Primex CW6CDC User manual

User Manual
CW6CDC
CONTROLLER
WWW.PRIMEXCONTROLS.COM
CW6CDC
844-4PRIMEX (844-477-4639)
WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER

PRIMEX®1 CW6CDC Level Controller User Manual
WWW.PRIMEXCONTROLS.COM
TABLE OF CONTENTS
REVISION B • Firmware Revision B2.02
Introduction......................................................................................................................................2
Warnings .................................................................................................................................................3
Installation & Dimension Data...............................................................................4-5
Electrical Connections ......................................................................................................6
Function Keys / Displays...................................................................................................7
Setting Up Levels and Simulation ...................................................................8-9
Configuration ...........................................................................................................................9-11
Configuration Mode Parameters .................................................................. 12
Run Mode Parameters..................................................................................................... 13
Specifications...............................................................................................................................14
Warranty ............................................................................................................................................ 15
Notes.......................................................................................................................................................... 16
WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER

PRIMEX®2 CW6CDC Level Controller User Manual
The CW6CDC level controller is a simple, easy-to-use microprocessor-
based controller capable of monitoring any 4-20 mA signal. It has six
programmable relay outputs that can be used for control and alarm.
The transducer input zero and span are fully configurable. A simulation
mode allows the user to test set-points and relay operation.
CW6CDC LEVEL CONTROLLER INTRODUCTION
The standard CW6CDC level controller kit contains (see Figure 2 on
page 5 of this manual):
• one CW6CDC level controller
• two mounting brackets for panel mounting
• a three pin power supply connector block (P1)
• a 18 pin relay output connector block (P2)
• a five pin transducer connector block (P3)
CW6CDC

PRIMEX®3 CW6CDC Level Controller User Manual
Failure to read and understand the information provided in this manual may result in personal
injury or death, damage to the product or product failure. Please read each section in its
entirety and be sure you understand the information provided in the section and related
sections before attempting any of the procedures or operations given.
Failure to follow these precautions could result in serious injury or death.
Keep these instructions with warranty after installation. This product must be
installed in accordance with National Electrical Code, ANSI/NFPA 70 so as to
prevent moisture from entering or accumulating within the controller housing.
See additional specifications on page 14 of this manual.
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing this product.
A qualified service person must install and service this product
according to applicable electrical codes.
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable liquids. Do not install in
hazardous locations as defined by National Electrical Code,
ANSI/NFPA 70.
• Do not install in area with: excessive or conductive dust, corrosive or
flammable gas, moisture or rain, excessive heat, regular impact shocks
or excessive vibration.
• Do not place in water or let water leak onto the controller.
• Do not allow debris to fall inside the unit during installation.
• Double-check all the wiring before turning on the power supply.
• Do not touch live wires.
• Stay as far as possible from high-voltage cables and power equipment.
• Leave a minimum of 10 mm space for ventilation between the top and
bottom edges of the controller and enclosure walls.
WARNINGS

PRIMEX®4 CW6CDC Level Controller User Manual
SIDE VIEW
CW6CDC
FIGURE 1 Dimensions and panel cut-out. Dimensions are indicative and may be subject to change without notification.
INSTALLATION & DIMENSIONAL DATA

PRIMEX®5 CW6CDC Level Controller User Manual
FIGURE 2 Standard CW6CDC level controller kit.
INSTALLATION & DIMENSIONAL DATA

PRIMEX®6 CW6CDC Level Controller User Manual
1. POWER (Terminal P1)
Connect power to terminal 1 and 2: the unit requires 24 VDC (+/- 10%).
2. TRANSDUCER (Terminal P3)
For loop powered transducers (2 wire) connect power conductor to terminal
1 and 2. If the cable is protected with an overall shield, connect the shield
to terminal (3). Terminal 4 and 5 must be connected if an output follower is
not required. If no valid input is present, the controller will display SENSOR
and all outputs will be de-energized.
NOTE: To avoid ground loops, the shield of the signal cable must only be
grounded at one end.
3. OUTPUT RELAY CONNECTIONS
The relay outputs are rated up to 10 A (resistive) at 240 VAC, fuse
protection is required individually or as a group.
FIGURE 3 Wiring diagram, back
view - with a submersible pressure
transducer.
ELECTRICAL CONNECTIONS

