ProFlow PF-OXY1 User manual

© 2016erie watertreatment TM-EN-PF-OXY-Rev2016.08
Technical Manual
WATER FILTER - Fe, Mn, H2S
Models:
PF-OXY1
PF-OXY+1
PF-OXY1,5
PF-OXY+1,5

TABLE OF CONTENT & INSTALLATION RECORD
Page 2
Table of content & Installation record..................................................................................Page 2
Warning & Safety instructions..............................................................................................Page 3
Operating conditions & Requirements.................................................................................Page 4
Assembly..............................................................................................................................Page 6
Installation...........................................................................................................................Page 8
Commissioning.....................................................................................................................Page 9
Electronic control panel.......................................................................................................Page 10
Maintenance........................................................................................................................Page 13
Troubleshooting...................................................................................................................Page 14
Electrical wiring diagrams ....................................................................................................Page 16
Default configuration parametersettings.............................................................................Page 17
Composition overview .........................................................................................................Page 18
Exploded view - PF-OXY1 & PF-OXY+1 - System ....................................................................Page 20
Exploded view - PF-OXY1 & PF-OXY+1 - Timer assembly.......................................................Page 22
Exploded view - PF-OXY1 & PF-OXY+1 - Valve body...............................................................Page 24
Exploded view - PF-OXY1,5 & PF-OXY+1,5 -System...............................................................Page 26
Exploded view - PF-OXY1,5 & PF-OXY+1,5 - Timer assembly..................................................Page 28
Exploded view - PF-OXY1,5 & PF-OXY+1,5 - Valve body.........................................................Page 30
Exploded view - PF-OXY1,5 & PF-OXY+1,5 - Piston assembly.................................................Page 32
Technical data - PF-OXY1 & PF-OXY+1...................................................................................Page 33
Technical data - PF-OXY1,5 & PF-OXY+1,5.............................................................................Page 34

WARNING & SAFETY INSTRUCTIONS
Page 3
Before you begin the installation of the appliance, we advise you read
andcarefully follow the instructions contained in this manual. It contains
importantinformationaboutsafety,installation,useandmaintenanceof
the product. The actual system that you have received, may differ from
the pictures/illustrations/descriptions in these Instructions.
Failure to follow the instructions could cause personal injury or damage
to the appliance or property. Only when installed, commissioned and
servicedcorrectly,theappliancewilloffer you manyyears oftrouble-free
operation.
The appliance is intended to ‘filter’ the water, meaning it will remove
specific undesired substances; it will not necessarily remove other
contaminants present in the water. The appliance will not purify polluted
water or make it safe to drink!
Installation of the appliance should only be undertaken by a competent
person, aware of the local codes in force. All plumbing and electrical
connections must be done in accordance with local codes.
Before setting up the appliance, make sure to check it for any externally
visible damage; do not install or use when damaged.
Use a hand truck to transport the appliance. To prevent accident or
injury, do not hoist the appliance over your shoulder. Do not lay the
appliance on its side.
Keep these Instructions in a safe place and ensure that new users are
familiar with the content.
The appliance is designed and manufactured in accordance with current
safety requirements and regulations. Incorrect repairs can result in
unforeseen danger for the user, for which the manufacturer cannot be
held responsible. Therefore repairs should only be undertaken by a
competent technician, familiar and trained for this product.
In respect of the environment, this appliance should be disposed of in
accordance with Waste Electrical and Electronic Equipment
requirements.Refertonational/locallawsandcodesforcorrectrecycling
of this appliance.

