Radionics D9000 Series Specification sheet

74-07692-000-C 4/97
D9000/D7000 Series Control/Communicator
Operation and Installation Manual
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 2
74-07692-000-C 4/97
Preface
This manual addresses the operation and
installation of the D9412, D9112, D7412, and
D7212 Control/Communicators only, and should
not be used in conjunction with the D9112B1 or
D7212B1 panels.
Throughout this manual, unless expressly stated,
the words “panel” and “control/communicator”
refer to all four panels (D9412, D9112, D7412,
and D7212).
New Features D9412 D9112 D7412 D7212
Access Control YES, 8 Doors No YES, 2 Doors No
Expanded Users
Arm/Disarm Passcodes
Cards/Tokens 249
996 249
N/A 99
396 99
N/A
Passcode Protected Custom
Functions 16 16 4 4
Number of Printers 3 3 1 1
Number of Points 246 246 75 75
Number of Relays 128 128 64 64
Text marked with a diamond (♦) indicates that
this function or feature is available on the D9412
and D7412 only.
The table below provides an overview of the
differences between the D9000/D7000 Series
Control/Communicators. For additional
information, see the document titled “What’s New
With the D9000/D7000 Series Control
Communicators” (74-07694-000).
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 3
74-07692-000-C 4/97
FCC Notices
Part15
This equipment has been tested and found to
comply with the limits for a Class A digital device,
pursuant to part 15 of the FCC rules. These limits
are designed to provide reasonable protection
against harmful interference when the equipment
is operated in a commercial environment.
This equipment generates, uses, and can radiate
radio frequency energy and, if not installed and
used in accordance with the instruction manual,
may cause harmful interference to radio
communications.
Operation of this equipment in a residential area
is likely to cause harmful interference in which
case the user will be required to correct the
interference at his own expense.
Part68
This equipment complies with Part 68 of FCC
rules. A label contains, among other information,
the FCC registration number and ringer
equivalence number (REN). If requested, this
information must be provided to the telephone
company.
The Radionics D9000/D7000 Series Control/
Communicators are registered for connection to
the public telephone network using an RJ38X or
RJ31X jack.
The ringer equivalence number (REN) is used to
determine the number of devices that may be
connected to the telephone line. Excessive RENs
on the telephone line may result in the devices
not ringing in response to an incoming call. In
most, but not all areas, the sum of the RENs
should not exceed five (5). To be certain of the
number of devices that may be connected to the
line, as determined by the RENs, contact the
telephone company to determine the maximum
REN for the calling area.
If the D9000/D7000 Series Control/
Communicators cause harm to the telephone
network, the telephone company will notify you in
advance. If advance notice isn’t practical, the
telephone company will notify the customer as
soon as possible. Also, you will be advised of
your right to file a complaint with the FCC if you
believe it is necessary.
The telephone company may make changes in
its facilities, equipment, operations, or
procedures that could affect the operation of the
equipment. If this happens, the telephone
company will provide advance notice in order for
you to make the necessary modifications in order
to maintain uninterrupted service.
If trouble is experienced with the D9000/D7000
Series Control/Communicators, please contact
Radionics Customer Service for repair and/or
warranty information. If the trouble is causing
harm to the telephone network, the telephone
company may request that you remove the
equipment from the network until the problem is
resolved. User repairs must not be made, and
doing so will void the user’s warranty.
This equipment cannot be used on public coin
service provided by the telephone company.
Connection to Party Line service is subject to
state tariffs. (Contact your state public utilities
commission for information.)
FCC Registration Number: AJ9USA-18808-AL-E
Ringer Equivalence: 0.1A 0.2B
Service Center in U.S.A.: Radionics, Inc.
1800 Abbott Street
Salinas, CA 93901
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 4
74-07692-000-C 4/97
Table of Contents
BatteryDischarge/RechargeSchedule ........16
ChargingStatusandLowBatteryLEDs ...........17
ChargingStatusLED(Yellow) .....................17
LowBatteryLED(Red)................................17
PowerOutputs .....................................................18
CircuitProtection .............................................18
TotalAvailablePower ......................................18
ContinuousPowerOutputs ..............................18
ContinuousCurrentDraw .............................18
IncreasingCurrentOutput................................18
D8132BatteryChargerModule....................18
ProgrammablePowerOutputs .........................18
Programming ...............................................18
OptionalRelaysRequired ............................19
Terminals6 and 7........................................20
FireSystemPower Formula ........................20
Terminal8 ...................................................20
TelephoneConnections.......................................21
Registration .....................................................21
Notification ......................................................21
Location...........................................................21
PhoneCordConnection ...................................21
PhoneLED(Red).............................................21
OperationMonitorLED(Green)........................21
DialingFormat .................................................21
PhoneLineMonitor..........................................21
Phone Line Test Points ...................................22
CommunicationFailure ....................................22
GroundStart ....................................................22
RelayInstallation.........................................22
PhoneMonitorSelectJumper .....................22
D928DualPhoneLineSwitcher.......................22
Description ..................................................22
Operation ....................................................23
WatchdogFeature .......................................23
InstallingtheD928 ......................................23
D928 Status LEDs ......................................24
On-BoardPoints .................................................25
Description ......................................................25
PointSensor Loops .........................................25
PointParameters.............................................25
PointResponse Time ......................................25
Off-BoardPoints...................................................26
Point (ZONEX) Bus .........................................26
D8125POPEXModule
D8127andD9127POPITModules ..................26
InstallingtheD8125POPEX Module ...............28
WiringtheD8125totheD9412/D9112 .........28
Wiring POPITs to the
DataExpansionLoop ..................................28
Preface ................................................................... 2
FCCNotices ..................................................... 3
Part15 ......................................................... 3
Part68 ......................................................... 3
Introduction ........................................................... 7
Points............................................................... 7
Areas and Accounts ......................................... 7
Communicator .................................................. 8
CommandCenters ............................................ 8
Keyswitch......................................................... 8
Access Control ................................................. 8
Event Memory .................................................. 8
Event Log ......................................................... 8
EMI/LightningTransientProtection ................... 9
Programming .................................................... 9
OtherFeatures ................................................. 9
Control/CommunicatorAssembly...................... 9
OrderedSeparately ...................................... 9
ListingsandApprovals ....................................10
Fire..............................................................10
Burglary.......................................................10
Installation............................................................11
Beforeyoubegin .............................................11
EnclosureOptions ...........................................11
BeginningtheInstallation.................................11
MountingtheEnclosure...............................11
PremisesWiring ..........................................11
Installing the Assembly ...............................12
ConnectingEarthGround.................................12
Locking the Reset Pin .....................................12
Finishing the Installation ..................................12
Charge the Battery as You Finish................12
Install and Wire Detection Devices..............12
Install Modules and Relays .........................13
MaketheTelephoneConnections ...............13
ConnecttheOn-BoardPointsand
CommandCenters ......................................13
PowerUp ....................................................13
ProgrammingthePanel ...................................13
Install the Point Chart Label.............................13
