinglocation.ObserveDirective1999/92/ECinrelationto
hazardousareas.
Thecorrespondingdatasheets,manuals,declarationsofconformity,EU-
typeexaminationcertificates,certificates,andcontroldrawingsif
applicable(seedatasheet)areanintegralpartofthisdocument.Youcan
findthisinformationunderwww.pepperl-fuchs.com.
Forspecificdeviceinformationsuchastheyearofconstruction,
scantheQRcodeonthedevice.Asanalternative,entertheserialnumber
intheserialnumbersearchatwww.pepperl-fuchs.com.
Duetoconstantrevisions,documentationissubjecttopermanentchange.
Pleasereferonlytothemostup-to-dateversion,whichcanbefoundunder
www.pepperl-fuchs.com.
5. Intended Use
Thedeviceisonlyapprovedforappropriateandintendeduse.Ignoring
theseinstructionswillvoidanywarrantyandabsolvethemanufacturer
fromanyliability.
VisuNetFLXpanelsconsistofadisplayunitwithtouchscreenin
combinationwithacomputingunit.Variousdisplaysizes(21.5inch,
19inchand15.6inch)andconfigurablecomputerunitsleadtohighest
applicationflexibility.TheVisuNetFLXpanelsaredesignedforZone2/22
andnon-Exapplications.
Usethedeviceonlywithinthespecifiedambienttemperaturerange.
Thedevicemustonlybeoperatedinthespecifiedambienttemperature
rangeandatthespecifiedrelativehumiditywithoutcondensation.
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Taketheintendeduseoftheconnecteddevicesfromthecorresponding
documentation.
Thedeviceisanelectricalapparatusforhazardousareas.
Thedeviceisnotsuitableforseparatinghazardousareas.
Excomponentsarenotintendedtobeusedalone.Mountingandusageof
Excomponentsindevicesorsystemsmustbecertifiedseparately.
ExcomponentshavetheUmarkingattheendofthecertificatenumber.
DevicesforwhichspecificconditionsofuseapplyhavetheXmarkingat
theendofthecertificatenumber.
Onlyusethedevicestationary.
6. Improper Use
Protectionofthepersonnelandtheplantisnotensuredifthedeviceisnot
usedaccordingtoitsintendeduse.
Thedeviceisnotsuitabletoseparateintrinsicallysafecircuitsfromnon-
intrinsicallysafecircuits.
Thedeviceisnotsuitableforseparatinghazardousareas.
7. Specific Conditions of Use
Ensurethatthedeviceprovidesandmaintainsadegreeofprotection
ofatleastIP64accordingtoIEC/EN60079-0.
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Onlyconnectsafetyextra-lowvoltagecircuits(SELV)orprotectiveextra-
lowvoltagecircuits(PELV)tothedevice.
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryII(orbetter)accordingtoIEC/EN60664-1.
Onlyconnectsuppliesthatprovideprotectionagainstelectricshock(e.g.
SELVorPELV).
Usethedeviceonlywithinthespecifiedambientandoperatingconditions.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
7.1. Requirements to Equipment
For Direct Monitor DM-320P-*
Securetheconnectionsofthedeviceagainstloosening
bysuitablemeans.
For Remote Monitor RM-320P-* and Personal Computer PC-320P-*
Securetheconnectionsofthedeviceagainstloosening
bysuitablemeans.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
DOCT-7047D/2022-06 1/2
8. Mounting and Installation
Priortomounting,installation,andcommissioningofthedeviceyou
shouldmakeyourselffamiliarwiththedeviceandcarefullyreadthe
instructionmanual.
Usemountingmaterialswhicharesuitabletosecurethedevicesafely.
Usemountingmaterialsthatfitthenatureofthemountingsurface.
Onlyuseaccessoriesspecifiedbythemanufacturer.
Ifmountingtheenclosureonconcreteuseexpansionanchors.When
mountingtheenclosuretoasteelframeworkusevibrationresistant
mountingmaterial.
Ensurethatallfastenersarepresent.
Observethetighteningtorqueofthescrews.
Mountthedeviceinaweatherprooflocation.