OPERATING CONDITIONS & REQUIREMENTS
Page 4
APPLICATION LIMITATIONS PF-OXY:
pH: for Iron removal: 6,8 - 9,0
for Manganese removal: 8,0 - 9,0
for Iron & Manganese removal: 8,0 - 8,5
maximum contaminant content:
Iron (Fe2+) 15 mg/L
Manganese (Mn2+) 2 mg/L
Hydrogen Sulfide (H2S) 5 mg/L
organic matter: max. 4,0 mg/L; higher level may hinder the correct operation of
the system.
chlorine: max. 1,0 mg/L
iron bacteria: if iron bacteria are present, frequent service may be necessary,
while the life of the system may be limited; by properly controlling the iron
bacteria with chlorine or another approved method of bacterial reduction, the
system will function properly.
APPLICATION LIMITATIONS PF-OXY+:
pH: 5,8 - 10,5
maximum contaminant content:
Iron (Fe2+) 70 mg/L
Manganese (Mn2+) 35 mg/L
Hydrogen Sulfide (H2S) 15 mg/L
organic matter: water should be free from organic matter.
iron bacteria: if iron bacteria are present, frequent service may be necessary,
while the life of the system may be limited; by properly controlling the iron
bacteria with chlorine or another approved method of bacterial reduction, the
system will function properly.
OPERATING PRESSURE MIN-MAX: 2,5-8,0 bar / 36-116 psi
low operating pressure may lead to insufficient backwash of the filter media,
resulting in an increase in pressure drop and/or a reduction of the filtration
capacity during the service cycle.
if installed on a well, verify that the well pump is powerful enough to provide
sufficient flow rate for the backwash cycle.
check water pressure regularly.
takeintoaccountthatnighttimewaterpressuremaybeconsiderablyhigherthan
day time water pressure.
install a pressure reducer ahead of the appliance if necessary.
OPERATING TEMPERATURE MIN-MAX: 4-48 °C / 39-120 °F
donot installthe applianceinanenvironment wherehighambienttemperatures
(e.g. unvented boiler house) or freezing temperatures can occur.
the appliance cannot be exposed to outdoorelements,such as direct sunlight or
atmospheric precipitation.
do not install the appliance too close to a water heater; keep at least 3 m (10 ft)
of piping between the outlet of the appliance and the inlet of the water heater;

OPERATING CONDITIONS & REQUIREMENTS
Page 5
water heaters can sometimes transmit heat back down the cold pipe into the
appliance; always install a check valve at the outlet of the appliance.
ELECTRICAL CONNECTION:
this appliance only works on 24 VAC; always use it in combination with the
supplied transformer.
in case of damage to the power supply cable of the transformer, immediately
disconnectthe transformer fromthe power outlet and replace the transformer.
make sure to plug the transformer into a power outlet, which is installed in a dry
location, with the proper rating and over-current protection.