Testing the System .........................................14
PowerSupply.......................................................15
PrimaryPower .................................................15
Primary(AC)PowerCircuit..........................15
InstallingtheTransformer............................15
SecondaryPower ............................................15
Secondary(DC)Power ................................15
Installing the Battery ...................................15
BatterySupervision .....................................16
BatteryChargingCircuit ..............................16
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 5
74-07692-000-C 4/97
WiringDataExpansion Loopsto
POPEXModules .........................................29
POPITSensorLoops ..................................29
POPIT Module Point Assignments ..............29
D8128COctoPOPITModule............................30
Description ..................................................30
Listing .........................................................30
Installing the OctoPOPIT ............................30
WiringOctoPOPITs.....................................31
LineTermination..........................................31
OctoPOPITSensorLoops...........................31
TestingOff-boardPoints..................................31
Off-BoardRelays ..................................................34
D8129OctoRelay ............................................34
ConfiguringtheD8129OctoRelay................34
RelayOutputs .............................................34
Installation...................................................34
WiringConnections .....................................34
D811Arm Status Relay Module.......................35
RelayOutput ...............................................35
Installation...................................................36
WiringConnections .....................................36
ArmingDevices ....................................................37
Description ......................................................37
CommandCenters ...........................................37
AssigningtheCommandCenter
anAddress..................................................37
Installation...................................................37
D268/D269IndependentZoneControl
D279IndependentZoneControl.......................38
Keyswitch........................................................39
Description ..................................................39
Programming ...............................................39
Installation...................................................39
KeyswitchOperation ...................................39
SDIDevices ..........................................................40
Description ......................................................40
Installation.......................................................40
D9131AParallelPrinterInterfaceModule ........40
Supervision .................................................40
Switch Settings ...........................................40
D9210BAccess ControlModule ..................41
Switch Settings ...........................................41
ProgrammerandAccessoryConnections..........42
ProgrammerConnector(J7) .............................42
ProgrammerAccessReports ......................42
AccessoryConnector(J2) ...............................42
D9412Faceplate ...................................................43
QuickReferenceTerminalDescription ...............44
TroubleshootingGuide........................................45
Introduction .....................................................45
Self Diagnostics ..............................................45
PhoneLineTrouble..........................................46
CommunicationsFailure ..................................47
ProblemsProgrammingthePanel ...................48
Problems with Points.......................................49
Extra Points ................................................49
Problems with the D8125 POPEX
DataExpansionLoops.....................................50
EMI .............................................................50
MeteringtheLoops......................................50
CheckingShieldedCable.................................50
EMIon Long Wire Runs...................................50
BatteryandPower Reports ..............................51
ProblemswithCommandCenters....................51
WatchdogResetReports.................................51
RunawayReportstotheReceiver....................52
OverloadedPowerSupply................................52
Service Walk Test ...........................................52
ApprovedApplicationsComplianceGuide ........54
ListingsandApprovals ....................................54
Fire..............................................................54
Burglary.......................................................54
Introduction .....................................................54
OptionalCompatibleEquipment.......................54
BurglaryApplications ..................................54
Bank Safe and Vault Applications ...............54
FireApplications .........................................54
Enclosures ..................................................55
System Chart ..................................................56
System Wiring Diagrams, Issue A ...................57
D9412Control/Communicator ......................57
D9112Control/Communicator ......................58
D7412Control/Communicator ......................59
D7212Control/Communicator ......................60
CurrentRatingChartforStandby
BatteryCalculations ........................................61
StandbyBatteryRequirements ........................62
HouseholdBurglaryand
CommercialBurglary ...................................62
Bank Safe and Vault ...................................62
CentralStation or Local Fire Alarm..............62
Remote Station or Auxiliary Fire Alarm........62
HouseholdFireWarningEquipment.............62
StandbyBattery Calculation for
NFPA 72 Fire Alarm Applications ....................63
CurrentChartFirst ...........................................63
Central Station or Local Systems ....................63
Remote Station or Auxiliary Systems ..............63
HouseholdFireWarningEquipment .................63
Specifications.......................................................64
Appendix:PointAddressChart...........................66
Bank 1, Points 9 - 127 .....................................66
Bank 2, Points 129 - 247 .................................67
♦♦
♦♦
♦
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 6
74-07692-000-C 4/97
Figures and Tables
Figure1:SystemConfiguration ..................................................................7
Figure 2:Enclosure Mounting ...................................................................11
Figure 3: Reset Pin .....................................................................................12
Figure4: ChargingandBattery LEDs........................................................ 17
Figure5:ConnectingD8132Modules ....................................................... 19
Figure 6: Relays for Terminals 7 and 8 and Ground Start ....................... 19
Figure 7: RJ31X Wiring ..............................................................................21
Figure8:TelephoneConnections ............................................................. 22
Figure 9: Phone Monitor Select................................................................. 22
Figure 10: D928 Dual Phone Line Switcher............................................... 23
Figure 11: On-board Point Sensor Loop Wiring....................................... 25
Figure 12: Connecting the D8125 POPEX to the Panel ............................ 27
Figure13: ProgramRecord Sheet .............................................................29
Figure14:D8128COctoPOPITs ................................................................. 32
Figure15:D8129OctoRelayConnections .................................................35
Figure 16: D811 Module Wiring ................................................................. 36
Figure17: PoweratCommandCenters .................................................... 38
Figure18:KeyswitchWiring ......................................................................39
Figure 19: Reset Pin ................................................................................... 42
Figure20:ProgrammerandAccessoryConnections .............................. 42
Figure 21:Service Walk TestFlow Chart .................................................. 53
Table1:CompatibleCommandCenters .....................................................8
Table2: DataExpansion LoopWire Specifications ................................. 28
Table3:D8128COctoPOPITSwitchSettings ........................................... 33
Table4:D8129 SwitchSettings ................................................................. 34
Table5:CommandCenterAddress Settings............................................ 37
Table6:CommandCenterConnections ................................................... 37
Table7:SDI DeviceConnections .............................................................. 40
Table8: PrinterAddress SwitchSettings ................................................. 40
Table9:Access ControlModuleAddressSwitch Settings ......................41
♦♦
♦♦
♦
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 7
74-07692-000-C 4/97
Introduction
Figure 1: System Configuration
Control/
Communicator
D8128C OctoPOPIT combines
8 POPIT Points in one module.
D8125 Interface for
D8127/D9127 POPITS
Points 9 - 127
D8129 OctoRela
y
provides
alarm and auxiliar
y
rela
y
output.
