Prolitec Air-Q 1100 User manual

Page1of18
Air‐Q1100
UserGuide
Rev1.05/13/09
©2009,ProlitecInc.

Air-Q 1100 User Guide Page2of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
Air‐Q1100
UserGuide
(Rev1.05/13/09)
©2009ProlitecInc.
I.IntroductiontoAir‐Q1100............................................................................... 1
A.ApplicationsandUses
1.AmbientScenting
2.OdorControl
II.SafetyPrecautions........................................................................................... 3
A.AppliancePrecautions
B.FragrancePrecautions
III.ApplianceandControls ................................................................................... 4
IV.GeneralMaintenance....................................................................................... 5
A.ChangingtheCartridge
B.O‐ringreplacement
C.BatteryReplacement
V.CommissioningAir‐Q1100.............................................................................. 7
A.UnitProgramming
B.SettingScentIntensity
VI.Installation........................................................................................................ 9
A.Pre‐InstallationChecklist
B.InstallationKit
C.AppliancePositioning
D.ApplianceInstallation
E.InjectorTubeInstallation
VII.Troubleshooting ............................................................................................. 15
VIII.GeneralCareandCustomerSupportContacts............................................ 17
IX.Specifications.................................................................................................. 18

Page1of18
I.IntroductiontoAir‐Q1100
TheAir‐Q1100applianceisanairtreatmentsystemforinteriorspacesservedbyaductedHVACair
handlingsystem(“HVAC”).TheAir‐Q1100deliversafragranceorairtreatmentagent(“Agents”)
intotheairflowoftheHVACsystemeitherthroughthecentralfanunit(CFU)oratsuitable
locationsinthebranchedductwork.Itisdesignedforpermanentinstallationontheoutsideor
insideoftheCFU.
TheAir‐Q1100ismanagedbyanon‐boardcomputerthatisfullyprogrammableforspacesizes
from1,000to250,000cubicfeetperapplianceandoneormoreintensitylevelsinthesameday.
MultipleappliancescanworktogetheronthesameormultipleCFUstotreattheairinthesame
spacesservedbytheHVAC.Inthisway,thereisnolimitationonthesizeofthespacethatcanbe
servedbyAir‐Q1100.
Air‐Q1100requireslittletonomaintenanceexceptperiodiccleaningforappearance.Installations
ofAir‐Q1100aredesignedsothattheconsumptionoftheconsumableCartridgesofAgent
(“Cartridges”)requiresreplacementnomorefrequentlythanonceamonth.
TypicalAir‐Q1100applicationsincludeairtreatmentforodorremediation,scentbrandingand
ambientscentinginpublicspacessuchascasinos,malls,hotels,theaters,ballrooms,convention
centers,hospitals,andrestrooms.
TheAir‐Q1100generatesultrafine,ultra‐lightdropletsapproximately500nanometersin
diameter.Bycomparison,adropletfromapressurizedaerosolis50microns(50000nanometers)in
diameteror166timeslargerthananAir‐Q1100droplet.Intermsofweightandvolumeofliquid,
thecomparisonisevenmoredramatic.A50‐micronaerosoldropletis4.6milliontimesheavier
thana300‐nanometerAir‐Qdroplet.1ThistinyAir‐Qdropletoffersmanyperformancebenefits
overaconventionalaerosolincluding:completelyuniformdistributionofthetreatmentagent;100
timesmoreexposedsurfaceareaallowinguseofmuchlessairtreatmentagentpercubicfoot;and
theabsenceofanyliquiddepositsonsurfacessuchastheinteriorsurfacesinaHVACsystem.
TheAir‐Q1100Guideispackedwithimportantinformationthatwillhelptheusers,installersand
serviceengineersoptimizetheperformanceofthismodernairtreatmentsystem.Weencourage
youtoreaditcarefully.
1This is calculated using the formula for the volume of a sphere where Vis the volume or weight and r is
the radius of the droplet.

