manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Pittway
  6. •
  7. Security Sensor
  8. •
  9. Pittway System Sensor WFDT User manual

Pittway System Sensor WFDT User manual

N770-05-00 1 I56-480-05R
WFDT/WFDTH Vane-type
Waterflow Detectors
INSTALLATION AND MAINTENANCE INSTRUCTIONS
A Division of Pittway
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Specifications
Contact Ratings: Two sets of SPDT (Form C)
10 A @ 125/250 VAC; 2.5 A @ 24 VDC
Triggering Threshold Bandwidth (Flow Rate): 4 - 10 GPM
Static Pressure Rating: 250 PSI (Max.)
Dimensions, Installed: WFDT– 45/16
″
H ×33/4
″
W ×63/4
″
D
WFDTH– 45/16
″
H ×39/16
″
W ×63/4
″
D
Operating Temperature Range: 32°F - 120°F (0°C - 49°C)
Shipping Weight: 2.6 lbs.
Enclosure Rating: WFDT– NEMA Type 4, as tested by Underwriters Laboratories, Inc. (U.L.)
WFDTH– Indoor use only, as tested by U.L.
The WFDTH can be installed between 2X4 stud wall construction.
Important
Please Read Carefully And Save
This instruction manual contains important information
about the installation and operation of waterflow detectors.
Purchasers who install waterflow detectors for use by
others must leave this manual or a copy of it with the user.
Read all instructions carefully before beginning.
CAUTION
Use vane-type waterflow detectors in wet-pipe systems
only. DO NOT USE IN DRY-PIPE, DELUGE, OR PRE-AC-
TION SYSTEMS. The sudden inrush of water in such sys-
tems may break the vane off or damage the mechanism. Do
not use in potentially explosive atmospheres. Do not leave
unused wires exposed.
Principles Of Operation
Vane-type waterflow detectors mount to water filled pipes
in sprinkler systems. Water flow in the pipe deflects a vane.
Deflection of the vane produces a switched output, usually
after a specified delay.
All WFDTs have a pneumatically controlled mechanical
delay mechanism. Delays are noncumulative; they reset if
the flow of water stops before the entire delay has elapsed.
All detectors will activate on a sustained flow of water
greater than 10 gallons per minute (gpm) but will not
activate if the flow rate is less than 4 gpm.
Compatible Pipe Tees
The WFDT and WFDTH fit 1
″
to 11/2
″
NPT threaded ferrous
and brass, 1
″
to 2
″
sweat brass, 11/2
″
polybutylene plastic
and 1
″
pvc plastic tees having a 1
″
threaded NPT branch
(see Figure 1 and chart for recommended tee depths).
Installation Guidelines
Before installing any waterflow alarm device, be
thoroughly familiar with:
NFPA 72: National Fire Alarm Code
NFPA 13: Installation of Sprinkler Systems
NFPA 25: Inspection, Testing, and Maintenance of
Water-based Fire Protection Systems
NFPA 13D: Standard for 1 and 2 Family Dwellings and
Manufactured Homes
NFPA 13R: Standard for Multi-family Dwellings
Figure 1. Mounting dimensions:
A78-1939-00
3
3
/
4
″
(WFDT)
3
9
/
16
″
(WFDTH)
3″
4
5
/
16
″
Gage (End of Paddle Tree)
Must Fit Between Top of
Tee and Bottom of Flange
Tee Fitting
Plastic Vane
Tee Adapter
Tee Depth
Refer to
Tee Depth
Table
ApproximateTee Depth Requirements
(See Figure 1)
Tee Depth Threaded Sweat Poly B CPVC
1 ×1 ×1″
1
1
/
4
×1
1
/
4
×1″
1
1
/
2
×1
1
/
2
×1″
2 ×2 ×1"
2
1
/
8
″
2
1
/
2
″
2
3
/
4
″
N/A 2
3
/
4
″
2
1
/
4
″
2
1
/
6
″N/A
2
1
/
2
″N/AN/A N/A
N/A
1
3
/
4
″N/A 2
1
/
4
″CPVC/Spears CPVC/Central
N/A
N/A N/AN/A N/A
N/A
2
15
/
32
″2
13
/
16
″
Technical Manuals Online! - http://www.tech-man.com
N770-05-00 2 I56-480-05R
Also, follow other applicable NFPA standards, local codes
and the requirements of the authority having jurisdiction.
Failure to follow these directions may result in failure of the
device to report a waterflow condition. System Sensor is
not responsible for devices that have been improperly
installed, tested or maintained.
1. Mount the detector where there is adequate clearance
for installation and removal and a clear view of it for in-
spection. See Figure 1 for mounting dimensions.
2. Locate to protect from damage, 6-7 feet above the floor.
3. On horizontal runs, position the detector on top of the
pipe or on the side of it. Do not mount it upside down
because condensation may collect in the housing and
impair the operation of the detector.
For vertical flow applications, mount detector on pipe
where upflow conditions exist. Failure to do so may pre-
vent unit from operating properly.
4. Mount detector at least 6 inches from a fitting which
changes the direction of the water flow, or no closer than
24 inches from a valve or drain.
5. BE SURE DIRECTION-OF-FLOW ARROW MATCHES AC-
TUAL DIRECTION OF FLOW IN THE PIPE.
Mounting Instructions
1. The WFDT and WFDTH waterflow detectors are de-
signed to fit only the appropriate tee fitting.
NOTE: Leg of tee perpendicular to flow of water must
have a 1"NPT thread. Do not use a reducer to
achieve the correct thread size. Failure to follow
this instruction will result in failure of the detector
to report a waterflow condition.
2. WFDT and WFDTH units are shipped without paddles
mounted to the actuator. Select the correct size paddle
