Polyaire Zonemaster Variable Air Volume Guide

VAV
(VARIABLE AIR VOLUME)
CLIMATE ZONING SYSTEM
Technical Manual
&
User Manual
Polyaire™ Pty Ltd
11-13 White Road
GEPPS CROSS
South Australia, 5094
Tel: (08) 8349 8466
Fax: (08) 8349 8446
www.polyaire.com.au
www.zonemaster.com.au
2008 EDITION

IMPORTANT INSTALLERS NOTE
The Installer MUST be familiar with the features of the VAV and the installation
process BEFORE INSTALLATION COMMENCES.
Zonemaster/Polyaire does not take responsibility for poorly designed or
installed VAV systems. Neither will we take responsibility for customer
complaints due to poor design and installation. We strongly suggest that any
installer wishing to install a Zonemaster VAV system should fully acquaint
himself with the design features and capabilities of the system before
commencing the job , either by reading the installation manual thoroughly
or consulting with a Polyaire staff member conversant with this system
(Preferably both). Contact Polyaire re VAV installation training.
INSTALLATION TIPS & COMMON PROBLEMS
1. TheVAVpowertransformer(s)arettedwith3pinplugsandshouldbe
pluggedin to their own power point separate from the A/C unit.
DONOTremovetheplugandhardwiretheVAVtotheA/Cpowersupplyas
thewideuctuationsintheA/CcurrentwilldamagetheVAVunit.
2. Don’tgetconfusedbetweenDataandControlCables.
Thepackagesareclearlymarked.DataCablehasleftlatchedplugsand
Controlcablehascentrelatchedplugs
3. Alwayscheckcables:Particularlyifmakingupyourowncables.Cablesand
plugscansometimesgettwistedorbefaulty,thewiresandcontactsarevery
small. To ensure that all cables are ok pre- test with Zonemaster Cable Tester
(AvailablefromPolyaire).Thiswillhelpeliminatefaultsbefore(ratherthan
after) installation.
4. Donottapeoverthebuttonatthebottomofthedamperbladewhenattaching
exibleduct.Thisiseasytodoandwillstopthedamperturningfreely.
5. All zones MUST have their own unique address allocated via the touchpad.
IE:Ifthereare6zonesthesystemmusthave6addresses.
6. Donotplug2touchpadsintoone3wayplug.
7. VAVsystemsshouldonlybettedtoFlexibleductwithlargeenoughdiameter
toeasilytaketherequiredvolumeofair.Smallductcreatesexcessivenoise
andvortexdraughtsanddoesn’tallowthesystemtoregulateproperly.
8. ReturnAirGrillesshouldbepositionedinthesamespaceasthedesignated
“Spill”zonetoensuretheVAVsensorcanoperateproperly.
9. Substantialdifferencesinzonetemperaturewillonlybeachievedinseparate
zonesiftheseareeffectivelyseparatedfromotherzones.IEDoorsmustbe
closedtopreventcrossowfromroomtoroom.
10. Theendusershouldbefullyinformedontheunitattimeofcommissioningso
thattheyfullyunderstandtheoperationoftheVAVunit.Theendusershould
beencouragedtoreadtheusermanual.

CONTENTS
Features 1
Application 1
Components 2
Conguration 3
Installation 5
BypassControl 7
Commissioning 8
1.InitiatingandExitSettingProcess 8
2. Initialisation of Touchpad Address 9
3.RoomTemperatureSensor 9
4. Minimum Ventilation 10
5.SupplyAirSafetyHigh&LowLimits-MasterTouchpad 10
6.Spill/BypassAirSetpoint-MasterTouchpad 11
7.NamingZones-MasterTouchpad 12
8. Damper on/off Test 12
InstallationInformationSheet 13
TroubleShootingGuide 15
User Manual 16
1.ZoneTouchpad 16
2. Master Touchpad 17
3.ProgrammingMode 18
AppendixA-TechnicalSpecications 25
AppendixB-StandardCongurationofVAVSystem 27
Liability
Please read the instructions carefully before installing this
Zonemaster VAV Climate Control System. Polyaire Pty Ltd does
not accept any responsibility for loss or damage that may occur
as a result of the incorrect installation of this system.