(
Other functions
available.
)
Use Command Centers and/or ke
y
switches to
arm the panel b
y
area. Each panel can have up
to 8 areas. Each area can have its own account
number or areas can be
g
rouped to
g
ether with
a common account number. Points of protection
are assi
g
ned to areas.
D928 module allows the
panel to monitor two
phone lines.
D8132 modules provide
additional power for control
centers and other powered
devices.
D9131A module
connects to a
parallel printer to
print event lo
g
.
On-board Points
1 to 8
♦
D9210B modules may be
used for access control.
(D9412/D7412 only)
PointsThe Radionics D9412/D9112 Control/
Communicator panel provides up to 246
separate points of protection, and the D7412/
D7212 Control/Communicator provides up to 75
points of protection. Point programming
parameters determine the panel’s response to
open and shorted conditions on the point’s
sensor loop. Points are programmed individually
with several options to custom-fit the protection to
your installation.
Points 1 to 8 are located on the circuit board (on-
board points). They are standard sensor loops.
The remaining off-board points are POPIT (Point
of Protection Input Transponder) points using
D8128C OctoPOPITs, D8125 POPEX (Point of
Protection Expander) modules and D9127/
D8127 POPITs .
Areas and Accounts
The system supports up to eight separate areas.
You can assign all points to a single area or
spread them out over up to eight areas.
You arm and disarm the panel by area. You can
arm and disarm several areas with one menu
function. You can also assign a passcode an
authority level that allows a user to arm an area
from a remote command center in another area.
Assigning each area its own account number
creates eight separate accounts in one panel.
Assigning the same account number to different
areas, groups them together in a single account.
Area options include: exit tone and delay,
separate fire and burglary outputs, and multiple
opening and closing windows. Area type can be
used to create area interdependencies.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 8
74-07692-000-C 4/97
Communicator
The Control/Communicator uses a built-in digital
communicator to send reports to the receiver. The
panel transmits reports in either the Modem IIIa2
TM or BFSK format. Your D6500 receiver's MPU
and line cards must have software revision 8.00
(or greater) installed to accept Modem IIIa2 TM
reports from the panel. Power your receiver down
and up to print the software revision numbers.
The panel connects to an RJ31X jack for phone
line seizure. Connection to the RJ31X complies
with FCC regulations for using the public
telephone network. You can program the panel to
direct reports to four separate phone numbers.
Adding the D928 Dual Phone Line Switcher
module allows you to connect and supervise a
second phone line.
The system has routing capabilities that allow you
to direct groups of event reports to four different
destinations. Each of the report groups can be
programmed to report to one or more of the
destinations. Primary and backup reporting paths
can be programmed for each of the destinations
and each of the report groups. A custom option
allows you to specify individual event reports to
be sent.
Command Centers
You can connect a maximum of 32 Command
Centers unsupervised to the system. The
available power, number of supervised
Command Centers, and number of areas you
intend to use, affect the total number of Command
Centers you can connect.
The system can supervise up to 8 Command
Centers. The panel transmits a serial device
trouble report, SDI FAILURE in the Modem IIIa2 TM
format or TROUBLE ZN D in the BFSK format, if it
loses communication with a supervised
Command Center. You can add more Command
Centers but only eight can be supervised. Table 1
shows the Command Centers compatible with the
D9000/D7000 Series Control/Communicators.
See
Command Center
in the
D9000/D7000
Series Program Entry Guide (74-07695-000)
for
complete details on programming Command
Center options.
Table 1: Compatible Command Centers
Keyswitch
You can arm and disarm any of the eight
available areas with maintained or momentary
closure devices such as keyswitches and sub-
control units (D279). Point programming
determines loop responses and which area a
keyswitch controls.
Access Control
The D9412 can control eight access doors (each
requiring the optional D9210B Access Control
Module) with up to 996 uniquely identified cards/
tokens. The D7412 can control two access doors
with up to 396 uniquely identified cards/tokens.
Access can be granted from a Weigand style
access control device (card reader) connected to
the D9210B Access Control Module. Access may
also be granted from a “request to enter” or a
“request to exit” input, or from a Command
Center.
The access control features of the D9412 and
D7412 can deny access during armed periods. It
can also grant access only to certain authorized
users depending on whether the area is master
armed, perimeter armed, or disarmed. The alarm
system can also be programmed to automatically
disarm when designated authorized users are
granted access.
Event Memory
The system uses event memory to store events
for each area. You can view the events for an
area at a D1255 Command Center assigned to
the area. The panel clears the events for an area
from event memory and starts storing new events
when you master arm the area.
Event Log
The system stores from 500 to 1000 events and
event modifiers from all areas in it's event log.
Event modifiers add information about an event
to the log. Some events are always followed by a
modifier. For example, the system adds at least
two items to the log each time you arm or disarm
an area, the open (or close) event and an event
modifier showing the previous arming state.
All events and their modifiers can be stored even
if the panel does not send a report for them. You
can view the log at a D1255 Command Center,
print it locally using the D9131A Parallel Printer
Interface and a parallel printer, or upload it to the
Remote Account Manager (RAM III).
See the appendix in the
User’s Guide
for a listing
of log events and event modifiers.
♦♦
♦♦
♦
Model Display Application
D1255 16-character alpha-numeric Fire/Burglary/Access
D720 8 LED Fire/Burglary
D1256 16-character alpha-numeric Fire
D1257 16-character alpha-numeric Fire
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 9
74-07692-000-C 4/97
EMI/Lightning Transient Protection
The D9000/D7000 Series Control/
Communicators maintain the Radionics high
level of quality and field dependability. Their
design significantly reduces electromagnetic
interference and malfunction generally caused by
lightning.