for the type of tee being used. Align hole on stem of
paddle with hole on actuator lever. Fasten together using
a #4-40 x 1/4"fillister head screw supplied in bag as-
sembly. See Figure 2. Use only the screw provided with
the unit. Drive screw head through hole in paddle until
it seats to actuator lever surface. No washer is required.
For paddle replacement refer to Maintenance section.
3. Carefully roll the vane opposite the direction of flow and
insert through tee. Thread detector onto tee fitting and
tighten with wrench. Use of thread sealant or tape is rec-
ommended. Use height gage (located at end of paddle
tee) to ensure proper depth of detector on tee fitting. See
Figure 1. Height gage must fit between top of tee fitting
and under side of hex tee adapter. A gap between gage
and tee adapter is acceptable. When correctly installed,
the detector must face in the proper direction of
waterflow and be aligned with the pipe.
4. Remove the metal cover. Move the actuator lever back
and forth to check for binding. If the vane binds, remove
the detector and correct the problem before proceeding.
CAUTION
Be sure the direction-of-flow arrow points in the right direc-
tion, otherwise a waterflow condition will go unreported.
See Figure 2.
Preoperation Testing
1. Fill the sprinkler system with water and check for leaks
around the WFDT or WFDTH. If there is a leak, check to
see that the fittings are tight. If leak persists, drain the
system and remove the detector (see removal instruc-
tions under Maintenance). Check for damaged threads
or cracked fitting. Reinstall the detector and check again
for leaks. Do not proceed until all leaks have been
stopped.
2. Connect an ohmmeter or continuity tester across (COM
and B) terminal switch contacts. The ohmmeter should
show an open circuit, no continuity.
3. Deflect the actuator lever and hold it until the pneumatic
delay shaft releases the switch buttons. The ohmmeter
or continuity tester should show a short circuit after the
delay has elapsed. If there is no delay, check the setting
of the delay adjustment dial.
Figure 2. Assembly diagram:
GROUND
SCREW
(GREEN)
MOUNTING
PLATE
FLOW
WATERFLOW
FILLISTER
HEAD SCREW
ACTUATOR
LEVER
PADDLE
(PADDLE
REPLACEMENT
KIT (P/N PRK9)
COVER
SWITCH ENCLOSURE
(REPLACEMENT
P/N A77-01-02)
DELAY
MECHANISM
(REPLACEMENT
P/N A3008-00)
1″NPT THREAD
TAMPER PROOF
WRENCH (P/N WFDW)
GASKET
(WFDT ONLY)
A78-2134-01
(Cover tamper option is available.)
Technical Manuals Online! - http://www.tech-man.com
N770-05-00 3 I56-480-05R
Field Wiring
WARNING
High Voltage. Electrocution Hazard. Do not handle live AC
wiring or work on a device to which AC power is applied.
Doing so may result in severe injury or death.
1. The WFDT and WFDTH have two SPDT switches. Switch
contacts (COM and B) are closed when water is flowing
and open when water is not flowing. Connect the switches
as shown in Figure 3 depending on the application.
2. When connected to a listed sprinkler/fire alarm control
panel, the initiating circuit must be non-silenceable.
3. A ground screw is provided with all units. When ground-
ing is required, clamp wire with screw in hole located
between conduit entrance holes. See Figure 2.
Mechanical Delay Adjustment
The pneumatic delay is preset at dial setting 2 at the
factory. To adjust the delay, turn the adjustment dial on the
delay mechanism. Turn clockwise to increase the delay,
counterclockwise to decrease the delay. Delay can be
adjusted over a range from 0-70 seconds. See Figure 4.
NOTE: Set the delay to the minimum required to prevent
false alarms due to flow surges.
After extended service, parts of the detector may become
worn reducing the delay time and causing false alarms. If
this happens, increase the delay. If the delay is already at
maximum, replace the mechanical delay assembly. Refer to
Maintenance section for ordering replacement parts.
Figure 3. Field wiring:
Top View
Switch 1
COM
COM
ABBA Switch 2
NOTE: Common and B connections will
close when vane is deflected, i.e.,
when water is flowing. Dual switches
permit applications to be combined
on a single detector.
CONTACT RATINGS
125/250VAC
24VDC 10 AMPS
2.5 AMPS
WFDTH
WFDT
BB
COM COM
WFDTH
WFDT
BB
COM COM
Typical FACP Connection
to nonsilenceable initiating
zone of listed FACP end-of-line resistor
B
COM
to power source
compatible
with bell local
bell
WFDT andWFDTH
switch assembly
Typical Local Bell Connection
Break wire as shown for
supervision of connection.
DO NOT allow stripped wire
leads to extend beyond
switch housing. DO NOT
loop wires.
A78-1992-00
Figure 4. Delay adjustment dial:
0
1
2
3
4
5
0
1
5
3
0
4
5
5
5
7
0
0
1
2
3
4
5
Table of dial settings
embossed here.
See below.
Delay adjustment dial
Dial setting 0 1 2 3 4 5
Seconds (±50%) 0 15 30 45 55 70
A78-1596-06
Technical Manuals Online! - http://www.tech-man.com
N770-05-00 4 I56-480-05R
© System Sensor 2000
Operational Testing
Always notify a central station monitoring waterflow