FEATURES
• Manualandtimeprogrammablezonetemperaturecontrol.
• Supportsupto16zones.
• Addressofeachzoneissetdirectlyfromthetouchpad.
• Maintainsroomtemperaturewithin±1°Cusinganonboardsensor.
• LCDindicatorforzonestatusandparameterdisplay.
• User-friendlytemperatureandprogramsetting.
• Realtimeclockwithbatterybackup.
• 5-1-1programmabletemperaturesettingpointandstarttime.
• Personalisedzonelabelling.
• Autospill/bypass---thedesignatedzones/bypassareforced
open when all zones are turned off.
• Safetysystem---Opensalldampersifthesupplyair
temperatureislessthanlowlimitormorethanhighlimit.
• Allzonesautomaticallyreturntotheiroriginalon/offstateonce
power up.
APPLICATION
TheZonemasterVAV(VariableAirVolume)isafullyfeaturedsystem
designedtoaccuratelymanageairowbyzoneinDuctedreversecycle,
heatingandevaporativeairconditioningsystems.
ItmanagesairowfromtheA/Cunitbyassessingtemperaturesineach
zoneandopeningandclosingdamperstoincreaseordecreaseairowto
achieve and maintain a preset temperature in that zone.
The temperature difference that the Zonemaster can achieve will not be
lower(cooling)orhigher(heating)thanthetemperaturesetbytheACunit.
Page 1

COMPONENTS
1) Main Controller
The main controller collects and processes all the information.
2) Master Touchpad
6buttontouchpad.
Toprogramandcontrolallthezonesinthesystem.
3) Zone Touchpad
3buttontouchpad.
4) Bypass Damper and Controller (optional) Green
Dampercontrollerreceivesbypasscontrolsignalfromthe
maincontrollertoopenorclosethebypassdamper.
5) Supply Air Sensor
Supplyairsensormeasuresthetemperatureofthesupplyair.
6) Power Supply
The24VACtransformerprovidespowertotherst8touchpads
- dampers and main controller.
7) Battery
3.6Vrechargeablebatteryformaincontroller.
8) LeftLatchedDoubleAdaptor&CableKit
Double adaptor connects the main controller/touchpads via the
data bus.
9) CentreLatchedTripleAdaptor&CableKit
Tripleadaptorconnectsthe24VACpowersupplyviathe
control bus.
10)MountingBracket
For the touchpads.
Page 2

Page 3
Figure1.MainControllerConnectionDiagram
ZonemasterVAVisaserialbusbasedsystemwhichhasaControlbusand
Data bus. The Control bus provides 24VAC power for up to 8 Dampers
viathemaincontrollerasshowninFig2.
Figure2.WiringdiagramofZone1toZone8
CONFIGURATION
Main controller collects and processes all the information. The connections
tothemaincontrollerareshowninFigure1.

Page 4
The Data bus provides communication between the main controller and
the touchpads.
NOTE:TheMainControllerprovidespowerforupto8Touchpadsand
damper motors. If more than 8 touchpads and dampers are installed
auxiliarypowermustbeprovidedviaseparate24VACand9VDCpower
suppliesasshowningure3.
Figure3.WiringdiagramofZone9toZone16

Page 5
INSTALLATION
1) Removethe3coversfromthemaincontrolboard.
2) Position the main controller on top of the fan coil unit or on the
supplyairductandsecure.
3) Connectthe24VACpowersupplytotheterminalsN+Lonthemain
controllerboard.Whenturningonthepower,theredLEDwill
illuminatetoshowthatthemaincontrollerisready.
3) Mountthesupplyairsensorinthesupplyairductupstreamfromthe
motoriseddampers.Plugthesensorintothesocketonthemain
controller board.
4) Connectthebatterybypluggingintothesocketonthemain
controller board.
5) Use two pre-tested data cables to connect the main controller
(touchpad 1-8 socket) and a touchpad via a double left latched
adaptor,asshowninFigure2.TheLCDonthe
touchpadshouldshowtheclockaftersettinga
unique address to the touchpad. (Refer to the
commissioningsection)Otherwise,checkthe
connection and the cables.
SENSORSOCKET
TOUCHPAD 1-8
TOUCHPAD 9-16
LED
24 VAC
VAV DAMPERS
BYPASS DAMPER
BATTERY CONNECTOR
BATTERY