Air-Q 1100 User Guide Page2of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
A. ApplicationsandUses:
Air‐Q1100isusedwithproprietaryfragrancesandodorremediationagents(“Agents”)toenhance
indoorairqualitybyerasingodorsandintroducingscent.Thisisaccomplishedbyconvertingliquid‐
stateAgentsintoultra‐finedropletsandinjectingthemintothemintotheHVACsystemtoblend
withtheairflow.Usedasdirected,theconcentrationofAgentintheairwillusuallybelessthan1
partpermillion(<1ppm).Thismeansthatforevery1,000,000moleculesofair,lessthan1
moleculeisairtreatmentAgent.TheAir‐Q1100’sdropletsareabout500nanometersindiameter
(halfamicron).Adropletofthissizepresents10,000timesmoresurfaceareatotheairthanthe
sameamountofliquidina50‐micronaerosoldroplet.TheAir‐Qdropletis1/1,000,000ththeweight
ofanaerosoldroplet.Thismeansthedropletsbehaveasiftheyweredry,donotleaveanyresidue
onthebladesorinteriorductsurfacesandcreatescenteffectwithconcentrationssolowitus
unlikelytotriggerallergicresponse.
TherearetwobasicapplicationsforAir‐Q1100:ambientscentingandodorremediation.TheAir‐Q
1100deliverysystemandProlitec’sproprietaryairtreatmentchemistrycandobothatthesame
timeoreitheronealone.
1.AmbientScenting
AmbientScentingistheuseoftheAir‐Q1100todeliverascenttocreateamoodor
ambience,associateascentwithabrand,enhanceavisualthemeorsimplymakeaspace
morepleasantforitsoccupants.
2.OdorControl
OdorControlistheuseofAir‐Q1100andspecialairtreatmentchemistrytoneutralize
odorsbyblockingcertainmalodorsthusallowingtheintroductionofverysmallquantities
offragranceintotheair.Normalairfreshenerssimplyusefragrancetodouseamalodor.

Air-Q 1100 User Guide Page3of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
II.SafetyPrecautions
A.Air‐Q1100AppliancePrecautions:
• Theappliancemustbeoperatedinanuprightorverticalpositionandfirmlyattachedtoa
verticalsurfacesuchasawalloraduct.
• TheapplianceshouldNOTbeusedwiththedoorintheopenposition.Thedoorisopened
onlytoperformacartridgeorprogramchange.
• NEVERputyournosetotheoutputofAir‐Q.Within12inchesoftheoutput,thefragranceis
highlyconcentrated.Theimproperinhalationofhighconcentrationsoffragrancemaycause
irritationincludingwateryeyes,headache,coughandupperrespiratorydiscomfort.
• Theapplianceisbuilttobepluggedintoan110VACor220VACpoweroutlet.TheULandCE
compliantpowersupplyconvertspowerto12VDCtopowertheappliance.
• Unplugbeforecleaning.
B.Air‐QCartridgePrecautions
• ReadtheProductSafetyInformationSheetandtheMaterialSafetyDataSheetenclosed
providedwitheachshipmentofCartridges.Insurethattheseinformationsheetsare
availableforreviewbyemployees
• UselatexglovestohandleaCartridgetoavoidtheliquidgettingonhands.TheAgentsare
formulatedsoastonotbeharmfulincontactwiththeskin,buttheconcentratednatureof
theagentsmakesthescentdifficulttoremovefromhandsandskin.
• WashyourhandsafterallcontactwithCartridgesorfragranceandairtreatmentagents.
• CartridgesmustbeprovidedbyandcontainAirTreatmentAgentformulationswhichhave
beencertifiedbyProlitec.
• WhileAir‐QAirTreatmentAgentsdonotcontainingredientsdeemedharmfultotheskin,if
thereisskincontact,washwithsoapandwater.Ifthereiscontactwiththeeyes,irrigate
theeyewithfreshwaterfor5minutes.Ifthereisanyeyeirritation,consultaphysician
immediately.

Air-Q 1100 User Guide Page4of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
III.ApplianceandControls
Air‐Q1100
Cartridge
InjectorHose
ControlDisplay
ControlButtons
PowerCord
ProgramSelector
BatteryTab
AirNozzle
HoseConnector
HoseClamp
AirFilter

