1.3.1. Related Documents
Installation of air heaters must be in accordance with the
relevant requirements of:
BS 5410: Part 2: 1978 Code of Practice for Oil Firing
Installations of 45kW and Above
The Building Regulations
The I.E.E. Regulations
It should also be in accordance with relevant require-
ments of the local authority and fire authority, in addition
the following British Standard Codes of Practice must be
observed CP.3 Ch IV Precautions Against Fire Part 2
Shops and Departmental Stores Part 3 Office Buildings.
OFTEC Technical Book 3: Domestic & Commercial
requirements for oil storage and supply equipment.
OFTEC Technical Book 4: Oil fired appliances & system
installation requirements.
OFTEC Easy Guides to non domestic oil feed pipes and
oil storage.
1.3.2 Location
The location chosen for the air heater must permit the
provision of a satisfactory flue system and an adequate air
supply. The location must also facilitate ease of servicing
and satisfactory air circulation around the heater.
The air heater must be installed strictly in accordance with
any fire regulations or insurance company's requirements
appertaining to the area in which the heater is located,
particularly where special risks are involved such as areas
where petrol vehicles are housed, cellulose spraying
areas, and wood working departments etc.
The air heater must be installed either:
(a) suspended by chains or straps of adequate strength to
safely carry the weight of the unit and ancillary equipment
or
(b) On specifically designed cantilever brackets from a
non-combustible wall or
(c) On a level non-combustible surface which is capable
of adequately supporting the weight of the air heater and
any ancillary equipment.
The heater must not be installed in conditions for which it
is not specifically designed e.g. highly corrosive atmo-
spheres, vitiated atmospheres, or where adverse wind
conditions may be experienced. Where the location of the
heater is such that it might suffer external mechanical
damage e.g. from overhead cranes, fork lift trucks etc. it
must be suitably protected. Any ducting should be kept as
short and direct as possible having regard to the distribu-
tion of the heated air.
Any combustible material adjacent to the heater and flue
systems must be so placed as to ensure that its tempera-
ture does not exceed 65°C (150°F).
1.3.3 Main Storage Tank and fittings
Construction and installation should be in accordance
with:
(a) BS 5410 Part 2 Section 6
(b) BS 799 Part 5
(c) BS 1563
The latter three standards apply to cast iron sectional,
mild steel sectional, and mild steel welded tanks respec-
tively and therefore must be applied appropriately.
1.3.4 Service Tanks and fittings
1.3.4.1 Construction
These should be designed and constructed in accor-
dance with BS 799 Part 5
1.3.4.2. Installation
The installation should be in accordance with:- BS 5410
Part 2.
In addition the service tank installation must comply with
local regulations and by-laws and with the requirements
of insurance companies
1.3.5 One Pipe System (Storage to
burner)
1.3.5.1 General
Refer also to the detail provided in the burner handbook
regarding pipe sizing. These must be generally in accor-
dance with B S 799 Part 3 and BS 5410 Part 2.
Particular attention is drawn to the following:
a) Pipe jointing compounds must be capable of withstand-
ing the solvent action of the fuel oil under all operating
temperatures and pressures. Jointing compounds
containing oil shall not be used. Hemp and other fibrous
materials shall not be used as packing for screwed joints.
b) Soft solder copper tube fittings and galvanised pipes
and fittings must not be used.
c) Oil lines must be completely air-tight.
d) The pump suction must not exceed a maximum of 0.4
bar (30cm Hg). Beyond this limit gas may be released
from the oil.
1.3.5.2 Single Pipe System - Gravity
Feed
Warning: The burners are supplied adjusted for a single
pipe system. If the burner is to be used on a twin pipe
system the Internal bypass plug of the burner oil pump
must be fitted. Refer to the burner instruction booklet.
Ideally the return pipe should terminate within the oil tank
at the same level as the suction line, both being below the
minimum oil level.
1.3.6 Fire Valve
It is recommended that the fire valves should be installed
as follows:
1. Main storage to service tank supply (if applicable)
2. Main storage to burner supply
3. Service tank to burner supply (if applicable)
Fire valves should be installed generally in accordance
with the requirements of BS 799: Part 5. The fire valve
should be situated in an easily accessible position as near
the tank as possible and where practicable within the
boundary of the tank chamber or catchpit retaining wall.
1.3.7 Flue System
The flue system should generally be in accordance with
BS 5410 Part 2.
Materials used for the flue system should be mechanically
robust, resistant to internal and external corrosion,
non-combustible and durable under the conditions to
which they are likely to be subjected. Prevention of
condensation within the flue should be an important factor
in the design of the flue system. In order to minimise
condensation the use of double walled flue pipe or insula-
tion is recommended.