Protectthedeviceagainstlong-termorexcessivemechanicalvibrations.
Installthedeviceinlocationswithalowriskofmechanicalhazard
accordingtoIEC/EN60079-0only.
Thedeviceisheavy.Inordertoavoidpersonalinjuriesorproperty
damage,makeappropriateprovisionsforthemountingprocedure.
Donotmountthedeviceatlocationswhereanaggressiveatmosphere
maybepresent.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-14.
ObservetheinstallationinstructionsaccordingtoIEC/EN60079-25.
Ifthedevicehasalreadybeenoperatedingeneralelectricalinstallations,
thedevicemaysubsequentlynolongerbeinstalledinelectrical
installationsusedincombinationwithhazardousareas.
Ensurethattheequipotentialbondingconnectionsareingoodcondition,
andarenotdamagedorcorroded.
Ensurethattheterminalsareingoodconditionandarenotdamagedor
corroded.
Whenconnectingintrinsicallysafedeviceswithintrinsicallysafecircuitsof
associatedapparatus,observethemaximumpeakvalueswithregardto
explosionprotection(verificationofintrinsicsafety).Observethe
standardsIEC/EN60079-14orIEC/EN60079-25.
Observethecomplianceoftheseparationdistancesbetweentwo
adjacentintrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Provideatransientprotection.Ensurethatthepeakvalueofthetransient
protectiondoesnotexceed140%oftheratedvoltage.
Thedevicemustbeinstalledandoperatedonlyinacontrolled
environmentthatensuresapollutiondegree2(orbetter)accordingto
IEC/EN60664-1.
Onlyconnectsafetyextra-lowvoltagecircuits(SELV)orprotectiveextra-
lowvoltagecircuits(PELV)tothedevice.
Protectthecircuitagainstovervoltage(e.g.,lightning).
Thedevicemustbeinstalledandoperatedonlyinanenvironmentof
overvoltagecategoryII(orbetter)accordingtoIEC/EN60664-1.
Thedevicemustbedisconnectedfromthepowersupplypriorto
installationandmaintenance.Thepowersupplymaybeactivatedonly
afterallthecircuitsrequiredforoperationhavebeenfullyassembledand
connected.
OnlyconnectadevicethatisinaccordancewithIEC/EN60950-1andis
designedassafetyextra-lowprotectivevoltage(SELV)system.
Thedeviceprovidesagroundingterminaltowhichanequipotential
bondingconductorwithaminimumcrosssectionof4mm2mustbe
connected.
Securetheconnectionsofthedeviceagainstloosening
bysuitablemeans.
Requirements in Relation to Intrinsic Safety
IfcircuitswithtypeofprotectionExiareoperatedwithnon-intrinsically
safecircuits,theymustnolongerbeusedascircuitswithtypeof
protectionExi.
Observethemaximumvaluesofthedevice,whenconnectingthedevice
tointrinsicallysafeapparatus.
Ifyouinstallfurthersuitablemodulesanddevicesinthesystem,keepthe
separationdistancesbetweenallnon-intrinsicallysafecircuitsand
intrinsicallysafecircuitsaccordingtoIEC/EN60079-14.
Circuitsofintrinsicallysafeapparatuscanbeledintohazardousareas,
wherebyspecialattentionmustbepaidtomaintainingseparation
distancestoallnon-intrinsicallysafecircuitsaccordingtotherequirements
inIEC/EN60079-14.
ObservethegroundingrequirementsfortypeofprotectionExiaccording
toIEC/EN6007914.
Forintrinsicallysafecircuits,thedielectricstrengthoftheinsulationagainst
otherintrinsicallysafecircuitsandagainsttheshieldmustbe
atleast500VaccordingtoIEC/EN60079-14.
Equipotentialbondingmustbeachievedalongtheintrinsicallysafe
circuits.
Requirements for Cables and Connection Lines
Observethemaximumpermissiblelengthofcablesandconnectionlines.
Thedielectricstrengthoftheinsulationmustbeatleast500Vaccordingto
IEC/EN60079-14.
