Projoy Electric PEFS-24V-CN Series User manual

www.projoy-electric.com
Installation
Guide
PEFS-24V-CN Series

www.projoy-electric.com
Operation Manual of Panel Level Rapid Shutdown(DC 24V) Control Box
1. Scope and General
2 Important Safety Precautions
3 Introduction
4 Installation & Connection
5 Technical Specification
6 Trouble Shooting
7 Aftersales service and warranty
8 Contact us
1
1
1
2
5
6
6
6
RSD PEFS-24V-CN Series
CONTENT

1 Scope and General
The manual only used to PEFS-24V-CN Series Panel-level Rapid Shutdown(DC 24V) Control Box.
Version Date Remark Chapter
V1.0 2021-10-15 First Edition -
www.projoy-electric.com
RSD PEFS-24V-CN Series
1
2 Important Safety Precautions
PROJOY assumes no responsibility for any loss, in particular for circuit damage, resulting from any violation of the specifica-
tions recommended and referred to in this specification. PROJOY assumes no responsibility for the damage of the product
caused by the maintenance, improper use, wrong installation or wrong system design of the product by non-designated
personnel.
3 Introduction
2.1 Disclaimer:
1) PEFS is an electrical product that should be installed by a suitable person who meets local regulations.
2) When modifying and existing installation, isolate the inverter from the PV array by turning OFF the DC isolator / switch
disconnect or turn OFF the inverter and the AC switch.
3) Incorrect connections to the PEFS-24V-CN may cause failure.
2.2 Safety instructions:
If the inverter and pv module connectors are not compatible with PEFS connectors, forced connections are unsafe and may
cause operational problems.
For the mechanical compatibility of the module / converter and PEFS, use the same connectors from the same manufacturer
on both the PEFS and modules, or obtain verification that the connectors to be used are compatible.
2.3 Cautions:
V2.0 2022-04-20 Content Modified 4 Installation & Connection/
5 Technical Specification
Control Box Include Power Supply
①PEFS-24V-C60
V3.0 2022-06-02 Content Modified
3 Introduction
4 Installation & Connection/
5 Technical Specification

1) Open the box, take out PEFS-24V-CN and parts, read this manual.
2) Prepare materials and tools.
ST4.8×38
expansion bolt
cross/straight screwdriver
www.projoy-electric.com
RSD PEFS-24V-CN Series
2
②PEFS-24V-C180
①PEFS-24V-C480
DC4
DC1
DC2 DC3
DC5
DC6 DC7
DC8
DC IN
Control Box External Power Supply
4 Installation & Connection
* PEFS-24V-C60/C180 Type provide
Product Cable L-shaped Clasps Manual
* 2-core wire 20/30/100m Optional

www.projoy-electric.com
RSD PEFS-24V-CN Series
3
a) Pull out the clasps to both sides.
DC 24V
SWITCH
POWER SUPPLY
L N
PE
+ -
Black White Black White
AC MAINS
3) The installation modes of PEFS-24V-CN are divided into the following two situations.
Control Box Include Power Supply (Take PEFS-24V-C60 as an example)
a) Align the round hole of the L-shaped calsp with the round hole of the box and fix them with screws.
b) Mount the control box to the appropriate location through the gourd-shaped hole.
Control Box External Power Supply (PEFS-24V-C480)
installation location(e.g. wall)
c) Wring.

b) Mount the control box to the appropriate location through the gourd-shaped hole.
installation location(e.g. wall)
PEFS-24V-C480 does not have a power supply, so an external power supply is required to power the control box.
c) Wiring
www.projoy-electric.com
RSD PEFS-24V-CN Series
4
4) Parallel connection of multiple control boxes
Inverter
Grid
Control Box
Control Box
Control Box
Control Box
Control Box
DC +
DC -
≤80V ≤80V ≤80V
……
PEFS-PL PEFS-PL PEFS-PL
≤80V ≤80V ≤80V
……
PEFS-PL PEFS-PL PEFS-PL
200m
200m
DC 24V
SWITCH
POWER SUPPLY
L
N
+
-
Black White
Black White
DC 24V Input
PE