Where condensation in the flue is unavoidable, or rain
ingress is possible, provision must be made for a conden-
sate drain connected to a suitable drain or gully. The
condensation pipe from the flue to the disposal point
should be of non-corrodible material of not less than
22mm (¾ in) size.
Facilities should be provided for disconnecting the flue
pipe from the air heater for inspection and servicing
purposes. Bends with removable covers should be fitted
for inspection and cleaning purposes where considered
appropriate.
The flue should terminate in a freely exposed position and
must be situated such that products of combustion do not
enter any opening in a building in such concentration as
to constitute a health hazard.
1.3.8 Combustion & Ventilation Air
Supply
Where the air heater is to be installed in the space to be
heated it requires the space containing it to have a perma-
nent air vent direct to outside air. The air vent should have
negligible resistance and must not be sited in any position
where it is likely to be easily blocked or flooded, neither
should it be positioned adjacent to an extraction system
carrying flammable vapour.
The air supply requirement that follows is related to the
maximum rated heat input of the heater, or heaters if more
than one is installed in the same space.
Total Input Rating Air Vent Area
of Air Heaters (Air direct-from outside)
Up to 60kW 4.5 cm²/kW in excess of 7kW
From 60kW up to 730kW 4.5 cm²/kW
Where the air heater is to be installed in a plant room, the
heater requires the plant room housing it to have perma-
nent air vents communicating directly with the outside air,
at high and low level. Where communication with the
outside air is possible only by means of high level air
vents, ducting down to floor level for the lower vents
should be used. Air vents should have negligible resis-
tance and must not be sited in any position where they are
likely to be easily blocked or flooded, neither should they
be positioned adjacent to any extraction system carrying
flammable vapour.
Grilles or louvers should be so designed that high velocity
air streams do not occur within the plant room.
The air supply requirements stated below are related to
the maximum rated heat input of the air heater(s). The
minimum free area requirements of the air vents is given
below.
Total Input Rating Position of Air Vent Areas
of Air Heater(s) Vents (Air direct from
outside)
Up to 730kW High Level 4.5cm²/kW
Low Level 9.0 cm²/kW
1.3.9 Air Distribution System
Where single OUH units are required to cover a large floor
area, and in buildings with high roof or ceiling heights
Calecon thermal economiser units should be fitted to
ensure even heat distribution and minimise stratification.
Care should be taken to avoid impeding the air throw with
racking, partitions, plant or machinery etc. Various outlet
configurations are available as optional extras to modify
the air throw pattern to suit particular site conditions.
For ducted units all delivery and return air ducts, including
air filters, jointing and any insulation or lining must be
constructed entirely of materials which will not contribute
to a fire, are of adequate strength and dimensionally
stable for the maximum internal and external tempera-
tures to which they are to be exposed during commission-
ing and normal operation.
Where inter-joist spaces are used as duct routes they
should be suitably lined with a fire-resisting material.
A full and unobstructed return air path to the air heater(s)
must be provided.
If the air heater(s) is installed in a plant room the return air
intake(s) and the warm air outlet(s) from the heater(s)
must be fully ducted, into and out of the plant room to
avoid interference with the operation of the heater.
The openings in the structure of the plant room through
which the ducting passes must be fire stopped.
Care must be taken to ensure that return-air intakes are
kept clear of sources of smells and fumes, and where
there is any possibility of pollution of the air by dust, shav-
ings etc., precautions must be taken to prevent contami-
nation.
If necessary suitable barrier rails should be provided to
prevent any combustible material being placed within
900mm of the outlets.
1.3.10 Electrical Supply
Wiring external to the air heater must be installed in accor-
dance with the I.E.E. Regulations for Electrical Installa-
tions and any local regulations which apply.
All standard heaters are supplied by 230V - 1ph, 50Hz.
The method of connection to the main electricity supply
must:-
- facilitate the complete electrical isolation of the unit(s)
- be in a readily accessible position adjacent to the unit(s)
- serve only the unit(s)
- have a contact separation of at least 3mm in all poles.
See the accompanying wiring diagram for the heater
electrical connections
OUH units can also be supplied for 400V 3N, 50Hz.
OUH Range Users, Instrucons & Service Instrucons Issue 5.1 September 2015 Page 11
2.1 Fitting the Unit
2.1.1 General
The air heater will be delivered to site pallet mounted and
protected by plastic sheeting.
