Technician Setup Menu Technician Setup Menu
Select GAS to have the system
control the fan during a call for
heat, select Electric to have the
thermostat control the fan during
a call for heat.
Note: If heat pump is set to“ON”this
step will not show, and will default
to ELECTRIC.
Electric or Gas
Fan Operation
Use and buttons to
change the setting.
Tech Setup Steps
Stages of
Cool
Adjustment Options Default
LCD Will Show
FAN SET
GAS
Tech Setup Steps Adjustment Options DefaultLCD Will Show
Technician Setup MenuTechnician Setup Menu
GAS
System Set
Use the or buttons
until the desired application
is ashing. AUTO = (Auto
Changeover) OFF
SYSTEM SET
AutoO
Em.Heat
Cool
You can congure the system
switch for the particular
application. Heat - O - Cool,
Heat - O, Cool - O, Heat - O -
Cool – Auto.
Note: Emergency Heat is available
in heat pump mode only.
Dual Fuel
Auxiliary For
Heat Pump OFF
This setting allows the system
to run Gas, Oil, Propane or any
other types of auxiliary heat. The
thermostat will default to electric
auxiliary heat in heat pump
applications.
OF
DUAL FUEL
Use the and buttons
to select ON/OFF.
2C
COOL
STAGES
2C
This setting allows you to select
the number of cool stages.
Use the and buttons
to select 1C, 2C.
This feature allows the thermostat
to keep multiple stages of heat or
cool energized until the setpoint
is satised.
Satisfy
Setpoint
Staging
(Only displayed
if there are more
than one stage of
heat or cool)
Use the or buttons
to turn on of o.
SS STAGING
OF
This feature allows a delay to
occur if an additional stage is
needed.This allows the previous
stage extra time to satisfy the
setpoint.
Note:Will not show if using
outdoor sensor with balance point
temperature.
Staging
Delay
(Only displayed
if there are more
than one stage of
heat or cool)
Use the or key to
select OFF, 5, 10, 15, 30, 45,
60, or 90 minutes.
STAGING
DELAY
OF
This feature allows the installer
to select the minimum run
time for the compressor. For
example, a setting of 4 will force
the compressor to run for at
least 4 minutes every time the
compressor turns on, regardless of
the room temperature.
Minimum
Compressor
On Time
You can set the minimum
compressor run time to
“OFF”,“3”, “4”, or “5”minutes.
If 3, 4 or 5 is selected, the
compressor will run for at
least the selected time
before turning o. Use the
and buttons to
change the setting.
MIN COMP ON
OF OFF
OFF
OFF
The compressor short cycle delay
protects the compressor from
“short cycling”. This feature will
not altlow the compressor to be
turned on for 5 minutes after it
was last turned o.
Compressor
Short Cycle
Delay ON
Selecting “ON”will not allow
the compressor to be turned
on for 5 minutes after the
last time the compressor was
on. Select “OFF”to remove
this delay. Use the and
buttons to change the
setting.
Cooling Fan
Delay
The cooling fan delay setting will
delay the fan from coming on in
cool mode and keep it running
after the compressor shuts o
for a short time to save energy in
some systems.
You can set the cooling fan
delay to OFF, 15, 30, 60 or 90
seconds. If 15, 30, 60, or 90
is selected the fan will not
turn on for that many seconds
when there is a call for cool
and will run for that many
seconds after satisfying a call
for cool.
OFF
COMP DELAY
COOL FAN DL
OF
This feature allows you to set a
minimum cooling setpoint limit.
The setpoint temperature cannot
be lowered below this value.
Cool
Setpoint
Limit
Use the or key to
select the minimum cooling
setpoint.
COOL LIMIT
CO 44˚F
This feature allows you to display
temperatures in either Fahrenheit
or Celsius.
˚F or ˚C
˚F for Fahrenheit
˚C for Celsius ˚F
F OR C SET
F
o
You can select either a 12 or 24
hour clock setting.