Programming
Use either the Radionics D5200 Programmer or
the Remote Account Manager (RAM III) to
program the D9000/D7000 Series Control/
Communicators. Refer to the
D9000/D7000
Series Program Entry Guide
(74-07695-000)
for
programming options.
Other Features
The D9000/D7000 Series Control/Communicator
have many programmable features. A short list of
some of the features follows. Complete details on
all the features can be found in the
D9000/D7000
Series Program Entry Guide
(74-07695-000)
.
• Supervision of AC (primary power), battery
(secondary power), ZONEX and SDI buses,
CPU (Central Processing Unit), up to 3
printers, and telephone lines
• Automatic system test reports
• Remote access for programming, diagnostics,
and log uploads using the Remote Account
Manager (RAM III)
• Fire Alarm Verification
• Programmable Alarm Output
• Programmable Relay Output using the D8129
OctoRelay Module
• Opening and Closing Windows
• Skeds (scheduled events)
Control/Communicator Assembly
The Radionics Control/Communicator is shipped
pre-assembled from the factory. You should
receive the following parts with your panel.
Literature Pack
•
D9000/D7000 Installation and
Troubleshooting Quick Reference
(33317)
•
D9412/D9112 Program Record Sheet
(74-
07697-000), or
D7412/D7212 Program
Record Sheet
(34583)
•
UL Smoke Detector Compatibility
Technogram
(33284)
•
Point Chart Label
(79-06660-000)
• Eight D105BL 1k W end-of-line resistors
• Two 14", 18 AWG, color-coded battery leads
Assembly:
• PC board
• Faceplate shield
• Mounting Skirt
• One #6x1/4" screw
OrderedSeparately
Order the following to complete a basic 8 point
installation.
• D1255 or D720 Command Center (or
keyswitch)
• D1640 Transformer
• D126 Battery
• D161 or D162 Phone Cord (order two cords if
you are using the D928 Dual Phone Switcher)
• D8103, D8108A, or D8109 Enclosure
Configured packages are also available. Please
consult your Radionics Product Catalog.
The following literature is available in a separate
literature package for dealers.
• D9000/D7000 Series Operation and
Installation Manual (74-07692-000)
• D9000/D7000 Series Approved Applications
Compliance Guide (74-07693-000)
• D9000/D7000 Series Program Entry Guide
(74-07695-000)
• D9412/D9112 Program Record Sheet (74-
07697-000), and D7412/D7212 Program
Record Sheet (34583)
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 10
74-07692-000-C 4/97
Listings and Approvals
The D9000/D7000 Literature Pack includes the
D9000/D7000 Series Approved Applications
Compliance Guide
(74-07693-000). Refer to this
guide for additional guidelines for installing the
Control/Communicator in UL and Fire specific
applications.
Fire
UL
Underwriters Laboratories lists the D9412, D9112,
D7412, and D7212 Control/Communicators as
Signal System Control Unit for: Central Station,
Local, Auxiliary, Remote Station, and Household
Fire Warning.
CSFM
Approved by the California State Fire Marshal for
residential and highrise.
NYC-MEA
Approved by New York City's Materials and
Equipment Acceptance System (requires red
enclosure).
Factory Mutual (FM)
Approved by Factory Mutual.
BSA
Not listed.
Burglary
UL
Underwriters Laboratories lists the D9412, D9112,
D7412, D7212 Control/Communicators for:
Central Station, Local, Police Connect, Bank Safe
and Vault, Mercantile Safe and Vault, and Grade A
Household systems, Access Control, and
Proprietary.
Department of Defense (DOD)
The D9412, D9112, D7412, and D7212 have
been granted approval for Department of
Defense (DOD) installations in Sensitive
Compartmented Information Facilities (SCIF).
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 11
74-07692-000-C 4/97
Installation
Before You Begin
This
Installation
section contains a general
installation procedure. It refers you to other
sections of the manual for detailed instructions.
Radionics recommends you review this manual
and the
D9000/D7000 Series Program Entry
Guide
(74-07695-000) before you begin the installation
to determine the hardware and wiring
requirements for the features you want to use.
Have the following additional documents handy
as you read through this manual:
•
D9412/D9112 Program Record Sheet
(74-
07697-000) or
D7412/D7212 Program
Record Sheet
(34583)
•
D9000/D7000 Series Approved Applications
Compliance Guide
(74-07693-000)
•
User’s Guide
(74-06141-000) and
User’s
Guide Supplement
(33267)
•
D1255 Command Center Installation
Manual
(74-06118-000) or
D720 Command
Center Installation Manual
(74-06935-000)
Before you begin the installation of the D9412/
D9112 you should be familiar with the operation
of the D5200 programmer or the Remote Account
Manager (RAM III).
Enclosure Options
Mount the Control/Communicator assembly in
any of the Radionics enclosures listed below.
Refer to the
D9000/D7000 Approved
Applications Compliance Guide
(74-07693-000)
to determine if your application requires a
specific enclosure.
• D8103 Universal Enclosure (tan)
• D8109 Fire Enclosure (red)
• D8108A Attack Resistant Enclosure (tan)
Beginning the Installation
MountingtheEnclosure
Mount the enclosure in the desired location. Be
certain to use all five mounting holes. See Figure
2.
PremisesWiring
Run the necessary wiring throughout the
premises and pull the wires into the enclosure.
EMI (Electro Magnetic Interference) may cause
problems:
EMI may occur if you install the
system or run system wires near the following:
• Computer network system
• Electrical lines, fluorescent fixtures or
telephone cabling
• Ham radio transmitter site
• Heavy machinery and motors
• High voltage electrical equipment or
transformers
• PBX telephone system
• Public service (police, fire departments, etc.)
using radio communications
• Radio station transmitter site, or other
broadcast station equipment
• Welding shop
If you think that EMI may be a problem, use
shielded cable. The drain wire for the shielded
cable must have continuity from terminal 10 on
the panel to the end of the wire run. If continuity is
not maintained, the shielded cable may
aggravate potential noise problems rather than
eliminate them.
Connecting the drain wire to ground at other than
terminal 10 may also produce problems. If you
cut the drain wire to install devices be certain to
splice it together. Solder and tape all splices.