6) Repeat step 5) to connect all the
touchpadsaccordingtoFigure2and3.
Makesureeverytouchpadisworking
correctlybycheckingtheclockandthe
temperaturedisplayedonthetouchpad.
7) Plugacontrolcableintothe‘VAV’socket
on the main board and the other end into
the‘24VacIN’portonatripleadaptor.
Plugthetripleadaptorintothemotorised
damper closest to the main board.
Warning - Only yellow Polyaire™
Dampers are compatible with the
system.
8) Useanothercontrolcabletopluginto
‘24VacOUT’portonthetripleadaptor
andtheotherendofthecableto‘24Vac
IN’portontheotheradaptorforthenext
motorised damper.
9) Follow Step 8) to connect all motorised
dampersinseriesasshowninFigure2.
10) Plugoneendofacontrolcableintothe
‘touchpad’socketonthetripleadaptor
and the other end into the socket on
the back of the touchpad.
11) Follow step 10) to connect all the
dampersandtouchpadstogether
asshowninFigure2.
Page 6

Page 7
12) Turn off the power and disconnect
the touchpad.
13) Positionthetouchpadattheright
place.Ideally,itspositionshould
beapproximately1.6metresoff
theooronthewall.Fitthedata
cableandthecontrolcablethrough
thewallcavityandconnectto
thetouchpadagain.Mountthe
touchpad onto the bracket in the
wallcavity.
Please note that the touchpad should not be
exposedtodirectsunlightandotherheat
sources.
13) Applythepoweragaintothetransformer.The
LCD should show clock time and temperature
wherethetouchpadislocatedaftershowing
‘initiate’onthesecondlineforabout15
seconds.
BYPASS CONTROL
1) Ifbypasscontrolischosenforthe
system,mountthegreendamper
controlleronthetopofagreen
motoriseddamperandplugthe
bridgecablein.

Page 8
2) Take off the small cover on the top of the
damper controller and set a special address
forthebypassdampercontroller.
3) Use a pre-tested control cable to
connectthebypassdamper
controllertothe‘point’socketonthe
main controller board. Make sure
theredlightonthedampercontroller
ison.Otherwise,checkthecableand
the connection.
COMMISSIONING
TheZonemasterVAVsystemhasseveralparametersthatmustbesetin
thecommissioningstage.
Zonetouchpad(3button)canonlysetthreezoneparameters:
1) Touchpad Address
2) Temperature Sensor
3) Minimum Ventilation
Mastertouchpad(6button)cansettheaboveparametersandthree
systemparameterslistedbelow:
1) SupplyAirSafetyHigh&LowLimits
2) SpillBypass/AirSetpoint
3) NamingZones
1.InitiatingandExitSettingProcess
1) Holddownbothandbuttonsforabout
5secondsuntiltheLCDdisplays‘Setting’onthe
top line of the LCD screen.

2) Forzonetouchpads,pressingbuttonafter
thesettingofallthreeparameterswillreturntothe
normal operation mode.
3) For the master touchpad,pressingbutton
will return to the normal operation mode.
2.InitialisationofTouchpadAddress
Each touchpad (zone) must have a unique address
from1to16tobeidentiedbythemaincontroller.
Thetouchpadhasafactorydefaultof‘Noaddr’that
cannotbeidentiedbythemaincontroller.
Thetouchpadneedstobeinitiatedbyallocating
a unique address. The allocation can be carried
outbypressingorbutton,andthen
pushing(zonetouchpad)or
(master touchpad) button.
Please note that each touchpad (zone) must have
auniqueaddress.Thesameaddressforanyoftwo
touchpads will cause communications problem
between the main controller and touchpads, and
thetouchpadLCDshows‘CheckAddress’
3. Room Temperature Sensor
Each touchpad has an onboard sensor to measure the temperature of
the room for temperature control. The sensor can be calibrated to provide
more accurate temperature control.
1) Usinganaccurateprobetomeasurethe
temperature of the area user wants to calibrate
and record the value.
Page 9