www.projoy-electric.com
RSD PEFS-24V-CN Series
5
5 Technical Specification
Protection Class
Model PEFS-24V-C60
Operating AC Voltage Range
Mounting
Maximum Distance
(Last RSD to Controller Box)
Norminal Frequency
Max. Output Current
Output Voltage
Operating Temperature Range
PEFS-24V-C180
Maximum PEFS-PL80S-21
Dimensions (mm)
Maximum PEFS-PL80S-11
With Lock
24Vdc Control Cable Length
With Standard Connectors
24Vdc Control Cable Size
-30℃~ +70℃
IP65
Wall Mounted
200m
8.8A
60 Units 180 Units
30 Units 90 Units
155*188*63 265*218*63
Optional (IP54)
100 V-240 V
50/60 Hz
2.2A
24V DC
0.823 mm2 / 18 AWG
20 m / 30 m / 100 m
YesSpare Terminal Connectors
Protection Class
Model
100 V-240 V
50/60 Hz
24V DC
-30℃~ +70℃
IP65
Wall Mounted
200m
Operating AC Voltage Range
Mounting
Maximum Distance
(Last RSD to Controller Box)
Norminal Frequency
Output Current / Per String
Output Voltage
Operating Temperature Range
PEFS-24V-C480
2.2A
Maximum PEFS-PL80S-21 / Per String
Dimensions (mm)
Maximum PEFS-PL80S-11 / Per String
With Lock
60 Units
30 Units
210*175*105
Optional
0.823 mm2 / 18 AWG
24Vdc Control Cable Length
With Standard Connectors
24Vdc Control Cable Size
20 m / 30 m / 100 m
Yes
Spare Terminal Connectors
Control Box (Include Power Supply)
Control Box (External Power Supply)
Maximum PEFS-PL80S-11
Maximum PEFS-PL80S-21
Output Current
480 Units
240 Units
≥20A
Recommend
Power Supply

In the occurrence of a fire, PROJOY recommend that all elements of the PEFS Rapid Shutdown system be assessed for
operational suitability by a competent person prior to re-energising.
6 Trouble Shooting
Possible Solution
Check area utility operational
Check mains ON
Check mains fuse
Check mains voltage between L&N marked terminals
Check 24VDC between + & - marked terminals
Turn red actuator anti-clockwise to release button
Check 24VDC between switch out terminal & PSU – marked terminal
Check 24VDC between terminals of remote AMP
Superseal connector (pin 1 +24VDC\pin 2 0VDC)
Check all PV to PEFS-24V-CN input connections
Check PV array Positive (+) goes to PEFS-24V-CN
Positive (+) and PV array Negative (-) goes to PEFS-PC Negative (-)
Replace PEFS-24V-CN
Check PEFS-24V-CN output connections
Check DC inputs to isolator
Turn DC Isolator ON
Check all PV array Positive (+) go to PEFS-PC
Positive (+) and PV array Negative (-) goes to PEFS-PC Negative (-)
Problem Possible Cause
No mains supply
PEFS-24V-CN switch activated
No PEFS-24V-CN switch output
PV array not connected
No PEFS-24V-CN output
No DC isolator (if fitted)
input
DC Isolator (if fitted) OFF
String voltage
too low
Incorrect PEFS-24V-CN
polarity connection
Panel (pair)
voltage is 0V
PV Inverter
input 0V
PEFS-24V-CN power supply failure
(LED OFF)
Broken cable
Incorrect PEFS-24V-CN
polarity connection
www.projoy-electric.com
RSD PEFS-24V-CN Series
7 Aftersales service and warranty
7.2 Aftersales service
This product is manufactured in a sophisticated quality management system. In case of fault, following warranty and after
services clauses are applicable.
1) Please contact the supplier or our company's after-sales service department in case of failure;
2) During the warranty period: For failures caused by the company's manufacturing problems, free repairs and replacements;
3) After the warranty period expires: If the function can be maintained after the repair, make a paid repair, otherwise it can be
replaced with a paid.
7.1 Warranty
On the premise of user’s compliance with reservation and use specifications of the breaker, for breakers whose delivery date is
within 60 months from now and whose seals are intact, PROJOY will repair or replace any of these breakers which are damaged
or cannot work normally due to manufacture quality. However, as for faults caused by following reasons, PROJOY would repair or
replace the breaker with a charge even it is still in warranty.
1) Due to incorrect use, self-modification and improper maintenance, etc.:
2) Use beyond the requirements of standard specifications;
3) After the purchase, due to falling and damage during installation, etc.;
4) Earthquakes, fires, lightning strikes, abnormal voltages, other natural disasters and secondary disasters, etc.
8 Contact us
Projoy Electric Co., Ltd.
Tell:+86-512-6878 6489
Web: https://en.projoy-electric.com/
Add: 2nd Floor, Building 3, No. 2266, Taiyang Road, Xiangcheng District, Suzhou
6
This manual suits for next models
3
Table of contents
Other Projoy Electric Firefighting Equipment manuals
Popular Firefighting Equipment manuals by other brands

Amerex
Amerex 570 Owner's service manual

PAB
PAB Fire Compact user manual

General Air Products
General Air Products RFP System Installation, operation and maintenance manual

jablotron
jablotron JA-80S quick start guide

SEI Industries
SEI Industries SACKSAFOAM I 8018 manual

MFA
MFA GORE WARNING & USER INFORMATION GUIDE