alarms before repairing, maintaining or testing waterflow
alarm devices.
1. Replace the cover and tighten the security screws with
the tamper proof wrench. Store the wrench in a secure
place.
2. Open the inspector’s test valve and time how long it
takes for the detector to indicate a flow condition. The
detector should remain activated until the inspector’s
test valve is closed. Air pockets in the sprinkler system
may increase the apparent time delay.
Maintenance
To prevent accidental water damage, control valves should
be shut tightly and the system completely drained before
waterflow detectors are removed or replaced.
Inspect detectors monthly for leaks. Test detectors at least
monthly as described under Operational Testing above to
insure proper operation. This device is not designed for use
on “dry pipe” systems. Test more often if required by the
authority having jurisdiction.
Under normal conditions System Sensor waterflow
detectors should provide years of trouble-free service. If,
however, the delay mechanism becomes faulty,
replacement kits are available. To replace the delay
mechanism, request Part No. A3008-00; for switch
enclosure, request Part No. A77-01-02. Complete
instructions are enclosed with each. Either mechanism can
be easily replaced without removing the detector from the
pipe or draining the pipe. If damage occurs to paddle, order
replacement kit PRK9. Refer to procedure below for
removal of detector on pipe. Do not repair or replace any
other waterflow detector components in the field. If any
other part of the detector does not perform properly,
replace the entire detector. Failure to follow this
instruction may result in failure of the detector to report
a waterflow condition.
Proceed as follows to remove a detector.
1. Drain the pipe.
2. Turn off electrical power to the detector, and then dis-
connect wiring.
3. Unscrew WFDT or WFDTH from tee fitting.
4. Lift detector clear of pipe.
CAUTION
If a vane breaks off in a pipe, find and remove it. Failure to
do so may restrict the proper flow of water to part of the
sprinkler system.
Three-Year Limited Warranty
System Sensor warrants its enclosed waterflow detector to be free from de-
fects in materials and workmanship under normal use and service for a
period of three years from date of manufacture. System Sensor makes no
other express warranty for this waterflow detector. No agent, representa-
tive, dealer, or employee of the Company has the authority to increase or
alter the obligations or limitations of this Warranty. The Company’s obli-
gation of this Warranty shall be limited to the repair or replacement of any
part of the waterflow detector which is found to be defective in materials
or workmanship under normal use and service during the three year pe-
riod commencing with the date of manufacture. After phoning System
Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authori-
zation number, send defective units postage prepaid to: System Sensor,
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL
60174. Please include a note describing the malfunction and suspected
cause of failure. The Company shall not be obligated to repair or replace
units which are found to be defective because of damage, unreasonable
use, modifications, or alterations occurring after the date of manufacture.
In no case shall the Company be liable for any consequential or incidental
damages for breach of this or any other Warranty, expressed or implied
whatsoever, even if the loss or damage is caused by the Company’s negli-
gence or fault. Some states do not allow the exclusion or limitation of inci-
dental or consequential damages, so the above limitation or exclusion may
not apply to you. This Warranty gives you specific legal rights, and you
may also have other rights which vary from state to state.
WARNING
The Limitations of Waterflow Alarm Devices
1. Waterflow detectors may not work or operate properly if
sprinkler piping being monitored is plugged with pipe
scale, mud, stones or other foreign material. Sprinkler
systems should be checked regularly for such blocking
material, following the instructions in NFPA Standard 25.
2. Alarms generated by the activation of waterflow detec-
tors may not be received by a central station if telephone
or other communication lines to the detector are out of
service, disabled, or open.
3. Vane-type waterflow detectors have a normal service life
of 10-15 years. Hard water systems, however, may re-
duce waterflow detector service life to 4 or 5 years.
4. If valves controlling the water supply to a sprinkler sys-
tem are closed, vane-type waterflow detectors will not
work. All valves controlling a sprinkler water supply
should be sealed or locked in the normally open posi-
tion. The normally open position should be monitored
by a sprinkler supervisory switch.
Please refer to insert for the Limitations of Fire Alarm Systems
Technical Manuals Online! - http://www.tech-man.com