Whichever method of mounting the air heater is used the
following minimum clearances for installation and servic-
ing must be observed:
Right-hand side (looking at front of heater) 0.5m
Left-hand side (looking at front of heater) 0.5m
Top of burner to ceiling 1.0m
Rear of heater to nearest wall 0.4m
In order to achieve the desired performance levels it is
recommended that the installation height (floor level to
base of unit) for OUH20 and OUH30 is between 2.5m
and 3.0m, and OUH45 and OUH60 is between 3.0m and
5.0m.
If the heater is to be base mounted it may be stood direct-
ly on the platform, provided it is of a suitable non-combus-
tible material and does not extend past the front edge of
the heater.
For multi-heater installations the following minimum
distances between units must be observed.
Between units, side to side 3.0m
Between units, back to back 3.0m
2.1.2 Fitting the Air Heater
The air heater may be installed either:
(a) Suspended by steel chains, rods or straps.
(b) On specifically designed cantilever brackets from a
non-combustible wall.
(c) On a level non-combustible surface providing the
platform does not extend past the front edge of the heater.
Whatever method of installation is used it must be capa-
ble of adequately supporting the weight of the unit (See
Table 2) and allowance must be made for any ancillary
equipment. Before installing the heater any existing truss-
es, walls brackets etc. must be inspected to ensure they
are suitable. All supports should be protected against
corrosion.
If noise levels are of particular importance, the heater
should be isolated from the structure of the building by
installing it on suitable anti-vibration mountings.
In all such cases, and in addition, when the heater is
suspended it is essential that all oil, duct, electrical and
flue connections to the heater are made with flexible
connections to maintain continuity of connection. In the
case of the flue connection single wall stainless steel flue
is deemed to flex sufficiently to meet the requirements.
2.1.3 Connection of Air Heater(s) to
Flue System
The flue system connects directly into the flue socket on
the top (OUH20) or rear (OUH30 - 60) of the heater. The
socket is sized to accept standard sheet metal flue that is
secured in place using suitable fasteners.
The flue system must be fabricated with sockets facing
upwards and sound joints must be achieved by either:
(a) a close tolerance mechanical fit between sections, or
(b) the use of a suitable caulking string and cold caulking
compound.
2.1.3.1. General Requirements
In all cases the flue outlet socket must be connected via
an approved flue system to outside air. . If an offset is
required two sets of 45° bends may be used each set
being equivalent to 0.5m of flue length. The minimum flue
length (end of flue terminal to top of heater) shall not be
less than 2.0m.
All flue ducts must be supported independently of the air
heater.
The flue terminal must not be installed so as to be less
than:
- 300mm below an opening e.g. window, air brick etc.
- 200mm below eaves or gutter.
- 300mm from an internal or external corner.
- 1200mm from a surface facing the terminal.
- 1500mm vertically from another terminal on the same
wall.
- 300mm horizontally from another terminal on the same
wall.
- 2000mm from ground level.
2.1.4 Condensate Drainage
The design of the flue system should minimise the forma-
tion of condensation and long external runs should be
completed in twin wall insulated flue. Where condensate
and/or rain water ingress is envisaged to be a problem a
flue drain length or condensate drain tee that drains into a
gulley must be fitted.
2.1.5 Oil Connection
The oil pipework length and diameter should be in accor-
dance with the information given in the burner instruction
booklet.
The pump suction should not exceed 0.4 bar.
The oil line must terminate not more than 450mm from the
burner with the final connection by the flexible hoses
supplied with the burner.
Because the burner is at high level it is recommended that
a non-return valve is fitted adjacent to the burner to
prevent oil draining back when the burner is not operating.
2.1.6 Electrical Connections
All units are fully prewired and only require final connec-
tion of the incoming mains supply and completion of the
control circuit (230V) via a room thermostat, time clock
etc.
All units must be earthed. The electrical supply must be
run to a point adjacent to the heater and be suitably termi-
nated to provide an isolation point that will prevent remote
activation of the unit during servicing. See Table 3 (Page
3) to ascertain the electrical loading of the unit(s) so that
cables of adequate cross-sectional area are used for the
electrical installation. The length of the conductors
between the cord anchorage and the terminals must be
such that the current carrying conductors become taut
before the earth conductor if the cable or cord slips out of
the cord anchorage. All external controls must be of an
approved type.
See the wiring diagram in Section 8.
OUH/D models supplied less fan must be electrically
interlocked to the air movement system so that this is
started in the same manner as the air heater fan would be
viz. A connection from the heater terminal marked “Live
Main Fan” must be made to one side of the fan motor
contactor coil, the other side of the coil being connected to
Neutral. The fan motor electrical supply must be direct
and not taken from the internal wiring of the OUH heater.