connecting RS485 data cable
Use a screened, stranded RS485 data cable with three twisted
pairs.
Connect data cable to devices in a ‘daisy chain’. Start at the
first device, then loop in and out of devices, with a single cable
termination at the last device.
The data cable should be segregated from any Mains Cables. If
the Data Cable has to cross over mains cables, it should do so
at a 90° angle.
A data cable that is connected to an energised dimmer is live.
Do not cut or terminate live data cables.
RS485 Serial Port: 1 x RS485 unterminated DyNet, consisting of 1 x 5 way terminal block, for permanent connections.
Inputs: 1 x Presented on a 2mm pitch 160mm long ribbon cable
Internal Controls: Programmable Logic Controller
Operating Environment: 0º to 50ºC ambient temperature, 0% to 95% RH non condensing
Power Consumption: 15mA from the DyNet network
Compliance: CE, C-Tick
Construction: Bare circuit board with heatshrink cover
Dimensions: H 19mm x W 40mm x D 19mm
Weight: 15.5 grams
DPMI940 Instruction Manual Revd.Doc Specifications subject to change without notice
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail: dynalite.info@philips.com Web: Philips.com/dynalite
Inputs: 7 core Flat Ribbon Cable
Flying Lead inputs
To trigger a preset place a short between SW 1, 2, 3 or
4 to the Ground. The +12V terminal is provided to
power 3rd party devices such as motion detectors,
ensure that it does not touch any other terminal of the
device.
connecting volt free inputs
Connect Ground and +12V leads to the motion detector’s 0V &
+12V terminals.
Connect Ground and Switch 1 leads to the motion detector’s
Alarm terminals.
Connect Ground and Switch 4 leads to the motion detector’s
Tamper terminals.
connecting to a motion detector
Connect Data Cable in a ‘Daisy Chain’
Serial Cable Permanent Connections
recommended cable colour coding
Green/White Pair paralleled for GND
Orange/White Pair paralleled for +12V
Blue/White Pair Blue for DATA+
White for DATA-
recommended cable types
Belden: 9503
Garland: MCP3S
Hartland: HCK603
M&M Cable: B2003CS
Dynalite: DYNET-STP-CABLE
M&M cable: B9503CS
Multicables: AWME120236209220