This manual suits for next models

1

Other Pittway Security Sensor manuals

Pittway SYSTEM SENSOR 1151EIS User manual

Pittway

Pittway SYSTEM SENSOR 1151EIS User manual

Pittway SYSTEM SENSOR 5451EIS User manual

Pittway

Pittway SYSTEM SENSOR 5451EIS User manual

Pittway System Sensor WFDTNR User manual

Pittway

Pittway System Sensor WFDTNR User manual

Pittway ECO1005 User manual

Pittway

Pittway ECO1005 User manual

Popular Security Sensor manuals by other brands

HST HD201-Mini Installation and maintenance instructions

HST

HST HD201-Mini Installation and maintenance instructions

SIM SIM2W-FLOOD-I installation instructions

SIM

SIM SIM2W-FLOOD-I installation instructions

SPX RADIODETECTION RD5100 H2O+ Operation manual

SPX

SPX RADIODETECTION RD5100 H2O+ Operation manual

Asco P152 Series Installation and maintenance instructions

Asco

Asco P152 Series Installation and maintenance instructions

ZKTeco ZK-D4330 user manual

ZKTeco

ZKTeco ZK-D4330 user manual

CPS LS790B owner's manual

CPS

CPS LS790B owner's manual

Buckleys Wet Roof Pro' operating instructions

Buckleys

Buckleys Wet Roof Pro' operating instructions

Hioki PD3259-90 instruction manual

Hioki

Hioki PD3259-90 instruction manual

PCB Piezotronics ICP 113A22 Installation and operating manual

PCB Piezotronics

PCB Piezotronics ICP 113A22 Installation and operating manual

Bircher Reglomat MERKUR operating instructions

Bircher Reglomat

Bircher Reglomat MERKUR operating instructions

Velocity VDOT-UB4 quick start guide

Velocity

Velocity VDOT-UB4 quick start guide

Sun Microsystems FI316 user manual

Sun Microsystems

Sun Microsystems FI316 user manual

diagral RP550 manual

diagral

diagral RP550 manual

Chentronics iScan3 Series Operation manual

Chentronics

Chentronics iScan3 Series Operation manual

Minelab VANQUISH 340 Getting started

Minelab

Minelab VANQUISH 340 Getting started

Jorc LOCATOR-EV instructions

Jorc

Jorc LOCATOR-EV instructions

Screening Eagle proceq UT8000 user manual

Screening Eagle

Screening Eagle proceq UT8000 user manual

SECUMAR GOLF 275 HV ALU quick start guide

SECUMAR

SECUMAR GOLF 275 HV ALU quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.