Page 10
2) Atthesettingmode,press(zone
touchpad) or (master touchpad) button
untiltheLCDdisplaysthe‘Sensor’screen
3) Press or button to adjust the
displayedvaluetotherecordedvalue.
4. Minimum Ventilation
Customersmaypreferminimumventilationduringtheclimatecontrol.
Thisventilationallowsaminimumairowintothezonethatisswitchedon.
Theamountofventilationcanbesetfrom0to30%openwithadefault
of0%.
1) Atthesettingmode,press(zone
touchpad) or (master touchpad) button
untiltheLCDdisplaysthe‘MinVent’screen.
2) Press or button to adjust the
percent value of the minimum ventilation as
desired.
5.SupplyAirSafetyHigh&LowLimits-MasterTouchpad
Forsafetyreasons,thesystemmonitorsthesupply
airtemperatureclosely.Ifthetemperaturemoves
outsideofthelimits,alldampersinthesystemare
forcedopenandtheLCDdisplays‘Safety’
onscreen.Thefactorydefaultsofsupplyairsafety
high&lowlimitsare60°Cand5°Crespectivelyand
thesafetycontrolisdisabled.
1) Atthesettingmode,pressbuttonuntil
theLCDdisplaysthe‘H_limit’screen.
2) Pressorbuttontochangethe
highlimittothedesiredvalue.Theadjustable
rangeofthehighlimitisfrom45°Cto75°C

3) Pressbuttononceagain,theLCD
screenwilldisplaythe‘L_Limit’.
4) Pressorbuttontochangethe
low limit to the desired value. The adjustable
rangeofthelowlimitisfrom0°Cto15°C.
Ifthecustomerdoesnotwantthesafety
function,thesafetyH-limitandL-limit
MUSTbedisabledbypressingbutton
duringthesetup.
Spill or Bypass Modes
A‘Spill’or“Bypass”functionisdesignedtorelievepressureintheductif
toomanyzoneshavebeenturnedoff.
Spill Mode
TheVAVsystemhasaninbuilt“Spill”systemthatwillautomaticallyopen
ventsiftoomanyhaveinadvertentlybeenclosed.Thepresetfactory
defaultis30%ofthetotalnumberofzones.ThePresetFactorydefault
canbevariedbutwerecommend30%asthelowestsafevaluetoprotect
theduct.InSpillmodethezoneswiththelowestaddressesinthesystem
areautomaticallyopenedifthetotalnumberofopenzonesislessthanthe
assignedspillsetpoint.(IE:Ifthesystemhas10zonesnumbered1-10
andallhavebeenclosedtheVAVwillautomaticallyopenzones1,2,3to
relievethepressure.Theonlywaytoclosethese“spill”zonesistomake
sureatleast3otherzonesareopen.
Bypass Mode
Thealternativewaytorelievepressureintheductistoinstallaductfrom
theA/Coutletviaamotorizeddampertothereturnairduct.Thissystem
shouldonlybeusedwherethespillfunctionisconsideredunsatisfactory.
InBypassmode,aspecicdamperisusedtoreturntheairdirectlytothe
return air duct if the total number of zones open is less than the setpoint.
Thebypassdamperiscontrolledbyaspecicdampercontrollerwithits
own unique address.
Note:EnsurethattheAirConUnitReturnAirSensorispositionedinthe
returnairductbetweentheBypassductandtheunitsothatitcanregister
theairfromthebypassduct.
Page 11

Page 12
7.NamingZones-MasterTouchpad
Thenameofazoneiscalled‘Zone_addr’.Forexample,zone1,which
hasanaddressof1,iscalled‘Zone_1’onitsfactorydefault.Thenames
canbecustomisedasfollows:
1) Atthesettingmode,pressbuttonuntil
theLCDdisplaysthe‘Spill’or‘Bypass’screen.
2) Pressbuttontoselectspillorbypassmode.
3) Pressorbuttontochangethe
spill/bypasssetpointtoitsdesiredvalue.
Theadjustablerangeisfrom0%to50%.
Werecommendasettingof30%ormoreto
safeguardDuct.Ifnospillorbypasscontrolis
required in the system, the setpoint MUST be
setto0%.
1) Atthesettingmode,pressbuttonuntil
theLCDdisplaystherstzonename,for
example‘Z1Name’onthetoplineoftheLCD.
The second line shows the current name of
zone 1.
2) Press or button to select one of
the preset zone names for the zone. There are
26presetnamesinthelist.
3) Tomakechangestothepresetselectedname,
press button to move to the character
thatisashing.
4) Use or button to select the
characterfromthelistasdesired.Thereare26
lettersincapitalandnormalcase,10numbers
and a space in the list.
5) Pressbuttontoselectthenextzone
namingscreenandfollowsteps2to4to
customise the name of the zone.
8. Damperon/offTest
1) Switch on the air conditioner.
2) Press button to turn a zone on or off to check if the damper is
correctlyconnectedbyfeelingtheairattheoutlet.RefertoUser’s
manual for the operation.