Observethepermissiblecorecrosssectionoftheconductor.
Theinsulationstrippinglengthmustbeconsidered.
Wheninstallingtheconductorstheinsulationmustreachuptothe
terminal.
Whenusingstrandedconductors,crimpwireendferrulesonthe
conductorends.
Observetheminimumbendingradiusoftheconductors.
Unusedcablesandconnectionlinesmustbeeitherconnectedtoterminals
orsecurelytieddownandisolated.
Installthecablesandconnectionlinesinsuchawaythattheyare
protectedfromultravioletradiation.
Installcablesandcableglandsinawaythattheyarenotexposedto
mechanicalhazards.
Equipotentialbondingmustbeachievedalongthefieldcircuits.
Requirements in Relation to Electrostatics
Avoidelectrostaticchargeswhichcouldresultinelectrostaticdischarges
whileinstalling,operating,ormaintainingthedevice.
Avoidinadmissiblyhighelectrostaticchargeofthecablesandconnection
lines.
Includethemetalhousingcomponentsintheequipotentialbonding.
Anelectrostaticchargeposesanignitionhazardincaseofdischarge.
Includethefastenersintheequipotentialbonding.
Requirements for Surrounding Enclosures
Ifadditionalsurroundingenclosuresarerequired,thefollowingpointsmust
beconsideredduringinstallation:
lDegreeofprotectionaccordingtoIEC/EN60529
lResistancetolightaccordingtoIEC/EN60079-0
lResistancetoimpactaccordingtoIEC/EN60079-0
lResistancetochemicalagentsaccordingtoIEC/EN60079-0
lThermalenduranceaccordingtoIEC/EN60079-0
lElectrostaticsaccordingtoIEC/EN60079-0
Ensurethatthedeviceprovidesandmaintainsadegreeofprotection
ofatleastIP64accordingtoIEC/EN60079-0.
Mountthedevicesothatitcomplieswiththespecifieddegreeof
protectionaccordingtoIEC/EN60529.
9. Operation, Maintenance, Repair
Priortousingtheproductmakeyourselffamiliarwithit.Readthe
instructionmanualcarefully.
ObserveIEC/EN60079-17formaintenanceandinspection.
Donotuseadamagedorpolluteddevice.
Ifthereisadefect,thedevicemustberepairedbyPepperl+Fuchs.
Thedevicemustnotberepaired,changed,ormanipulated.Incaseof
failure,alwaysreplacethedevicewithanoriginaldevice.
Observethewarningmarkings.
Donotremovethewarningmarkings.
Ifthedeviceisinstalledinpotentiallyexplosivedustatmosphere,remove
dustlayerswhichexceed5mminregularintervals.
Connectionordisconnectionofenergizednon-intrinsicallysafecircuitsis
onlypermittedintheabsenceofapotentiallyexplosiveatmosphere.
Ifcleaningisnecessarywhilethedeviceislocatedinahazardousarea,in
ordertoavoidelectrostaticchargingonlyuseacleandampcloth.
Avoidmechanicalimpactstothedevice(e.g.fromheavyorsharp-
edgedobjects).
Thedevicecangetveryhotduringoperation.Toprotectthedevicefrom
excessiveheating,observetherequiredclearancesandsufficient
ventilationwheninstallingthedevice.
Donotuseinterfacesthatarenotintendedfortheuseintheexplosion-
hazardousarea.
Donotuseoperatingelementsthatarenotintendedfortheuse
intheexplosion-hazardousarea.
10. Delivery, Transport, Disposal
Checkthepackagingandcontentsfordamage.
Checkifyouhavereceivedeveryitemandiftheitemsreceivedarethe
onesyouordered.
Keeptheoriginalpackaging.Alwaysstoreandtransportthedeviceinthe
originalpackaging.
Storethedeviceinacleananddryenvironment.Thepermittedambient
conditionsmustbeconsidered,seedatasheet.
Thedevice,built-incomponents,packaging,andanybatteriescontained
withinmustbedisposedincompliancewiththeapplicablelawsand
guidelinesoftherespectivecountry.
DOCT-7047D/2022-06 2/2