ASSEMBLY
Page 6
CONTENT CHECK
Actualpartsthatyouhave received,maydifferfromthe
pictures/illustrations in these Instructions!
Only on systems with ≥3 cuft of filter media: for ease of
transportation and installation, the filter media is NOT
loaded in the pressure tank, but delivered in separate bags
of 1 cuft; it must be loaded on-site, after positioning of the
pressuretank.
Check the content of the system, using the Composition
Overview in these Instructions. Identify and lay-out the
different components to facilitate the assembly.
SIMPLEX
Picture 1.a, 2.a, 3.a
A Simplex system consists of 1 single filter module (pressure
tank, filter media, control valve).
Duringnormaloperation,the system deliverstreatedwater.
As soon as it initiates a regeneration, it automatically goes
into bypass, guaranteeing uninterrupted supply of untreated
water.
It ispossibletoinstall aso calledNormallyOpenService Valve
(e.g.asolenoidoperateddiaphragmvalve)intheoutletofthe
system, that is controlled by the electronic timer of the
system; this Service Valve will be activated during the entire
duration of the regeneration, to close-off the control valve's
standard 'untreated water bypass during regeneration'.
MULTIPLEX PARALLEL
Picture 4
A Multiplex PARALLEL system consists of 2 or more Simplex
systems, that:
-are hydraulically installedin parallel;
-are programmed for different times of regeneration;
-may have aso called Normally Open Service Valve (e.g. a
solenoid operated diaphragm valve) in the outlet of each
Simplex system, that is controlled by the electronic timer
of each Simplex system; this Service Valve will be
activated during the entire duration of the regeneration,
to close-off thecontrolvalve's standard 'untreated water
bypass during regeneration'.
During normal operation, all Simplex systemsare in service,
doubling/tripling/… the service flowrate!
In case of a power failure, all Service Valves will be
deactivated, meaningtheoutlet of allSimplexsystemswill be
open, guaranteeing uninterrupted supply of water.
FILTER MEDIA LOADING
1. Move the pressure tank to the correct installation
location; position it on a flat and level surface. Make sure
to leave enough space for ease of service.
2. Position the riser assembly upright and centred in the
pressure tank; plug the top of the riser tube with a piece
of tapeor cleanrag, toprevent filter media fromentering
the tube.
3. Place a funnel on the pressure tank opening and fill the
pressure tank with filter media; make sure the riser
assembly remains centered in the pressure tank.
4. Rinse the pressure tank opening to remove any grains of
filter media from the threaded section.
5. Unplug the top of the riser tube.
CONTROL VALVE
only for PF-OXY1 & PF-OXY+1
1. Make sure the O-ring in the riser insert and the tank O-
ring(aroundthethreadedsectionofthecontrolvalve)are
in the correct position.
2. Screw the top distributor onto the control valve.
3. Lubricate the threaded section of the pressure tank, the
top of the riser tube and the tank O-ring of the control
valve; use a silicon-based lubricant.
4. Lowerthecontrolvalvestraightdownontotherisertube,
until the riser tube is correctly inserted in the riser insert;
then push it down firmly and screw it onto the pressure
tank.
only for PF-OXY1,5 & PF-OXY+1,5
Picture 5
1. On the brass valve seat:
makesuretheO-ringintheriserinsertisinthecorrect
position;
install the top distributor and fix it by means of the 2
stainless steel screws;
install the tank O-ring in the groove on the flange
around the threaded section.
2. Lubricate the threaded section of the pressure tank, the
top oftherisertube andthetank O-ring of the valve seat;
use a silicon-based lubricant.
3. Lower the valve seat straight down onto the riser tube,
until the riser tube is correctly inserted in the riser insert
inside the valve seat; then push it downfirmly and screw
it onto the pressure tank.
4. Install the valve seat O-ring in the groove on the valve
seat.
5. Install the control valve onto the valve seat; mind the
alignment pin!
6. Bolt the control valve tothe valveseat by means of the 4
stainless steel bolts; tighten firmly.

ASSEMBLY
Page 7
AIR INJECTION SYSTEM
only for PF-OXY1 & PF-OXY+1
Picture 6.a
Make sure the air injection system is installed in vertical
position, with the check valve and air intake filter screen
pointing upwards. Rotate it to this position if necessary.
only for PF-OXY1,5 & PF-OXY+1,5
Picture 6.b
1. Install the air injection systemon the control valve;
tighten the nut firmly by hand.

