Phoenix Contact IBS IL 24 BK-T/U User manual

6291A 1
IBS IL 24 BK-T/U
10/2001
Data Sheet 6291A
This data sheet is only valid in
association with the "Configuring and
Installing the INTERBUS Inline
Product Range" User Manual
IB IL SYS PRO UM E.
This bus terminal replaces the
IBS IL 24 BK-T bus terminal, which
was supplied until now (see page 7).
Function
The bus terminal connects an Inline station to the
INTERBUS remote bus and provides the supply
voltages for the connected devices.
Features
– Remote bus connections using copper
cables
– Can supply an Inline station with all of the
required 24 V voltages for low-level signals
– Electrical isolation of the remote bus
segments
– Automatic configuration of the outgoing
interface as remote bus interface or local bus
interface
– Support of up to 15 connected terminals with
remote bus branch
Figure 1 IBS IL 24 BK-T/U terminal with
connectors and end plate
Please note that the connectors are
not supplied as standard with the
terminal. To order these connectors,
please refer to the "Ordering Data" on
page 22.
The end plate is supplied with the bus terminal.
Place this plate at the end of the Inline station.
The end plate does not have any electrical
function. It protects the station from ESD pulses
and the user from dangerous voltage.
6 2 9 1 A 0 0 2
6 2 9 1 A 0 0 1
INTERBUS Inline Bus Terminal

IBS IL 24 BK-T/U
26291A
Figure 2 Diagnostic indicators on the IBS IL 24 BK-T/U terminal
Local Diagnostic Indicators
6291A003
B A
R C
B K - T / U
R D
L D
U L U S
U M
Des. Color Meaning
BA Green Bus active
RC Green Remote bus cable check
RD Yellow Outgoing remote bus switched off
LD Yellow Local bus switched off
UL Green 24 V bus terminal supply/7.5 V communications power/interface supply
US Green 24 V segment supply
UM Green 24 V main supply

IBS IL 24 BK-T/U
6291A 3
Figure 3 Terminal point assignment
Terminal Point Assignment
55600005
1 2
1
2
3
4
1
2
3
4
1 . 1
1 . 2
1 . 3
1 . 4
2 . 1
2 . 2
2 . 3
2 . 4
1 2
1
2
3
4
1
2
3
4
1 . 1
1 . 2
1 . 3
1 . 4
2 . 1
2 . 2
2 . 3
2 . 4
Terminal
Point
Assignment Remark/
Wire Color in the INTERBUS Standard Cable
Connector 1 Incoming Remote Bus
1.1 DO1 Receive Green
2.1 DO1 Receive Yellow
1.2 DI1 Send Pink
2.2 DI1 Send Gray
1.3 F-GND Reference
potential
Brown
2.3 Not used
1.4, 2.4 Shield Shield potential is connected with a capacitor to functional
earth ground (FE) of the potential jumper.
Connector 2 Outgoing Remote Bus
1.1 DO2 Send Green
2.1 DO2 Send Yellow
1.2 DI2 Receive Pink
2.2 DI2 Receive Gray
1.3 R-GND Reference
potential
Brown
2.3 Not used
1.4, 2.4 Shield Shield potential is directly connected to functional earth
ground (FE) of the potential jumper.

IBS IL 24 BK-T/U
46291A
Terminal
Point
Assignment Remark/
Wire Color in the INTERBUS Standard Cable
Connector 3 Reconfiguration Connector/Bus Terminal Supply
1.1, 2.1 Connection of the
external reconfiguration
button
See Figure 6 on page 10
1.2, 2.2 24 V DC UBK 24 V bus terminal supply
Supply of the bus terminal power supply unit
1.3, 2.3 BK-GND GND GND of the bus terminal supply
This potential is reference ground for the bus terminal
electronics.
1.4, 2.4 FE Functional
earth
ground
Grounding of the bus terminal, i.e., of the Inline station
The contacts are directly connected with the potential
jumper and the FE spring on the bottom of the housing.
Functional earth ground is only used to
discharge interference.
Connector 4 Power Connector
1.1, 2.1 24 V DC US24 V segment supply
The supplied voltage is directly led to the potential jumper.
1.2, 2.2 24 V DC UM24 V main supply
The supplied voltage is directly led to the potential jumper.
1.3, 2.3 GND Reference
potential
The reference potential is directly led to the potential
jumper and is, at the same time, ground reference for the
main and segment voltage.
1.4, 2.4 FE Functional
earth
ground
Grounding of the bus terminal, i.e., of the Inline station
The contacts are directly connected with the potential
jumper and the FE spring on the bottom of the housing.
Functional earth ground is only used to
discharge interference.

IBS IL 24 BK-T/U
6291A 5
Do not mix up the connectors
Do not mix up the connectors, especially the remote bus connectors and connectors for
the voltage supply, as this may damage the terminal.
Observe the current carrying capacity
The maximum total current of the potential jumpers UMand US is 8 A.
Ground the bus terminal
Connect the bus terminal to functional earth ground (FE) via one of the FE connections of
connector 3 or connector 4. Connect the corresponding contact with a grounding terminal
block (see also Figure 6 on page 10).