Air-Q 1100 User Guide Page5of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
IV.GeneralMaintenance
A.ChangingtheCartridge
• Unlatchandopenthedoortoaccessthecartridge:Thedoorshouldbeopenedonlyto
performacartridgeorprogrammingchange.Wheninuse,thedoormustbeclosed.
1.Removeairnozzle(locatedonthesideofthecartridgehead)byrotating90degreesand
pullingtowardsyou.(SeePicture#1)
2.DetachInjectorhoseandhoseconnectorfromthecartridgeoutputport(locatedonthe
topofthecartridgehead).Thisisdonebyunscrewingthehoseconnectorfromthe
cartridgeoutputportandpullingout.
3.Removecartridgefromapplianceenclosure.
4.Installnewcartridge,placeandtightenhoseconnectorfirmlyoncartridgeoutputport.
5.Insertairnozzleandrotatethehandle90degreesuntilsecured(bystemretainingtab
oncartridgehead).(SeePicture#2)
6.Turnapplianceon.Verifythattheplumeisnotescapinginsidetheapplianceandthatall
connectionsaretight.Closethedoorwhencomplete.
B.O‐ringReplacement–every6monthsorasneeded:
• Replacetheairnozzle3o‐rings(Partnumber10208) ifworedownorswollen.Apartiallyfull
cartridgemayindicateanairleakbetweentheairnozzleandthecartridge,reducingplume
output.Replaceasneededand/oreverysixmonthsforpreventativemaintenance.
• IfthereisanyAgentthatleaksduringthecartridgeinstallation,cleanitcarefullywitha
papertowelwithsomeethanoloranotheralcohol.
C.AirFilter–every6monthsorasneeded.
• Replaceairfilter(partnumber10417) ifdirty.Ifanydusthasgatheredinsidetheunit,
removeitwithadamppapertowel.
Picture1Picture2
Cartridge
RetainingTab

Air-Q 1100 User Guide Page6of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
D.BatteryReplacement–approx.every2years:
(requires3VoltCR2032LithiumBattery,partnumber8111):
1.Unlatchandopenthedoortoaccesstheenclosure.
2.Usingapairoftweezersorneedle‐nosepliers,remove
batteryfromthecenteropeningoftheovalgrommet.The
grommetislocatedonthefrontofthebluebracketbelowthe
operatingbuttons.
3.InsertthenewCR2032battery.Thepositivesideofthe
batteryshouldfaceyourrightwhilelookingatthefrontofthe
appliance.Thebatterywillhavea+or–markingonaside.

Air-Q 1100 User Guide Page7of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
V.CommissioningtheAir‐Q1100
A‐UnitProgramming
1.Openthedoorandunlockifneeded.
2.TurnonthepowerbypressingtheON/OFFbuttonintheupperleftcornerofthecontrolpanel.
(MakesuretheapplianceispluggedintotheACpoweroutlet.)Thepowerbuttonwilllightblue
3. SettingtheClock.
•TurnthedialtoSetClock.Thetimewillblink.
•Adjustthetimeforwardorbackwardusingthe+/–buttonsontherightsideofthecontrol
panel.AMorPMisindicatedonthelowerrightsideofthetimedigits.Hold+tofastforward.
4. Usingthe24/7Mode.
• IfyouwanttheAir/Q™1100toruncontinuously—7daysaweek,24hoursaday—turn
thedialto24/7.Ifnot,skiptoStep5.
5. SettingspecificStart/StopTimes.
• TurnthedialtoStart.
• Adjusttheclocktothetimeyouwanttheappliancetostarteachdayusingthe+/–keys.
• TurnthedialtoStop.
• Adjusttheclocktothetimeyouwanttheappliancetostopeachdayusingthe+/–keys.
6. UsingtheProgramMode
• TurnthedialtoProgramtooperatewiththespecifiedstart/stoptimes.
7. UsingtheProgramOverride
• Pressthebuttoninthebottomleftcornertooperatetheapplianceoutsidethespecified
start/stoptimes.
• Eachtimethebuttonispressed,anotherhourisaddedupto12hours.

Air-Q 1100 User Guide Page8of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
B‐SettingScentIntensity
1.ConsulttheSettingsTable,whichprovidesasettingforthesizeincubicfeet(lengthxwidthx
ceilingheight)ofthespaceyouaretreating.Usetheindicatedintensitysettingasastarting
pointfromwhichyoucanincreaseordecreasetotaste.Numberoffreshairchangesperhour
anduserpreferencewillaffectsettings.
SettingsTable:
Output Level Range
Settings Space to be treated
in Cubic Feet Space to be treated
in Cubic Meters
1 thru 5 3,000-15,000 85-425
6 thru 10 15,000-29,000 425-820
11 thru 15 29,000-48,000 820-1360
16 thru 20 48,000-68,000 1360-1,900
21 thru 25 68,000-91,000 1,900-2,600
26 thru 30 91,000-117,000 2,600-3,300
31 thru 35 117,000-146,000 3,300-4,100
36 thru 40 146,000-177,000 4,100-5,000
41thru 45 177,000-214,000 5,000-6,000
46 thru 50 214,000-250,000 6,000-7,100
2. Pressthepowerbuttonon.TurnthedialtoProgramandsettheintensitylevelwiththe+/–
keys.Youwillseethelevelnumbers(1to50)ontherightsideofthescreen.
Hint:Therearemanyvariablesinvolvedinfindingtherightsettingsforscent.Feelfreetoadjustto
taste.DonotsetscentleveltomaximumsettingorhigherthanrecommendedintheSettingTable,
butstartfromrecommendedlowestlevelandincreaseprogressivelyforoptimumresults.
TheLastStep
1.Setthedialtoeither24/7orProgramifyouhaveprogrammedastart/stoptime.
2. Makesurethepowerison.Thebluelightwillshowthroughthebutton.
3. Closeandlockthedoor,storingthekeyinaknownplace.