INSTALLATION
Page 8
INLET & OUTLET
We strongly recommend the use of flexible hoses to
connect the appliance to the water distribution system; use
hoses with a large diameter in order to limit the pressure
loss.
We strongly recommend the installation of a bypass
system (not included with this product!) to isolate the
appliance from the water distribution system in case of
repairs.Itallowstoturnoffthewatertotheappliance,while
maintaining full-flow(untreated) water supply to theuser.
To prevent air from escaping from the compressed air
chamber, make sure the inlet line runs vertically upwards
into the water filter. If this is not possible, install a check
valve in the inlet line.
only for PF-OXY1 & PF-OXY+1:
with factory bypass (optional)
Picture 1
= mains water supply (untreated water)
= inlet of control valve(untreated water)
= outlet of control valve (treated water)
= application (treated water)
1. Screw the factory bypass onto the in/out ports on the
control valve (&); make sure to install the gasket
seals. Tighten the nuts firmly by hand.
2. Screw the connection kit with nuts onto the factory
bypass (&); make sure to install the gasket seals.
Tighten the nuts firmly by hand.
3. Connect the mains water supply to the adaptor on the
inlet port of the factory bypass ().
4. Connect the application to the adaptor on the outlet port
of the factory bypass ().
only for PF-OXY1 & PF-OXY+1:
with 3-valveconnection kit (not included)
Picture 2
= inlet of control valve (untreated water)
= outlet of control valve (treated water)
1. Install the 3-valve connection kit.
2. Screw the connection kit with nuts onto the in/out ports
on the control valve (&); make sure to install the
gasket seals. Tighten the nuts firmly by hand.
3. Connect the IN valve of the 3-valve connection kit to the
adaptoron the inport of the control valve().
4. ConnecttheOUTvalveofthe3-valveconnectionkittothe
adaptor on the out port of the control valve ().
5. Connectthemainswatersupplytotheinletofthe3-valve
connection kit.
6. Connect the application to the outlet of the 3-valve
connection kit.
only for PF-OXY1,5 & PF-OXY+1,5:
with 3-valveconnection kit (not incl.)
Picture 3
= inlet of control valve (untreated water)
= outlet of control valve (treated water)
1. Install the 3-valve connection kit.
2. Inserttheadaptorsinthein/outportsonthecontrolvalve
(&); make surenot todamagethe O-rings. Install the
nuts and tighten them firmly by hand.
3. Connect the IN valve of the 3-valve connection kit to the
adaptor on the in port of the control valve ().
4. ConnecttheOUTvalveofthe3-valveconnectionkittothe
adaptor on the out port of the control valve ().
5. Connectthemainswatersupplytotheinletofthe3-valve
connection kit.
6. Connect the application to the outlet of the 3-valve
connection kit.
DRAIN
We recommend the use of a stand pipe with air trap.
To prevent backflow from thesewerage system into the
appliance, always install and use an air gap (included with
PF-OXY1 & PF-OXY1+), to connect the drain hose to the
sewerage system.
Lay-out the drain hose in such a way that pressure loss
is minimized; avoid kinks and unnecessary elevations.
Make sure that the sewerage system is suitable for the
rinse water flow rateof the appliance.
only for PF-OXY1 & PF-OXY+1
Picture 7
1. Install the air gap to the sewerage system; it fits over a
32 mm pipe or inside a 40 mm pipe adaptor. Ensure a
permanent and watertight connection.
2. Connect a 13 mm hose to the drain connection of the
control valve (); secure it by means of a clamp.
3. Run the drain hose to the air gap and connect it to one of
the hose barbs; secure it by means of a clamp. This drain
lineoperatesunderpressure,soitmaybeinstalledhigher
than the appliance.
only for PF-OXY1,5 & PF-OXY+1,5:
Picture 8
1. Connectapipetothe1”BSPMaledrainconnectionofthe
control valve (); use an appropriate sealant.
2. Run the pipe to the sewerage system and connect it,
ensuring sufficient air gap between the end of the pipe
and the sewerage system. This drain line operates under
pressure,soit may beinstalled higher than the appliance.
SERVICE VALVE (optional)
Picture 9
1. Plug the DIN plug on the connection cable of the Service
Valve into the DIN socket at the back of the electronic
timer head of the control valve ().

COMMISSIONING
Page 9
ELECTRICAL
1. Connect the appliances power cord to the transformers
output.
2. Plug the transformer into an electrical outlet.
PRESSURIZING
1. Put the bypass system in 'bypass' position.
2. Make sure the electronic controller of the appliance is in
service mode.
3. Open the mains water supply.
4. Open a cold treated water faucet nearby the appliance
and let the water run for a few minutes until all air is
purged and all foreign material that may have resulted
from the installation is washed out; close the faucet.
5. Gently pressurizethe appliance, byputting it into service:
close the 'BYPASS' valve;
open the 'OUT' valve;
slowly open the 'IN' valve.
6. After 2-3 minutes, open a cold treated water faucet
nearby the appliance and let the water run for a few
minutesuntilallairispurgedfromtheinstallationandthe
filter media is rinsed (it is normal for the rinse water to
show some discoloration!); let the water run until the
rinse water is clear; close the faucet.
7. Check the appliance and all hydraulic connections for
leaks.
During the passage through the compressed air
chamber,the treated water will get highlyoxygenated. As a
consequence it may becomeslightly non-transparent (milky
appearance) when it flows from the tap into a glass. This is
totallyharmlessfor the qualityof thetreated water and will
disappear rapidly if thewater is left standing for a moment!
ELECTRONIC CONTROL PANEL
1. Program the electronic controller.
INITIATE A REGENERATION
We strongly recommend to postpone the execution of
this 'start-up' regeneration by 24 hours. The filter media
needs sufficient time to absorb water and reach its normal
service weight. If the regeneration is performed too soon,
the filter media may be pushed against the top distributor
duringthe backwash cycle, possiblyresulting in loss of filter
mediaor damageto the top distributor.
1. Manually initiate a regeneration, by pressing the scroll
button repeatedly until the display shows:
2. Leave the appliance in this position; the count-down
timer will count down to 0 sec and start a regeneration.
Regen in 10 sec