POINT CHART LABEL MOUNTING
SKIRT HOOK
MODULE MOUNTING
LOCATIONS
MODULE
MOUNTING
LOCATIONS
TAMPER SWITCH
MOUNTING LOCATION
MOUNTING
SKIRT HOOK
SKIRT MOUNTING HOLE
BACK OF D9412
MOUNTING
SKIRT HOOK
OPENINGS
LOCK DOWN TAB
Figure2: Enclosure Mounting
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 12
74-07692-000-C 4/97
Installing the Assembly
1. Place the assembly over the inside back of
the enclosure, aligning the large rectangular
openings of the mounting skirt with the
mounting hooks of the enclosure. Slide the
assembly down so it hangs on the hooks.
See Figure 2.
2. Remove the tape from the #6x1/4" screw in
the mounting tab on the assembly. The
screw passes through the mounting tab and
into the skirt mounting hole in the enclosure.
Tighten the screw to secure the assembly in
the enclosure.
3. Connect earth ground to the panel before
making any other connections. See
Connecting Earth Ground
below
.
Connecting Earth Ground
Terminal 10
To help prevent damage from electrostatic
charges or other transient electrical surges,
connect the system to earth ground at terminal 10
before making any other connections. A
grounding rod or cold water pipe are
recommended earth ground references.
Do not use telephone or electrical ground for
the earth ground connection
. Use 14-16 AWG
wire when making the connection. Do not
connect any other panel terminals to earth
ground.
Locking the Reset Pin
Locking the Reset Pin disables the panel. See
Figure 3. The system ignores the Command
Centers and points while disabled. CALL FOR
SERVICE appears in Command Center displays
while the pin is locked down.
On-board relays (terminals 6, 7, and 8) and off-
board relays, deactivate when the panel is reset.
There is power at terminal 8 when the relay is
deactivated. Activation interrupts power at that
terminal. The relays remain deactivated while the
Reset Pin is locked in the disable position.
Releasing the reset pin from the closed position
resets the panel. The panel resets all its timers,
counters, indexes, and buffers.
If you place the reset pin in the disable position
when all areas are armed, there must be an entry
in the
Answer Armed
program item. See
RAM
Parameters
in the
D9000/D7000 Series Program
Entry Guide
(74-07695-000).
Locking the pin in the disable position allows you
to power up the panel and charge the battery as
you install the detection devices and Command
Centers.
FinishingtheInstallation
Earth ground and reset pin first:
Make the earth
ground connection to terminal 10 and lock the
reset pin in the closed position if you haven’t
already done so.
ChargetheBattery asYouFinish
Connect the battery and then the transformer so
that the panel can charge the battery as you
finish the installation. See the
Power Supply
section for instructions.
On-board Buzzer Sounds at Power Up and
Reset:
The system performs a series of self
diagnostic tests of its hardware, software, and
program at power up and at reset. The buzzer on
the panel sounds during the tests. They take
about 1-3 seconds to complete.
If the panel fails any of the tests, the buzzer
continues sounding and a system trouble
message appears at the Command Centers. See
Self Diagnostics
in the
Trouble Shooting
section
for a description of each system trouble message.
Touch Terminal 10 first:
If the on-board buzzer
sounds briefly when you touch the panel, you're
discharging any static charge you may be
carrying to the panel. The panel may generate
WATCHDOG RESET and/or PARAM FAIL events.
See the
Trouble Shooting
section for a
description of these events. Always touch
terminal 10, the panel's earth ground connection,
before beginning work on the panel.
InstallandWireDetectionDevices
Install and wire detection devices and Command
Centers at their locations throughout the
premises. DO NOT make the connections at the
panel end of the wiring yet.
The
On-Board Points
section of this manual
contains instructions for wiring the on-board
points to detection devices. The
Arming Devices
section contains instructions for wiring the
Command Centers.
Operation Monitor
Pulses When Normal
Flickers When Ringing
32
COMMON -
31
30
29
GRN
RESET PIN
LOCKED (CLOSED)
RESET PIN
NORMAL (OPEN)
Reset Pin
Disable All Except Battery
Charging and Local Programming
DATA BUS B
DATA BUS A
POWER +
BLACK
GREEN
YELLOW
RED
Figure 3: Reset Pin
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 13
74-07692-000-C 4/97
Instructions for wiring the off-board point POPIT
sensor loops are found in the instructions
packaged with the POPIT modules.
InstallModules and Relays
1.
Power Down First:
Power down the unit by
unplugging the transformer and
disconnecting the battery. Radionics
recommends that you power down the unit
when installing modules or relays, or when
making wiring connections to the panel.
2. Install and wire any modules required for
your installation as described in the
module’s installation instructions.
Instructions for the D8125 POPEX Module,
the D8128C OctoPOPIT Module, the D8129
OctoRelay Module, the D811 Arm Status
Relay Module, and the D928 Dual Phone
Line Switcher appear in this manual.
See
Off-board Points
for D8125 and D8128C
instructions. See
Relays
for D8129 and
D811 instructions. See
Dual Line
Transmitting
in the
Telephone Connections
section for instructions for the D928.
3. If you are using the power outputs at
terminals 7 or 8, install a D136 relay in the
appropriate sockets. See
Programmable
Power Outputs
in the
Power Outputs
section
for instructions.
4. If you are using a ground start phone system,
insert a D136 relay in socket K6/J5 and set
the ground start pin in the ground start
position. See
Ground Start
in the
Telephone
Connections
section.
MaketheTelephoneConnections
See
Telephone Connections
. If you are
connecting the panel to a ground start phone
system, you need to install D136 relay, see
Install
Modules and Relays
above.
ConnecttheOn-BoardPointsandCommand
Centers
Connect the on-board points and Command
Center wiring to the system. See the
On-Board
Points
and
Arming Devices
sections for
instructions.
PowerUp
Reconnect the battery and then plug in the
transformer. Remember the buzzer sounds for 2
seconds when you first power up the panel.
Leave the reset pin locked down for now.
Yellow Charging Status LED doesn’t go out:
If
the yellow charging status LED doesn’t go out
within 5 minutes of powering up the panel, the
battery may be deeply discharged, or you may
have connected too many powered devices to
the panel. Combined continuous current draw for
terminals 3, 8, 24, and 32, the Accessory
Connector (J2), and the Expansion Port (J4)
cannot exceed 1.4A. See the
Power Outputs
section for help.