PRIMEX®7 CW6CDC Level Controller User Manual
LEFT AND RIGHT ARROW KEYS
are used to navigate through the menu items. These
arrow keys can also be used to back out when in editing
and simulation mode.
ENTER KEY
is used for selecting a menu item for editing. This key is
also used after a value has been edited to store in memory.
UP AND DOWN ARROW KEYS
is used to increase or decrease the current value being
edited.
NOTE: The display automatically returns to “level” after 20 seconds of
inactivity, regardless of where it was left.
Pressing once will increment the current value by one unit. Pressing and
holding will begin repeatedly incrementing after a short delay. If the
operator continues to hold the key, the value continues to increment at a
faster rate.
lSET POINTS
6 programmable set
points status LED. Form
C (SPDT)
contacts: rated at
10A at 240 VAC.
CW6CDC
lLEVEL
DISPLAY
Eight character alpha-
numeric LED for
process value display
and program
parameters.
lKEYPAD
Arrow keys are
used to navigate
through the
configuration and
used for adjusting
set points.
lBAR GRAPH
20 segment bar
graph display for
process value.
Each bar
represents 5%
of full scale.
FUNCTION KEYS / DISPLAYS

PRIMEX®8 CW6CDC Level Controller User Manual
SETTING UP LEVELS AND SIMULATION
LEVEL DISPLAY
FLASHING
STORE
SELECT
EDIT
Continued on next page...
FIGURE 4 Example of how to move from the level display screen
through each set-point and to change set-point 2.

PRIMEX®9 CW6CDC Level Controller User Manual
LEVEL DISPLAY
The adjustable ON and OFF function allows for an individual hysteresis or
differential setting of each set-point. For an emptying application, the ON set-
point must be greater than the OFF set-point. For a filling application, the ON
set-point must be less than the OFF set-point (Refer to FIGUIRE 5).
NOTE: For proper operation of the CW6CDC controller, the ON and OFF
set-points must not be set to the same value.
FIGURE 5
...Continued from previous page
FLASHING

PRIMEX®10 CW6CDC Level Controller User Manual
CONFIGURATION
To enter the configuration mode, simultaneously press the LEFT and RIGHT
arrow key and hold for three (3) seconds with the unit powered ON.
NOTE: Eight (8) seconds of inactivity (no keys pressed) will terminate the
configuration menu and exit back to the run menu.
The first item in the configuration menu is the UNITS selection. Use the LEFT or
RIGHT arrow keys to navigate through all the items in this menu.
UNITS Select the unit of measure display after the process value.
FT = Feet
IN = Inches
CM = Centimeters
%= Percentage
oC= Degrees Celsius
oF= Degrees Fahrenheit
PS = Pound Per Square Inch (PSI)
BR = Bar
NONE = Blank, No Units Displayed
When you are at the item you wish to edit, press the ENTER key and the original
value for the item selected will flash. Use the UP and DOWN arrow keys to change
to your desired value and press ENTER.
NOTE: The edited value will not be saved until the ENTER key is pressed.
4 mA Set the value displayed when the signal value is equal to 4 mA (zero).
The default value is zero.
20 mA Set the value displayed when the signal value is equal to 20 mA (span).
The default value is 10.0.
BAR MIN This value set the level for which all bars on the bar graph will turn OFF.
BAR MAX This value set the level for which all bars on the bar graph will turn ON.
OFFSET An offset value can be added or subtracted to bring the display value to
zero at atmospheric pressure. If you are using a submersible pressure transducer,
the level readout at atmospheric pressure (out of the wet well) should be zero. If it
is not, add or subtract (negative) a value to bring the display to zero. Check the
level readout to verify it is zero. If not, try changing the offset again.