ELECTRONIC CONTROL PANEL
Page 10
Picture 10
symbol
button
function
SCROLL
to advance to the next
parameter
UP
to increase the value of the
parameter
DOWN
to decrease the value of the
parameter
POWER-UP
After power-up the display will show the installed software
version. After 5 seconds it will automatically revert back to
the service display.
POWER FAILURE
In the event of a power failure, the program will remain
stored in the NOVRAM®duringan undefined period, while an
incorporated SuperCap will maintain the correct time of day
during a period of several hours; consequently, in case of
prolonged power failure, the time of day might not be
maintained; if this happens, the time of day will be reset to
8:00 when the power supply is re-established, while the
indication will flash, indicating that the time of day needs to
be set.
When the power failure occurs during the execution of an
automatic regeneration, the control valve will remain in its
last position; when the power supply is re-established, the
control valve will return to the service position, stay there for
60 sec. and restart a complete regeneration from the
beginning.
TIMER FAILURE
In the event of a timer failure, the display will show the
message:
If powering off/on the appliance doesn’t solve this problem,
professional service is required.
SERVICE MODE
In service mode the display shows the time of day and the
number of days remaining until the next regeneration:
REGENERATION MODE
In regeneration mode the display shows the remaining
regeneration time and the remaining cycle time:
The control valve can be reset to service modeat any timeby
pressing the scroll button, as such manually advancing it
through the regeneration cycles.
MANUAL REGENERATION
It is possible to manually initiate a regeneration.
1. Press the scroll button repeatedly until the display
shows:
If the control valve is left in this position, the count-
down timer will count down to 0 sec and start a
regeneration.
To cancel this mode, press the scrollbuttonbefore
the countdown timer has reached 0 sec; the control
valve will return to the service mode.
2. Press the scroll button again if you want to manually
advance the control valve to the next regeneration cycle.
DRIVE MOTOR SPEED
(only for PF-OXY1 & PF-OXY+1)
The drive motor of the control valve, that drives the valve
body to its different regeneration positions, will start-up at
low speed to reduce its noise level. To increase the speed of
the drive motor, simply press the scroll button as soon as
the drive motoris activated.
Service Required
Regen in 10 sec
8:01 4 DAY REM
Rgn:123 CycY:456

ELECTRONIC CONTROL PANEL
Page 11
PROGRAMMING INSTRUCTIONS -
BASIC SETTINGS
Beforeenteringtheprogrammingmode,makesurethat
the appliance is in the service mode.
1. Press the scroll button; the display will show:
Press the up or down button to set the
language.
2. Press the scroll button again; the display will show:
Press the up button or down button to set the
time of day.
3. Press the scroll button again; the display will show:
Press the up ordown button to set the number
of days between regenerations.
The filtration capacity of the appliance mainly depends
on the daily water usage and the Iron/Manganese content
in the water; many otherfactors mayalso have a significant
impact on the filtration capacity. Therefore it is
recommendedtoregeneratetheapplianceona regulartime
basis. In most applications a regeneration every 4 days
should besufficient.
In case of extreme iron/manganese content and/or
water consumption, it is recommended to lower the
regeneration interval to 1 or max. 2 days.
Language:English
Set time: 8:01
Interval:4 Days

