Installation Instructions
Wayfinder™2
Phoenix Lighting 8711 West Port Avenue Milwaukee, WI 53224 USA
Phone: +1 414.973.3300 Toll Free: 800.438.1214 Fax: +1 414.973.3210 www.phoenixlighting.com
Wiring (EMB)
If fixture is provided with a cord installed:
1. Insert cord into a waterproof junction box (not provided).
2. Connect the wires according to Figure 4 (black to switched line (L2), white to neutral (N), red to charging line (L1), green to ground (PE)).
3. Remove front cover by loosening the six screws. Note that these are captive screws and should not be completely removed from cover.
4. Connect the two wires inside from the battery (see Figure 5).
5. Reattach cover. Use caution not to pinch wires between fixture housing.
6. Tighten screws to 20-23 lb-in (2.2-2.6 N-m).
If fixture is not provided with a cord installed, then standard Wayfinder 2 EMB fixtures are provided with 2 cord grips:
1. Remove front cover by loosening the six screws. Note that these are captive screws and should not be completely removed from cover.
2. Minimum 90°C supply conductors should be used.
3. Insert power supply cord into first cord grip far enough so you are able to see cord jacket inside fixture. Tighten cord grip to 30-35 lb-in (3.5 -4.0 N-m).
4. If installing with through-wire, install second cord same as Step 2.
5. Connect wires using connectors provided according to Figure 4 (black to switched line (L2), white to neutral (N), red to charging line (L1),
green to ground(PE)).
6. Connect the two wires inside from the battery (see Figure 5).
7. Reattach cover. Use caution not to pinch wires between the fixture housing.
8. Tighten screws to 20-23 lb-in (2.2–2.6 N-m).
9. If not installing with through-wire, remove outside cord grip and insert M20 threaded plug into unused cord grip hole. Tighten to 53 in-lbs (6 N-m).
If fixture is not provided with a cord installed, then the standard Wayfinder 2
fixture comes with 2 cord grips:
1. Remove front cover by loosening the six screws. Note that these are
captive screws and should not be completely removed from cover.
2. Minimum 90°C supply conductors should be used.
3. Insert power supply cord into first cord grip far enough so you are able
to see cord jacket inside fixture. Tighten cord grip to 30-35 lb-in
(3.5 -4.0 N-m).
4. If installing with through-wire, install second cord same as Step 2.
5. Connect wires using connectors provided according to Figure 3 (black to
line (L2), white to neutral (N), green to ground (PE)).
6. Reattach cover. Use caution not to pinch wires between fixture housing.
7. Tighten screws to 20-23 lb-in (2.2–2.6 N-m).
8. If not installing with through-wire (non-interconnection type), use
supply cords of at least 16-18 AWG or with a minimum cross-sectional
area 1.0 mm2 - 1.5 mm2 with an outer diameter in range of 5mm-9mm.
Remove outside cord grip and insert M20 threaded plug (supplied) into
unused cord grip hole. Tighten to 53-in-lbs (6 N-m).
9. If installing with through-wire (interconnection type), use supply
cords of at least 12 AWG minimum or with a minimum cross-sectional
area of 4.0 mm2 (for interconnection type). The outside diameter of
cables should be in range of 5mm-9mm. Use a wrench to make the
cord grip(s) and/or threaded plug fully tightened with a torque of
at least 53 in-lbs (6 N-m).
Figure 3
N/A
supply
white or
blue (N)
green and
yellow (PE)
black or
brown (L2)
white (N)
black (L2)
N/A
green (PE)