Programming the Panel
If you haven’t created a program for the panel,
review the
D9000/D7000 Series Program Entry
Guide
(74-07695-000). Check to be certain you
have all the required accessory modules
installed for the features you want to use. The
reset pin must be in the locked position to copy or
send information to and from the panel.
Use the D5200 Programmer or the Remote
Account Manager (RAM III) to load your custom
program into the panel.
Move the reset pin to the normal position. See
Figure 3. The panel transmits reboot and battery
reports to the receiver if programmed for
reporting.
Install the Point Chart Label
Radionics recommends you fill out the
Point
Chart Label
(79-06660-000) provided in the
literature pack and install it on the inside of the
enclosure door for all systems.
Point chart label required for fire systems with
verification points:
You must install the point
chart label for fire or combined fire/burglary
systems using verification points.
Use the program record sheet to gather the
information you need to fill out the point chart.
Install the label on the enclosure door as shown
in Figure 2. To avoid smearing your entries on
the chart, use the label's peel off backing to press
the label in place.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 14
74-07692-000-C 4/97
Testing the System
After finishing the installation and programming
of the panel, make a complete functional test of
the system. Test the panel and all devices for
proper operation. Test after you first program the
panel and after any subsequent programming
session.
Service Walk Test shows extra points:
Use the
service walk test at a panel wide Command
Center to perform a complete test of the panel.
The service walk test function is similar to the
ordinary walk test function, with the additional
ability to display points that are not properly
programmed.
If you test a POPIT with it’s switches set for a point
with a blank point index and/or no area
assignment, it appears as an extra point during a
Service Walk Test.
If you test a device, and the panel doesn’t
respond, there may be a problem with the device,
the wiring, the POPIT ID setting, or the
programming for the point. If you incorrectly set
the switches on a POPIT, you may create both a
missing and extra point. When you find a missing
point, performing a service walk test for extra
points may help diagnose the problem.
See the
Trouble Shooting Section
of this manual
for complete service walk test instructions.
Clear after test:
To clear the event memory and
report buffer, momentarily close the reset pin.
Events stored in the panel's event log are not
cleared.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 15
74-07692-000-C 4/97
Power Supply
Primary Power
Terminals 1 2
Primary(AC)PowerCircuit
A 16.5 VAC, 40 VA internally fused transformer
(Radionics model D1640) is the primary power
source. The AC power circuit provides 1.9 Amps
of rectified AC power. The panel reserves 500
mA of this power for internal operations leaving
1.4 Amps for powered devices.
Transient suppressors and spark gaps protect the
circuit from power surges. This protection relies
on the ground connection at terminal 10. Make
sure you connect terminal 10 to a proper ground.
See
Connecting Earth Ground
in the
Installation
section
.
AC Power Failure
The system indicates an AC power failure when
the power at terminals 1 and 2 is missing. The
AC Fail Time
program item sets the number of
seconds that AC must be missing before the
panel acknowledges the failure and the number
of seconds after the power returns before the
panel acknowledges the restoral of power.
You can program
AC Fail Time
from 1 to 90
seconds. The Radionics default sets
AC Fail
Time
at 15 seconds.
InstallingtheTransformer
Do not short the terminals of the transformer:
Shorting the terminals opens the internal fuse
causing permanent failure. Connect the
transformer to terminals 1 and 2 of the panel
before plugging it into the power source.
Use 18 AWG (minimum) wire to connect the
transformer to the panel. Wire length should be
kept as short as possible. Maximum length is 50
feet.
AC wiring can induce both noise and low level
voltage into adjacent wiring. Route phone and
sensor loop wiring away from any AC conductors,
including the transformer wire. Route data wiring
away from AC and phone wiring.
Connect the battery and then plug in the
transformer:
Radionics recommends that you
always connect the battery first and then plug in
the transformer. Instructions for
Installing the
Battery
appear on the next page.
Only plug the transformer into an unswitched,
120 VAC, 60 Hz power outlet. Secure the
transformer to the outlet with the screw provided.
D8004 Transformer Enclosure required for fire
systems:
Use the D8004 Transformer Enclosure
for the D1640 transformer in fire and combined
fire/burglary applications. Check with AHJ on
mounting transformers on specific circuits.
Secondary Power
Terminals 45
Secondary(DC)Power
A 12V, 7 Ah (up to 14 Ah) sealed lead-acid
rechargeable battery (D126) supplies secondary
power for auxiliary and alarm outputs, and
powers the system during interruptions in primary
(AC) power.
Lead Acid Batteries ONLY:
The charging circuit
is calibrated for lead-acid batteries. Do not use
gel-cell or nicad batteries.
Extra Batteries Increase Back-up Time:
To
increase battery back-up time, connect a second
12V, 7 Ah battery in parallel to the first battery to
form a 12V, 14 Ah battery. Use a D122 Dual
Battery Harness to ensure proper and safe
connection.
InstallingtheBattery
Place the battery upright in the base of the
enclosure. Locate the red and black leads
supplied in the literature pack. Connect the black
battery lead to terminal 4, and then to the
negative (-) side of the battery. Connect the red
battery lead to terminal 5, and then to the positive
(+) side of the battery.
Warning, High Current Arcs Possible:
The
positive (red) battery lead and Terminal 5 can
create high current arcs if shorted to other
terminals or the enclosure. Use caution when
working with the positive lead and terminal 5.
Always disconnect the positive (red) lead from
the battery before removing it from terminal 5.
Replacement
Radionics recommends battery replacement
every 3 to 5 years under normal use. Exceeding
the maximum output ratings, or installing the
transformer in an outlet that is routinely switched
off, causes heavy discharges. Routine heavy
discharges can lead to premature battery failure.
Record the date of installation directly on the
battery.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 16
74-07692-000-C 4/97
D8132 boosts battery backup:
Adding a D8132
Battery Charger Module supports additional
batteries of up to 36 Ah capacity if required.
Failure to add a D8132 will cause situations that
create false alarms and differential voltage levels.
You can use the D8132 Battery Charger Module
to connect two additional batteries for a total of
four. The panel plus any connected D8132
modules and AUX power supplies must be on the
same AC circuit so they will discharge evenly if
AC power fails. The number of D8132 modules is
determined by the number of available outlets on
the same circuit. See the
Standby Battery and
Current Rating Chart
in this manual for battery
standby time calculations. Note: Dual batteries
are required for fire applications.