ELECTRONIC CONTROL PANEL
Page 12
PROGRAMMING INSTRUCTIONS -
CONFIGURATION PARAMETERS
Beforeenteringtheprogrammingmode,makesurethat
the appliance is in the service mode.
All configuration parameters on this appliance have
been pre-programmed in the factory, to offer optimal
performance in a wide range of applications and situations.
Neverthelessitmaybenecessaryordesirableto changeany
of these parameters, to further optimize the appliances
performance or to adapt it to the specific requirements of
the installation.
1. Press the scroll button and hold it for 5 sec until the
displayshows:
2. Within 10 sec, press the up button; the display will
show:
Press the up or down button to set the length
of the regeneration cycle.
Pressthescrollbuttonagaintoadvancetothenext
regeneration cycle.
Cycle 1
Backwash
Cycle 2
Air intake
Cycle 3
Fast rinse
Cycle 4
No function
(PF
-
OXY
1,5
& PF
-
OXY1,5
+
)
3. Press the scroll button again; the display will show:
Press the up or down button to set the time of
regeneration.
4. Press the scroll button again; the display will show:
Press the up or down button to save the
program into the NOVRAM® and exit the
programming level.
Cycle 1: XX min
System Check
Regen @ 0:00
Exit

MAINTENANCE
Page 13
ROUTINE CHECKS
Regularlytheusershouldperformabasicchecktoverifyifthe
appliance is functioning correctly, on the basis of the
following control points:
1. Check settings of electronic control panel.
2. Check water composition before/after appliance.
3. Check drain line from control valve; there shouldn’t be
any water flow(unless appliance is in regeneration).
4. Checkapplianceandsurroundingarea;thereshouldn’tbe
any water leakages.
BYPASSING THE APPLIANCE
Occasionally it may be necessary to put the appliance
hydraulically in bypass, i.e. to isolate it from the water
distribution system; f.e.:
in case of an urgent technical problem;
when it is not necessary to supply treated water to the
application.
WITH FACTORY BYPASS (optional) (only for PF-OXY1 & PF-
OXY+1)
Picture 11.a
SERVICE POSITION
= inlet valve to appliance is OPEN
= outlet valve from appliance is OPEN
Picture 11.b
BYPASSPOSITION
= inlet valve to appliance is CLOSED
= outlet valve from appliance is CLOSED
Picture 11.c
MAINTENANCE POSITION
= inlet valve to appliance is OPEN
= outlet valve from appliance is CLOSED
SANITIZING THE APPLIANCE
This appliance is manufactured from premium quality
material and assembled in safeconditions to assureit is clean
and sanitary. If installed andserviced correctly, this appliance
willnotinfectorcontaminateyourwatersupply.However,as
in any 'device' plumbed-in in your water distribution system,
a proliferation of bacteria is possible, especially in case of
'stagnant water'. Therefore this appliance will automatically
rinse the filter media periodically.
If the power supply to the appliance is disconnected for a
longer period of time, we recommend, when the power
supply is re-established, to manually initiate a complete
regeneration.