Air-Q 1100 User Guide Page9of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
VI.Installation
A.Pre‐installationChecklist
Thischecklistshouldbecompletedbeforetheinstalldate.
1.Confirmtheareatobetargetedforairtreatment
2.DeterminetheAirHandlingUnitorductthatservesthetargetarea.
3.MakesuretheAHUdoesnotuseanopengasflame.
4.FindandmarktheoptimalinsertionpointfortheInjectorTube.(SeesectionC:“Appliance
Positioning”)
5.Findandmarktheexactlocationforplacementoftheappliance(SeesectionC:“Appliance
Positioning”)
6.Notethedistancebetweentheinsertionpointandtheproposedappliancelocation.(NEVER
MORETHAN6FEET)andthereshouldNEVERbeaLOWPOINTinthehoserun.
7.Determineandmarkthelocationforthe110or220VACpoweroutlet.(NEVERDIRECTLY
BELOWTHEappliance)
B.InstallationKit(photos–Page10)
• One(1)Air‐Q1100appliance(notpictured)
• One(1)ProlitecInjectorTube(a)
• Three(3)Feet3/8thID,½ODInjectorhose(b)
• One(1)hoseconnectorassembly(c)
• One(1)hoseclamp(d)
• Seven(7)#10self‐tappingsheetmetalscrewsforsecuringtheapplianceandinjectortubeon
sheetmetal.(e)
• 1sparesetof3o‐ringsfortheairthenozzle(f)

Air-Q 1100 User Guide Page10of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
• Optional:Onehosequickdisconnectfittingwith3feethoseextensionwithhoseclamps,to
increasedistanceupto6feet(seenote#6above)
(a)
(b)
(c) (d)
(e)
(f)

Air-Q 1100 User Guide Page11of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
C.AppliancePositioning
Itisimportanttofindaninsertionpointwheretheplumeoutputwillbesmoothlydrawninto
andmixedwiththeairflow.ThisusuallymeansthosepartsoftheAHUwherethestatic
pressureisnegative.Ideallocationsinclude:
• BeforethesupplyfanwithinjectionthroughthewalloftheAHU.Positioningimmediately
beforethefanandafterthecoilsifpossibleorinthemixedairchamber.
• BehindtheblowerwiththewholeappliancemountedinsidetheAHUinthemixedair
chamber.
• OutsidetheAHUintheSupplyairduct.
BestpracticewheninstallinginanAHUistoplacetheinjectortubeaftertheheatingand
coolingcoils.Ifthisisnotpossible,thePlumeoutputcanpassoverhotwater,steam,chilled
water,andDXcoils.
Opengasflamesshouldabsolutelybeavoided.Ifinstallationmustbeovergasheatedcoilsor
opengasflames,contactProlitecTechnicalSupport.
ThebestlocationfortheApplianceisbelowtheinjectortube(SeeFigure1).Theinjectorhose
shouldberunupwardasshortadistanceaspossibleandNEVERMORETHAN6FEETOR180
CENTIMETERS.Ifanupwardinjectorhoserunisnotpossible,careshouldbetakensupportthe
hosetopreventsaggingoranylowspotintheruntoavoidanypossibilityofcondensationand
liquidcollectionwhichwillblocktheplumeoutput.Theinjectorhoseispronetostretching,so
supportpointsshouldbeplacedevery5to6inchesonhorizontalruns.Givethehoseaslight
upwardslantalongitsrun(SeeFigure2).Thehosemustnotberunhorizontally.Astrongtape
(suchasVenturetape)maybeusedtosupportshortruns.ThehosemayberunthroughPVC
pipeforlongerdistances.
Figure1
InjectorTube
PowerJunctionbox
Injectorhose
Air‐Q1100