IBS IL 24 BK-T/U
12 6291A
Technical Data
General Data
Order Designation IBS IL 24 BK-T/U
OrderNo. 2742094
Housing dimensions (width x height x depth) 48.8 mm x 120 mm x 71.5 mm
(1.921 in. x 4.724 in. x 2.815 in.)
Weight 142 g (without connectors)
Permissible temperature (operation) -25°C to +55°C (-13°F to +131°F)
Permissible temperature (storage/transport) -25°C to +85°C (-13°F to +185°F)
Permissible humidity (operation) 75% on average, 85% occasionally
In the range from -25°C to +55°C (-13°F to +131°F) appropriate measures against
increased humidity (> 85%) must be taken.
Permissible humidity (storage/transport) 75% on average, 85% occasionally
For a short period, slight condensation may appear on the outside of the housing if, for
example, the terminal is brought into a closed room from a vehicle.
Permissible air pressure (operation) 80 kPa to 106 kPa
(up to 2000 m [6562 ft.] above sea level)
Permissible air pressure (storage/transport) 70 kPa to 106 kPa
(up to 3000 m [9843 ft.] above sea level)
Degree of protection IP 20 according to IEC 60529
Class of protection Class 3 according to VDE 0106, IEC 60536
Interfaces (INTERBUS)
Remote Bus
Incoming remote bus Copper cable (RS-422), connected with Inline
shield connector; supply electrically isolated;
shielding connected with a capacitor to functional
earth ground
Outgoing remote bus Copper cable (RS-422), connected with Inline
shield connector; supply electrically isolated;
shielding directly connected to functional earth
ground
Recommended cable lengths See INTERBUS system data

IBS IL 24 BK-T/U
6291A 13
Branch/Local Bus
Connection Through data routing
Level 5 V CMOS signal level
Number of Inline terminals that can be connected
Limitation through software
Limitation through power supply unit
63, maximum
Maximum logic current consumption of the
connected local bus modules: Imax 2 A DC
Observe the current consumption of the modules
Observe the logic current consumption of each device when configuring an Inline station.
This information is given in every module-specific data sheet. The current consumption
can differ depending on the individual module. The permissible number of devices that
can be connected depends on the specific station structure.
Functions
Reconfiguration (external) If necessary, you can connect an external
reconfiguration button to the bus terminal (see
Figure 6 on page 10).
Pressing this button activates the reconfiguration
request to the controller board.
Interface configuration (internal) When the next device is snapped on, the bus
terminal configures the interface automatically.
If the next device is a terminal with remote bus
branch, the interface is configured as a remote
bus interface.
For every other device (e.g., I/O terminal) the
interface is configured as a local bus interface
with diagnostics.
Interfaces (INTERBUS) (Continued)

IBS IL 24 BK-T/U
14 6291A
24 V Main Supply/24 V Segment Supply
Connection Through power connector
For terminal point assignment see page 3
Connection method Spring-clamp terminals
Recommended cable lengths 30 m (98.43 ft.), maximum; do not route cable
through outdoor areas
Voltage continuation Through potential routing
Special demands on the voltage supply UM/USare electrically isolated from the bus
terminal supply UBK if they are supplied
separately. This is only possible when using two
separate power supply units.
Behavior if voltage dips and interrupts occur Voltages (main and segment supply) that are
transferred from the bus terminal to the potential
jumpers follow the supply voltages without delay.
Nominal value 24 V DC
Tolerance -15%/+20% (according to EN 61131-2)
Ripple ±5%
Permissible range 19.2 V to 30 V
Current carrying capacity 8 A, maximum
Safety measures
Surge voltage Yes
Polarity reversal Yes
Provide an external fuse for the 24 V area
This 24 V area must be fused externally. The power supply unit must be able to supply 4
times the nominal current of the external fuse, to ensure that the fuse blows safely in the
event of an error.

IBS IL 24 BK-T/U
6291A 15
24 V Bus Terminal Supply
Connection Through connector
For terminal point assignment see page 3
Connection method Spring-clamp terminals
Recommended cable lengths 30 m (98.43 ft.), maximum; do not route cable
through outdoor areas
Voltage continuation Through potential routing
Special demands on the voltage supply The bus terminal supply UBK is electrically
isolated from UM/USwhen it is supplied
separately. This is only possible when using two
separate power supply units.
Nominal value 24 V DC
Tolerance -15%/+20% (according to EN 61131-2)
Ripple ±5%
Permissible range 19.2 V to 30 V
Minimum current consumption at nominal voltage 0.10 A DC
(At no-load operation, i.e., incoming remote bus
connected, no local bus devices are connected,
bus inactive)
Maximum current consumption at nominal voltage 1.25 A DC
Consisting of:
0.75 A DC for communications power
0.5 A DC for analog voltage supply
Safety measures Only for the bus terminal supply
Surge voltage Yes
Polarity reversal Yes
Provide an external fuse for the 24 V area
This 24 V area must be fused externally. The power supply unit must be able to supply 4
times the nominal current of the external fuse, to ensure that the fuse blows safely in the
event of an error.

IBS IL 24 BK-T/U
16 6291A
24 V Module Supply
Communications Power (Potential Jumper)
Nominal value 7.5 V DC
Tolerance ±5%
Ripple ±1.5%
Maximum output current 2 A DC (observe derating)
Safety measures Electronic short-circuit protection
Communications Power (Interfaces)
Nominal value 2 x 5 V DC
Tolerance ±5%
Ripple ±1.5%
Maximum output current 2 x 0.15 A DC
Safety measures None
Communications Power (Internal)
Nominal value 1 x 5 V DC
Tolerance ±5%
Ripple ±1.5%
Maximum output current 1 x 0.15 A DC
Safety measures None
Analog Supply (Potential Jumper)
Nominal value 24 V DC
Tolerance -15%/+20%
Ripple ±5%
Maximum output current 0.5 A DC (observe derating)
Safety measures Electronic short-circuit protection
Table of contents