TROUBLESHOOTING
Page 14
PROBLEM
C
AUSE
S
OLUTION
U
ntreated
water to
service
Open or defective bypass
C
lose
orreplace
bypass
A
ppliance
in regeneration
Wait until regeneration finishes or
manually
advance regeneration to end
Excessive water usage
Initiate regeneration manually
Change in raw water
composition
Verify
composition
of
i
ncoming
untreated
water
and adjust regeneration frequency accordingly
Appliance
fails to
start a
regenerat
ion
Refer to problem “Appliance fails to start a
regeneration”
Appliance
fails to backwash properly
Refer to problem “
Appliance
fails to
backwash
properly”
PF
-
OXY
1
&PF
-
OXY
+
1
only
: valve body andtimer
out of synchronisation
Synchronize valve body and timer
Decreasing
filter
capacityof
filter media
Clean or replace filter media
Loss of
filtermedia
Refer to problem “Loss of
filtermedia
”
Leak between riser tube and
control valve body
Verify that riser tube is seated correctly and is not
cracked
Low levels of
contaminant in treated
water
Bypass not completely closed
Close bypass
Excessive service flow rate
Lower service flow rate
Increasefiltercapacitybyincreasingvolumeoffilter
media
Leak between riser tube and
control valve body
Verify that riser tube is seated correctly and is not
cracked
Air from compressed
air chamber rapidly
escapes to outlet
Leak between riser tube and
control valve
body
Verify that riser tube is sea
ling off correctly inside
control valve body
Bypass between inlet and outlet of system
PF
-
OXY1 only
: check that mixing valve on factory
bypass is completely closed
Checkthat bypass valveon 3-valve bypasssystemis
closed
Valve body and timer out of synchronisation
Synchronise valve body and timer
Treated water is
slightly non-
transparent and/or
effervescent
Passage through
compressed air
chamber
causes water to become highly oxygenated
T
otallyharmlessforqualityofthetreatedwaterand
will disappear rapidly if water is left standing for a
moment
Appliance
fails to
start
a regeneration
Faulty electrical supply
Verify electrical service
(fuse, transformer,...)
Defective PCB
Replace PCB
Defective
drive motor
Replace
drive motor
Regeneration frequency not programmed
Program regeneration frequency
Loss of water pressure
B
uild
-
up
of impurities
in
pressure
tank
Clean
filter media
and control valve; increase
regeneration frequency
Plugged lowerand/or upperdistributor
Verify that distributors are free of debris
Drain line from control
valve flows
continuously
Appliance
in regeneration
Wait until regeneration finishes or
manually
advance regeneration to end
Faulty electrical supply
Verify electrical service (fuse, transformer,...)
Defective drive motor
Replace drive motor
PF
-
OXY
1
& PF
-
OXY
+
1
only
: defective micro
switch
Replace micro switches
PF
-
OXY
1
,5 & PF
-
OXY
+
1,5
only
:defective optical
switch
Replace optical switch
Defective PCB
Replace PCB
PF
-
OXY
1
&PF
-
OXY
+
1
only
: valve body andtimer
out of synchronisation
Synchronise valve body and timer
Loss of
filter media
Lower and/or upper distributor damaged
Replace
distributor(s)
Leak between riser tube and upper distributor
Verify that riser tube is seated correctly and is not
cracked

TROUBLESHOOTING
Page 15
PROBLEM
C
AUSE
S
OLUTION
Appliance fails to
backwash properly
Low operating pressure
Check
operating pressure; must
be
higher than
2,5
bar
Insufficient water supply
Check water supply(flow rate/dynamicpressure)
Restricted drain line
Verify drain linefor kinks or restrictions
Excessiveb
uild
-
up
ofimpurities
in
pressure
tank
Clean
or replace
filter media
and control valve;
increase regeneration frequency
Plugged backwash flow control
Clean
or replace backwash flow control
Plugged top or bottom distributor
Verifythattopandbottomdistributorarecleanand
slots are not clogged by iron or other impurities
Filter media is completely ‘caked’ (solid block)
Replace filter media and reduce regeneration
interval
Control valve cycles
continuously
PF
-
OXY
1
& PF
-
OXY
+
1
only
: defective micro
switch
PF-OXY1,5 & PF-OXY+1,5only: defective optical
switch
Replace micro switches
Replace optical switch

ELECTRICAL WIRING DIAGRAMS
Page 16
PF-OXY1 & PF-OXY+1
= position switches
= powerlead
= drive motor
= service valve NO (optional)
= key pad
PF-OXY1,5 & PF-OXY+1,5
= optical switch
= powerlead
= drive motor
= service valve NO (optional)
= key pad

