2 | EN
This heat pump contains a ammable refrigerant R32.
Any acon on the refrigerant circuit is prohibited without a valid authorisaon.
Before working on the refrigerant circuit, the following precauons are necessary for safe
work.
1. Work procedure
The work must be carried out according to a controlled procedure, in order to minimise the risk of presence of
ammable gases or vapours during the execuon of the works.
2. General work area
All persons in the area must be informed of the nature of the work in progress. Avoid working in a conned area. The
area around the work area should be divided, secured and special aenon should be paid to nearby sources of ame
or heat.
3. Vericaon of the presence of refrigerant
The area should be checked with a suitable refrigerant detector before and during work to ensure that there is no
potenally ammable gas. Make sure that the leak detecon equipment used is suitable for ammable refrigerants, i.e.
it does not produce sparks, is properly sealed or has internal safety.
4. Presence of re exnguisher
If hot work is to be performed on the refrigeraon equipment or any associated part, appropriate re exnguishing
equipment must be available. Install a dry powder or CO2 re exnguisher near the work area.
5. No source of ame, heat or spark
It is totally forbidden to use a source of heat, ame or spark in the direct vicinity of one or more parts or pipes contai-
ning or having contained a ammable refrigerant. All sources of ignion, including smoking, must be suciently far
from the place of installaon, repair, removal and disposal, during which me a ammable refrigerant may be released
into the surrounding area. Before starng work, the environment of the equipment should be checked to ensure that
there is no risk of ammability. «No smoking» signs must be posted.
6. Venlated area
Make sure the area is in the open air or is properly venlated before working on the system or performing hot work.
Some venlaon must be maintained during the duraon of the work.
7. Controls of refrigeraon equipment
When electrical components are replaced, they must be suitable for the intended purpose and the appropriate speci-
caons. Only the parts of the manufacturer can be used. If in doubt, consult the technical service of the manufacturer.
The following controls should be applied to installaons using ammable refrigerants:
• The size of the load is in accordance with the size of the room in which the rooms containing the refrigerant are
installed.
• Venlaon and air vents work properly and are not obstructed.
• If an indirect refrigeraon circuit is used, the secondary circuit must also be checked.
• The marking on the equipment remains visible and legible. Illegible marks and signs must be corrected.
• Refrigeraon pipes or components are installed in a posion where they are unlikely to be exposed to a substance
that could corrode components containing refrigerant.
8. Vericaon of electrical appliances
Repair and maintenance of electrical components must include inial safety checks and component inspecon
procedures. If there is a defect that could compromise safety, no power supply should be connected to the circuit unl
the problem is resolved.
9. Inial security checks must include:
• That the capacitors are discharged: this must be done in a safe way to avoid the possibility of sparks.
• No electrical components or wiring are exposed during loading, recovery or purging of the refrigerant gas system.
• There is connuity of grounding.
WARNING