12 or 24
Hour Clock
Use the or key to
select 12 or 24 hour clock. 12H
CLOCK SET
12
Tech Setup Steps Adjustment Options Default
LCD Will Show
The pre-occupancy fan settings
will energize the fan before the
occupied time to provide ventila-
tion prior to scheduled occupancy
time periods. This feature only
shows if the technician setup step
for time periods is set to 2C or 4C.
Use the and buttons to
adjust.
Pre
Occupancy
Fan
You can select the
pre-occupancy fan from OFF,
1, 2, or 3 hours. If 1, 2, or 3
is selected, the fan will turn
on that many hours prior to
the scheduled occupied time
period. OFF
PRE-OCC FAN
OF
The display light can be
congured to stay on all the
time or turn on when any key
is pressed. There are LOW and
HIGH selections for continuous ON
selection.
NOTE: The thermostat will need to be
hardwired in order for the LOW and
HIGH display light functions to work
properly. “ALWAYS ON LIT”will alter-
nate in the text eld with“HARDWIRE
ONLY”when HIGH is selected. These
prompts will alternate every three
seconds.
If the thermostat is hardwired
this feature will default to LOW.
Display
Light
Use the and buttons
to select OFF, LOW, or HIGH.
OFF congures the display
light to come on when the
light key or any button is
pressed.
LOW congures the display
light to stay on at a low
intensity constantly. When a
button is pressed, the display
light will transition to high
intensity.
HIGH congures the display
light to remain on at high
intensity all the time.
ALWAYS ON LIT
dL OFF
HARDWIRE ONLY
dL LOW
If
Hardwired
If Battery
Powered
This feature allows you to put
your phone number in the
display. You can choose ON or
OFF.
Notes:
If contractor call number is selected
ON, the phone number entered will
show in the display if there has been a
continuous call for heating or cooling
for 24 hours or if the light button is
held down for 3 seconds.To remove
the phone number from the display,
hold the light button down for 3
seconds.
Contractor
Call Number
If selected ON, you will see
the input screen after
pressing NEXT STEP. Use the
or button to select
the desired number and
the FAN or SYSTEM key to
move from one character to
another. See note below for
operation. OFF
OF
PHONE NUMBER
Tech Setup Steps Adjustment Options Default
LCD Will Show
This feature will congure the
fan to run a selected number of
cycles per hour. Note:This mode
can be enabled or disabled at
anytime during normal operation
by selecting IAQ mode with the
fan key. Turning this feature on
shows IAQ option in fan key.
Notes:
This programmable/selectable mode
will operate the fan 1-4 cycles per
hour, 1-45 minutes per cycle. Once
programmed in tech setup, to enable
this mode select“IAQ”with the fan
key. Disable this mode by selecting
“ON”or“AUTO”with the fan key.
IAQ Mode
Cycle
Select OFF, 1, 2, 3 or 4 with the
or buttons. This sets
the number of cycles per hour
that the IAQ fan mode will
operate.
OFF
IAQ MODE CYCL
OF
Contractor Call Number Note
If contractor call number is selected ON, the phone number entered will
show in the display if there has been a continuous call for heating or
cooling for 24 hours or if the light button is held down for 3 seconds. To
remove the phone number from the display, hold the light button down
for 3 seconds.
This feature allows fresh air
into a unit for a selectable time
period.When Fresh Air Mode is
enabled, the fan and the fresh air
damper terminal will energize
simultaneously.
Fresh Air
Mode
(This setting cannot
be used with PTAC,
three stages of
cool, or economizer
turned on)
OFF
FRESH AIR
OF
Use the and buttons to
select OFF, OC ON or ON.
OFF:Thermostat does not
enable Fresh Air Mode.
OC ON: Fresh Air Mode is
enabled during the OCCUPIED,
WAKE, RETURN, and SLEEP
time periods (It will not bring
in fresh air during UNOCCUPIED
and LEAVE time periods).
ON:Thermostat will enable
Fresh Air Mode for every time
periods.