Air-Q 1100 User Guide Page12of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
D.ApplianceInstallation
1.TheAPPLIANCEiswall‐mounted.PlacetheAPPLIANCEontothedesiredlocationonthewall
orAHUandensurethatitislevel.
2.FastentheAPPLIANCEtothewallorAHUusingthenecessaryscrews.
3.ConnectthepowercordtoajunctionboxorattachanACplugtothecordandconnecttoa
nearbyoutlet.
4.Opentheenclosuredoorandunscrewthealuminumcapofthewaterproofcollarlocated
ontopoftheapplianceenclosure.Removeandsetasidethegrommet(seephotoonPage
13).
5.Assemblehoseandhoseconnectortogether(seephotobelow).Besuretoleave
approximately1/8ofaninchclearancebetweenthetopofthecartridgehoseconnector
andtheendofthehose.Thensecurewithclamp,ensuringthatthehoseconnectorisstill
freetorotate.
AQ
1100
DUCT or
PLENUM
DIP
INCORRECT
AQ
1100
DUCT or
PLENUM
CORRECT
Figure 2
Clamp
Leave 1/8"
clearance
Hose
Connecto
r

Air-Q 1100 User Guide Page13of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
6.Fromtheinsideoftheenclosure,slidehoseassemblyupwardthroughtothewaterproof
collar.
7.LubetheinsideofthegrommetifneededtoallowtheInjectorhosetoeasilyslidethrough.
Leaveapproximately2inchesofhoselengthinsidetheappliancetoprovideenoughplay
whenreplacingthecartridge.Tightenaluminumcapofwaterproofcollartoensurea
watertightseal.
8.Usetheoptionalquickdisconnectfitting(SeephotoonPage10)toaddahoseextensionif
needed.
Waterproof
Colla
r

Air-Q 1100 User Guide Page14of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
E.InjectorTubeInstallation
TheinjectortubeisinstalleddirectlyintotheAHUortheductwork.Itsorientationcanbeadjusted
relativetotheairflow.
• Forinstallationsintothenegative/suctionsideoftheAHUfan,orientthetubewiththe
elbowpointedupwards(SeeFigure2),sothatanyplumecondensationwillsipbackin
thetube.
• Forinstallationsafterthesupplyfan,suchasinasupplyduct,itisnecessarytoconfigure
andorienttheInjectorTubetoobtainagoodaspirationoftheoutputintotheair
stream.Theinjectortubeshouldbepointedinthedirectionoftheairflowandinclined
45oupwardapproximately.Turbulenceintheairflowcanpreventevenaspirationofthe
plume.Itisbesttoplacethetubeinastraightsectionofduct,andfarawayfromany
turns,branches,orcross‐sectionchangesaspractical,andnotimmediatelyafterthe
supplyfan.
1.Attheinsertionpoint,drillaholeusinga½”drillbit.
2.InserttheInjectorTubethroughthehole.
3.FindanorientationoftheinjectorTubethatappearstoproduceagooddrawofairinto
theendofthebarb.
4.Fastentheflangeusingthethree#10sheetmetalscrews
5.TurntheAPPLIANCEonandverifythataplumeisproduced.
6.BeforeattachingtheInjectorhosetotheinjector,verifythattheplumecanfloweasily
throughtheinjector.Thiscanbedonebyplacingtheendofthehose½inchawayfrom
theinjectorandverifyingthattheplumeisbeingdrawnin(aflashlightwillmakethe
plumeeasiertosee).Iftheplumedoesnotriseintothehose,adjusttheorientationof
theInjectorTubeuntilaspirationisachieved.
7.AttachtheInjectorhoseontothehosebarboftheInjectorTube.
ForCartridgeInstallation–See"ChangingtheCartridge"onPage5.