WARNING:
Do not connect the D8132 module to
the panel’s battery terminals 4 and 5. Always
connect to AUX outputs (see Figure 5 on page
23).
BatterySupervision
When the battery voltage drops to 13.8 VDC, the
yellow Charging Status LED lights. When the
battery drops to 12.1 VDC the red Low Battery
LED lights and the panel, if programmed for
power supervision, transmits a BATTERY LOW
report in the Radionics’ Modem IIIa2™
Communication Format. It transmits a TROUBLE
ZN 9 report in the BFSK format.
If the battery is missing or shorted, the red Low
Battery LED flashes at the same rate as the green
Operation Monitor LED. If the panel is
programmed for power supervision, it transmits a
BATTERY MISSING report in the Radionics’
Modem IIIa2™ Communication Format, or
TROUBLE ZN 9 report in the BFSK format.
When battery voltage returns to 13.7 VDC the
Low Battery LED goes out. If the panel is
programmed for power supervision, it transmits a
BATTERY RESTORAL report in the Radionics’
Modem IIIa2™ Communication Format or
RESTORAL ZN 9 report in the BFSK format. At
13.9 VDC the Charging Status LED goes out.
Investigate low battery reports immediately
: If
primary (AC) power is off and the discharge
continues, the panel becomes inoperative when
the battery voltage drops below 10.2 VDC.
BatteryChargingCircuit
Float Charge
The float voltage for the battery charging circuit is
13.5 to 13.9 VDC at a maximum current of 1.4
Amps. If float voltage drops lower than 13.5 VDC,
the Charger LED will illuminate.
Loss of AC Load Shed Relay protects battery:
During an AC power loss the battery supplies all
power to the security system. If the battery voltage
falls below 10.2 volts during an AC power loss, a
“load shed” relay isolates the battery from the
panel and disables the panel. Load shed protects
the battery from being damaged by deep
discharge. When AC power restores, the load
shed relay resets and battery voltage is again
available.
Overcharge Load Shed With AC Present:
If
more than 1.4 amps from the panel is detected,
the panel shuts down. Remove all loads to the
panel and disconnect AC power. Add a new
battery and reconnect AC power.
Reset the panel by momentarily placing the reset
pin in the disable position. See Figure 3. The red
Low Battery LED continues to flash until you reset
the panel.
A shorted battery condition is created either by a
shorted cell inside the battery or by a short on
terminals 4 and 5. A shorted battery may
generate WATCHDOG RESET reports.
BatteryDischarge/RechargeSchedule
Discharge Cycle
ACOFF AC fail report when AC fails if panel
is programmed to report AC failure
at occurrence.
13.9 VDC Charging float level
13.8 VDC Charging Status LED on
12.1 VDC Low Battery & AC fail reports if
programmed; Low Battery LED on
10.2 VDC Battery load shed (processing
functions continue if AC is present)
Recharge Cycle
AC ON Load shed relay resets, battery
charging begins, battery trouble and
AC restoral
reports sent.
13.7 VDC Battery restoral reports sent, Low
Battery LED off
13.9 VDC Charging Status LED off, battery
float charged
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 17
74-07692-000-C 4/97
Charging Status and Low Battery LEDs
ChargingStatusLED(Yellow)
The yellow LED shows the charging status of the
battery. Figure 4 shows its location.
Figure 4: Charging and Battery LEDs
•Yellow LED flashing once per minute
The yellow LED normally flashes once per
minute as the system checks the battery.
•Yellow and red LEDs flashing once per
minute
The yellow and red LEDs flash on once
every minute when current draw for devices
connected to the power outputs exceeds 1.4
Amps and the battery is missing.
LowBatteryLED(Red)
The red LED shows the condition of the battery.
Figure 4 shows the location of the LED.
Low Battery
•Red LED off
The red LED is off when the battery is fully
charged. When battery voltage drops below
12.1 VDC, the red LED comes on. It goes
out when battery voltage reaches 13.7 VDC.
•Red LED on
A steadily lit red LED indicates battery
voltage has fallen below 12.1 VDC. The
LED goes out when battery voltage reaches
13.7 VDC.
Missing Battery
•Red LED flashing (same rate as green
LED)
The red LED flashes with the green
Operation Monitor LED when the battery is
missing or shorted.
Missing Battery and Over Current
•Red and yellow LEDs flashing once per
minute
The yellow and red LEDs flash once every
minute when current draw for devices
connected to the power outputs exceeds 1.4
Amps and the battery is missing.
•YellowLED off
The yellow LED is off when the battery is
fully charged.
LED off when battery is missing, shorted,
or reversed:
The charging LED is off when
the battery is missing, shorted, or reversed,
but the red Low Battery LED is flashing.
•Yellow LEDon
A steadily lit yellow LED indicates the
battery float voltage is below 13.8. If AC is
present the battery is charging.
The yellow LED also comes on when the
combined current draw from all outputs
exceeds 1.4 Amps. This is normal under
alarm conditions for non-fire systems when
sirens or bells draw more than 1.4 Amps. If
the LED comes on regularly for extended
periods or doesn’t go out, check the current
draw for devices connected to the power
outputs. See the
Power Outputs
section in
this manual for instructions.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 18
74-07692-000-C 4/97
Power Outputs
Circuit Protection
Three self-resetting thermal circuit breakers
protect the panel from short circuits on both the
continuous and programmable power outputs.
The circuit breakers are thermal rated and open
at 3 to 5 Amps. If the panel is programmed for
power supervision and short is sustained on one
of the power outputs, the panel transmits a
BATTERY LOW or BATTERY MISSING for
Radionics’ Modem IIIa2™ Communication
Format, or TROUBLE ZN 9 for BFSK.
One thermal circuit breaker protects Terminal 3 -
Auxiliary Power and Terminal 24 - ZONEX Power
and the Expansion Port (J4). A short on one
disrupts the power to the others.
One breaker protects Terminal 6 - Alarm Power
Output, Terminal 7 - Alternate Alarm Power
Output, and Terminal 8 - Switched Auxiliary
Power. A short on one of these terminals disrupts
the power to the other two.
One circuit breaker protects terminal 32 - Power
+.