PRIMEX®11 CW6CDC Level Controller User Manual
FIGURE 6 Use the right or left arrow keys to navigate through these menu items. Begin with
UNITS, 4 mA, 20 mA, BAR MIN, BAR MAX, OFFSET, and back to UNITS.
NOTE: Eight (8) seconds of inactivity (no keys pressed) will terminate the
configuration menu and exit back to the run menu.
LEVEL DISPLAY
HOLD BOTH ARROW KEYS FOR 3 SECONDS

PRIMEX®12 CW6CDC Level Controller User Manual
MIN MAX DEFAULT USER
OOOUNITS FT
OOOO4OMA 0.0 999.9 0.0 FT
OOO20OMA 0.0 999.9 10.0 FT
OBAROMIN 0.0 999.9 0.0 FT
OBAROMAX 0.0 999.9 10.0 FT
OOOFFSET -9.9 9.9 0.0 FT
CONFIGURATION MODE PARAMETERS
NOTES
FT, IN, CM, %, oC, oF, PS, BR, (NONE)

PRIMEX®13 CW6CDC Level Controller User Manual
USER USER
MIN MAX DEFAULT FUNCTION VALUE
-99.9 999.9
OOSP1OON 0.0 999.9 1.5 FT
OSP1OOFF 0.0 999.9 1.0 FT
OOSP2OON 0.0 999.9 2.5 FT
OSP2OOFF 0.0 999.9 2.0 FT
OOSP3OON 0.0 999.9 4.5 FT
OSP3OOFF 0.0 999.9 4.0 FT
OOSP4OON 0.0 999.9 6.5 FT
OSP4OOFF 0.0 999.9 6.0 FT
OOSP5OON 0.0 999.9 8.5 FT
OSP5OOFF 0.0 999.9 8.0 FT
OOSP6OON 0.0 999.9 9.5 FT
OSP6OOFF 0.0 999.9 9.0 FT
SIMULATE
RUN MODE PARAMETERS
LEVEL
DISPLAY
4 mA value in
configuration
20 mA value in
configuration
SENSOR on invalid input signal

PRIMEX®14 CW6CDC Level Controller User Manual
INPUT TYPE
4-20 mA signal.
INPUT IMPEDANCE
100 ohms.
INPUT RESOLUTION
12 - bits, 0.1% of full scale.
SAMPLING CYCLE TIME
100 mS.
AVERAGING
8 consecutive samples.
ACCURACY
0.5% of full scale.
EXCITATION VOLTAGE
24 VDC, 30 mA available for loop powered transducers.
RELAY OUTPUTS
Six programmable relay outputs with LED indication. “Form C” (SPDT) contacts: rated at 10A
at 240 VAC.
LEVEL DISPLAY
Eight character alpha-numeric LED for process value and program parameters. The display is
SunBrite grade, sharp and clear, even in direct sunlight from 10 feet away.
POWER
24 VDC (+/- 10%). 200 mA nominal, 400 mA max.
OPERATING TEMPERATURE
-15oC to 70oC (0oF to 150oF) at up to 0-90% RH non-condensing.
ENCLOSURE RATING
Front Panel: IEC Standard IP54 (with additional gasket) for indoor use.
Rear Case: IEC Standard IP20.
BAR GRAPH
20 segment bar graph display for process value. Each bar represents 5% of full scale.
SPECIFICATIONS

PN 1024820D 10/20
© 2015 SJE, Inc. All Rights Reserved.
PRIMEX
is a trademark of SJE Inc.
WWW.PRIMEXCONTROLS.COM
WATER SYSTEM INTEGRATOR AND CONTROLS PROVIDER
+1-844-4PRIMEX (477-4639)
Table of contents
Other Primex Controllers manuals
Popular Controllers manuals by other brands

Festo
Festo SPC11 Series Supplementary manual

SANKI
SANKI P212 instruction manual

Precision Digital Corporation
Precision Digital Corporation Helios PD2-6210 instruction manual

oventrop
oventrop Hycocon DTZ Installation and operating instructions

PI
PI P-841.1 user manual

S.R.Smith
S.R.Smith WPC2 T Series installation instructions