Air-Q 1100 User Guide Page15of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
VII.Troubleshooting
ConditionCausesSolutions
Powerlightoff.TheApplianceisnot
pluggedinortheplug
hasnopower
Makesurethepowerconnectionisoperational.
Verifythatthepowerbuttonlightisbluewhen
pressed.
Unitdoesnotstart
automaticallyafterapower
interruption
Back‐upbatterynot
operational
Verifytheprotectiveyellowbatterytabhas
beenremoved.
Verifythebatteryispositionedwiththepositive
sidefacingtheright.
Replacetheback‐upbattery.
Thefragrancecannotbe
detectedwhencominginto
thetreatedareafroman
untreatedarea.
Theoutputrateistoo
loworthereisan
insufficientnumberof
appliancesservingthe
space
TheO‐Ringsonthestem
thatfitsintothehead
maybewornoutand
causinganairleak.
Increasetheoutputratebyoneortwosettings
andevaluatedetectionin30minutes.Repeatas
needed.IfconsumptionrequiresCartridge
changemorefrequentlythaneachmonth,
installanadditionalappliance.
ReplacetheO‐Ringsbyremovingthewornone
withapointytoolandrollingonthenewones
Fragranceintensityis
strongerthanjust
detectable.
Theoutputrateistoo
high.
Lowertheoutputrateinincrementsofoneor
twosettingsordowntothestartingrates
suggestedintheroomsizechart.
Thepowerlightisonbut
thethereisnooutputor
youcannothearthe
compressorinthe
appliance.
Youareinan“OFF”
periodintheTimercycle.
Simplywaitafewminutesfortheapplianceto
cycleon.Iftherealproblemisthatthescent
cannotbedetected,increasetheoutputrateas
instructedabove.
Thepowerlightisonand
thecompressorcanbe
heardbutnofragrance
detected.
Theoutputtubemaybe
blocked.
Theairintakemaybe
blocked.
Removethehosefromtheoutputtubeleaving
theCartridgeinplaceintheappliance.Turnthe
applianceonsoyoucanhearthecompressor.
Useaflashlighttoobservethetopoftheoutput
headforaplumeofdroplets.Ifyoucanseethe
plumethentheblockagemaybeinthehoseor
theinjectortubeintotheHVAC.Checkthese.If
thereisnoplumesomethingisblockingthe
outputtube.Checkandremoveit.
Anothermethodforclearingobstructionsis,
whiletheappliancecompressorisrunning,
blocktheoutputtubewithafingerfor2or3
secondsandthenopenit.Byremovingyour
finger.

Air-Q 1100 User Guide Page16of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
TheO‐Ringsonthestem
thatfitsintothehead
maybewornoutand
causinganairleak
ReplacetheO‐Ringsbyremovingthewornone
withapointytoolandrollingonthenewones
Youdetectthefragrance
whenenteringtheroombut
afterawhileyounolonger
noticeit.
Thisiscalledolfactory
adaptationandis
normal.
Leavetheareafor5to10minutes.Comeback
inside,youwillsmellthefragranceonceagain.
Donothesitatetorepeatthisprocessevery
timethatyoudoubtthepresenceofthe
fragranceinthearea.

Air-Q 1100 User Guide Page17of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
VIII.GeneralCareandCustomerSupportContacts
• DonotinstallorstoreAir‐Q1100inplaceswheretheambienttemperaturemayfallbelow
0degreesCelsius(32degreesFahrenheit)orriseabove54degreesCelsius(130degrees
Fahrenheit).(Ifoperatingconditionsmustbeoutsidetheseranges,contactProlitecSafety
andSupportHotlineat888.615.9282).
• DonotdropAir‐Q1100onthefloor.Donotdropitinorpositionitnearanopenbasinof
water.
• Donotpaintorotherwisetrytoalterthecoloroftheoutercover.
• AlwayskeepthelidsonCartridgeswhenstoredoutsideoftheAir‐Q1100.
• DonotoperateAir‐Q1100inverydustyareasthatmaycausetheairintaketoclog.
• PleasecallProlitecCustomerServiceat866.387.4333forinstructionsonreturnshipping
instructionsorquestions.

Air-Q 1100 User Guide Page18of18
(rev 1.0 5/13/09)
© Copyright 2009 Prolitec Inc
IX.Specifications
TechnicalCharacteristics
ReferenceAir‐Q1100:ModelAQ1100
Type1headnebulizerintegratedwithcartridge
Diameterofparticles300nmto1µmicron
PowerInput
Input100–240VACat0.6A
Frequency50/60Hz
ProtectionSwitchingpowersupply
InternalPower12VDCat1.5A
Back‐upbattery
Lithium3V,#CR2032
Performance
Upto250,000cu.feet(7,080cumeters)subjecttoairflowconditions
Control
Programmablestart&stoptimes
Programmableoutput0to50
Dimensions
HeightXWidthXDepth151/2”X133/8”X66/8”(39.4cmX34.0cmX17.2cm)
Weightwithfullcontainer13.7lb(6.2kg)
Cartridge
Reservoir‐1250ml
Disposable/Recyclable
PatentedProlitecInc.......... Multiplepatentspending