Page 13
INSTALLATION INFORMATION SHEET
Thefollowingzonetableisdesignedtoassistinstallationand
commissioning.
Address DefaultName Zone Name Program
1 Zone_1
2 Zone_2
3 Zone_3
4 Zone_4
5 Zone_5
6 Zone_6
7 Zone_7
8 Zone_8

Page 14
Please note the following:
Zone name is the actual name of the zone, for example; lounge, kitchen,
bedroom etc.
Spill zones should be assigned lower addresses, and they should be
located near return air grilles.
Parameter Default Custom Value
Address No addr
Sensor
Min Vent 0%
Highlimit Disable/
60oC
Low limit Disable/
5oC
Spill Spill/
30%

TROUBLE SHOOTING GUIDE
Problem SuggestedAction
Touchpad has
nothingshownon
LCD.
• Disconnect the data cable from the touchpad
immediately.
• Check if the cable is crossed over with the
Zonemaster Cable Tester.
•Checkthepowersupply.
LCD shows the
touchpad address.
• Check the cables and the connection of the
data bus.
LCD shows
‘CheckAddress’. • Check addresses for all touchpads.
Touchpaddisplayis
not normal.
•Resetthetouchpadbydisconnectingthedata
cableandthenpluggingitinagain.
•Resetthemaincontrollerbyturningoffpower
supplyandturningonagain.
Dampers have no
response when
turned on or off.
• Check the control cable between the touchpad
and the damper.
•Checkthe24VACpowersupply.
Temperature is
beyond±1°Crange.
•AirConditionerdoesnothaveenoughcapacity
for the area at the particular moment.
•Toomuchaircomingfromotherareas.
Pleasecontactdistributorsforanyother
problems not listed as above.
Page 15

Page 16
USER MANUAL
Touchpad Layout
TheMastertouchpadhasaLCDwithsixbuttons,whereastheZone
touchpadhasaLCDscreenwithonlythreebuttons,asshowninFigure5.
Innormaldisplaymode,theLCDscreenswilldisplayclocktimeandtheir
local zone temperatures.
Figure5.LayoutofMasterandZoneTouchpads
Master Touchpad Zone Touchpad
Zone Touchpad
ZoneOn/OffControl
1) In‘on’status,theLCDofthetouchpaddisplays
zonetemperatureorsetpoint.Pressing
button once will turn off the zone and the
secondlineofthescreenwilldisplay‘off’.
2) In‘off’status,pressingbuttononcewill
turn on the zone and the second line of the
LCDscreenwilldisplaythesetpointofthe
zonefor20seconds,andthenwillreturntothe
normaldisplayofthezonetemperature.

ZoneTemperatureSetting
1) In‘on’status,pressorbutton
once to allow the setpoint of the zone to be
displayedonthesecondlineoftheLCD.
2) Pressorbuttonagaintoadjust
the setpoint to the desired value.
3) The screen will return to zone temperature
displayin20secondswithnokeybeing
pressed.
Master Touchpad
ZoneOn/OffControlandTemperatureSetting
Master touchpad controls the temperature of the zone where it is located
besidesitsfunctionofsettingotherzonestemperatures.Itsoperationfor
on/offcontrolandtemperaturesettingarethesameasthezonetouchpad
described in above section.
All Zone Browse
1) Amastertouchpadcanbrowsethroughallthe
zonesbypressingbutton.Whenazone
hasbeenselected,thezone’snameandits
setpointor‘off’statusareshownontheLCD
screen.
2) Inbrowsemode,pressingbuttononce
will turn the selected zone on or off.
3) Whenaselectedzoneisin‘on’status,press
or button to adjust the setpoint to
the desired value for the zone.
4) Pressbuttonagain,usercanselectnext
zonefortemperaturesettingoron/offcontrol.
Page 17
Table of contents
Other Polyaire Temperature Controllers manuals
Popular Temperature Controllers manuals by other brands

RedWave Labs
RedWave Labs LTC25 operating manual

La Crosse Technology
La Crosse Technology TX141TH-Bv3 quick start guide

Nobile
Nobile 9108011010 Mounting Operation Instruction

Crestron
Crestron C2N-RTHS Operations & installation guide

Warmworld
Warmworld Dataterm IHC user guide

Auber Instruments
Auber Instruments WS Series Operation & instruction manual