DEFAULT CONFIGURATION PARAMETER SETTINGS
Page 17
Model PF-OXY1 & PF-OXY+1
Filter media (cuft) 1 2 3
Interval (days) 4 4 4
Cycle 1:BACKWASH (min) 10 10 10
Cycle 2:AIRINTAKE(min) 10 10 10
Cycle 3:PURGE (min) 1 1 1
Regen@ 0:00 0:00 0:00
Model PF-OXY1,5 & PF-OXY+1,5
Filter media (cuft) 3 4 5 7 10
Interval(days) 4 4 4 4 4
Cycle 1:BACKWASH (min) 10 10 10 10 10
Cycle 2:AIRINTAKE(min) 9 12 15 21 30
Cycle 3:PURGE(min) 1 1 1 1 1
Cycle 4:nofunction 0 0 0 0 0
Regen@ 0:00 0:00 0:00 0:00 0:00

COMPOSITION OVERVIEW
Page 18
Model Media
volume PN Control valve, incl. transformer,
1” male BSP connections Pressure tank,
incl. distributor assy Underbedding Filter media
(1 cuft bag)
cuft model # model # type ltr type #
PF-OXY1
1 35669 2400TF/J5N/SV/AIR 1 10x40 1 Gravel 2-4 mm 4 Birm 1
2 35670 2400TF/J5Q/SV/AIR 1 12x52 1 Gravel 2-4 mm 6 Birm 2
3 35708 2400TF/J5S/SV/AIR 1 14x65 1 Gravel 2-4 mm 8 Birm 3
PF-OXY+1
1 35781 2400TF/J5N/SV/AIR 1 10x40 1 Gravel 2-4 mm 4 Katalox-Light 1
2 35782 2400TF/J5Q/SV/AIR 1 12x52 1 Gravel 2-4 mm 6 Katalox-Light 2
3 35783 2400TF/J5S/SV/AIR 1 14x65 1 Gravel 2-4 mm 8 Katalox-Light 3
Model Media
volume PN Control valve, incl. transformer,
1,5” male BSP connections Pressure tank,
incl. distributor assy Underbedding Filter media
(1 cuft bag)
cuft model # model # type ltr type #
PF-OXY1,5
3 35862 EV1.5TF/J/100/AIR 1 14x65 1 Gravel 2-4 mm 12 Birm 3
4 35863 EV1.5TF/J/150/AIR 1 16x65 1 Gravel 2-4 mm 15 Birm 4
5 35864 EV1.5TF/J/200/AIR 1 18x65 1 Gravel 2-4 mm 18 Birm 5
7 35865 EV1.5TF/J/250/AIR 1 21x62 1 Gravel 2-4 mm 22 Birm 7
10 35866 EV1.5TF/J/350/AIR 1 24x72 1 Gravel 2-4 mm 26 Birm 10
PF-OXY+1,5
3 35874 EV1.5TF/J/100/AIR 1 14x65 1 Gravel 2-4 mm 12 Katalox-Light 3
4 35875 EV1.5TF/J/150/AIR 1 16x65 1 Gravel 2-4 mm 15 Katalox-Light 4
5 35876 EV1.5TF/J/200/AIR 1 18x65 1 Gravel 2-4 mm 18 Katalox-Light 5
7 35877 EV1.5TF/J/250/AIR 1 21x62 1 Gravel 2-4 mm 22 Katalox-Light 7
10 35878 EV1.5TF/J/350/AIR 1 24x72 1 Gravel 2-4 mm 26 Katalox-Light 10

Page 19

EXPLODED VIEW - PF-OXY1 & PF-OXY+1 - SYSTEM
Page 20
Other manuals for PF-OXY1
1
This manual suits for next models
2
Table of contents
Other ProFlow Water Filtration System manuals
Popular Water Filtration System manuals by other brands

Schaffner
Schaffner FN5420 User and installation manual

MAUNAWAI
MAUNAWAI PI CONNECT PiTec 2in1 manual

Riello
Riello BAG2 MIX CLIMA INSTRUCTIONS FOR THE INSTALLER AND THE TECHNICAL ASSISTANCE SERVICE

KOGANEI CORPORATION
KOGANEI CORPORATION FRZ Series instruction manual

Unilever
Unilever pureit UR5640 instruction manual

Thermo Scientific
Thermo Scientific 1403 Series operating manual