Total Available Power
The system produces up to 1.4A of combined
power at 10.2 VDC to 13.9 VDC for all powered
devices. The outputs listed below share the
available power. These outputs are shown as red
circles on the face plate.
Terminal 3 - Auxiliary Power. Use this terminal
to power devices requiring continuous power. To
increase output by 1.4 amps, connect a D8132
module to this terminal.
Terminal 6 (Relay A) - Alarm Power Output.
Normally open, power on alarm.
Terminal 7 (Relay B) - Alternate Alarm Power
Output. Normally open, power on alarm.
Terminal 8 (Relay C) - Switched Auxiliary
Power. Normally open, power off on reset.
Terminal 24 - ZONEX Power. Use this terminal to
power ZONEX modules such as the D8125,
D8128C, and D8129 modules. To increase
output by 1.4 amps, connect a D8132 module to
this terminal.
Terminal 32 - Power +
Use this terminal to power SDI (Serial Device
Interface) devices such as command centers, the
D9131A Parallel Printer Interface, and the
D9210B Access Control Interface. To increase
output by 1.4 amps, connect a D8132 module to
this terminal.
Accessory Connector (J2)
The D928 Dual Phone Line Switcher connects to
J2.
Expansion Port (J4)
The Expansion Port is reserved for future use.
Continuous Power Outputs
Terminals 3 24 32
J2 J4
ContinuousCurrentDraw
The continuous current draw for powered
devices connected to terminals 3, 8, 24, and 32,
the Expansion Port (J4), and the Accessory
Connector (J2) must not exceed 1.4A . Devices
powered from these outputs must operate over a
range of 10.2 VDC to 13.9 VDC.
Power restricted for fire and combined fire/
burglary systems:
Use the
Fire System Power
Formula
to calculate the current available for fire
and combined fire/burglary systems. See
Programmable Power Outputs
.
Increasing Current Output
D8132BatteryChargerModule
The D8132 Battery Charger Module increases
total output from 1.4 amps to 2.8 amps. Up to four
D8132 modules can be connected to the panel.
Figure 5 shows the terminal connections for the
D8132 modules.
Warning: Do not connect a D8132 module to the
battery terminals 4 and 5. Ensure AC power for
the panel and all connected D8132 modules is
on the same circuit.
Programmable Power Outputs
Terminals 6 7 8
Programming
The power outputs at terminals 6, 7, and 8 are
programmed as relays A, B, and C. All relays are
programmed in the
Relays
module of the
program. Relays are assigned a relay type, Fire
Bell for example, when they are assigned to an
area. Relays can be assigned to one or more
areas.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 19
74-07692-000-C 4/97
The Radionics defaults set relay A (terminal 6)
as a Steady Alarm Bell output and relay A
(terminal 7) as a Pulsed Fire Bell output, and
relay C (terminal 8) as a Verification/Reset
output for smoke detectors. The
D9000/D7000
Series Program Entry Guide
(74-07695-000)
contains complete instructions for programming
relays. Descriptions of the functional
characteristics of each terminal appear on the
next page.
See the
Bell Parameters
section of the program
to set the Fire Bell, Alarm Bell output responses
for relays. Four annunciation patterns: Steady,
Pulsed, California Standard, and Temporal Code
3 are available.
Unexpected Output at Terminals 6, 7 and 8:
If
terminals 6, 7, and 8 don’t provide the output you
expect:
• Check the programming for relays A, B, and
C in the
Relays
module of the program.
• Check the
Bell Parameters
section of the
program to verify the Alarm and Fire Bell
responses are programmed for the duration
and pattern you expect.
• Check the
Point Assignments
to verify each
point is programmed for the local response
you expect.
Figure 5: Connecting D8132 Modules
5
9
10
1
2
Low Battery
LEDs Off Wh en No rmal
EARTH GROUND
COMMON
CLAS S 2 TRANSFORMER
16.5 VAC 40 VA 60 H Z
PartNo.D1640
Internally Fused - Do N ot Short
Requires Un switched Outlet
Do Not Share With OtherEquipment
+ AUX POWER
BATTERY NEGATIVE O NLY
Maximum Charging
Current 1.4 Amps.
PHONE MONITOR SELECT
Loop Start
Ground Start
TELCO
CORD PHONE
LED
ON WHEN
COMMUNICATING
OFF WHEN IDLE
Requires
Relay
#D136
ON-BOARD POINTS
1.0K Resistor
Required at End ofLine
Ω
VOLTAGE RANGES
Open 3.7 - 5.0VD C
Normal 2.0 - 3.0VDC
Short 0.0 - 1.3VDC
PERIPHERAL DEVICE WIRING
ZONEX OUT 1
ZONEX IN 1
ZONEX OUT 2
ZONEX IN 2
ZONEX POWER +
ZONEX COMMON
Operation Monitor
Pulses When Normal
Flickers When Ringing
PROG
CONN
RED
YELLOW
GREEN
BLACK
17-05823-002
32
POWER +
DATA BUS A
COMMON
RE D
GROUND
START
YE L
RED
Reset Pin
Disable All Except Battery
Charging And Programming
GR N
STEADY O R
PULSE
+
Ch ar g ing S t at us
N.F.P.A.
Style 3.5
Signaling
Line
Ci r cu i t s
12 15 18 2113
11
14 16 17 19 20 22
PROGR AMMABLE
AL A RM O U T PU TS
Terminals
&
Req ui re
Opti onal
D136 Relay
in J1 & J9
7
Point 1 Point2 Point 3 Point4 Point5 Point 6 Point 7 Point 8
DATA BUS B
29
31
30
24
23
28
27
26
25
BATTERY POSITIVE ONLY
+ALTERNATE
SWITC HED
AUX POWER
+
6
7
8
8
3
4
(
+
)
(
-
)
3
4
8
9
(
+
)
(
-
)
32
29
D8132
1.4 Amps
(
+
)
(
-
)
24
23
D8132
1.4 Amps
(
+
)
(
-
)
D8132
1.4 Amps
D8132
1.4 Amps
1.4 Amps
NOTE
: Combined Total Dispersed
Current of 7.0 amps @ 12 VDC
M
Aromat
DS2E-M- DC12V
MArom at
DS2E-M-DC12V
M
Arom at
DS2E-M-DC12V
J
K3/
J1
K1/
J9
GND START
K6/
J5
TOP
L
E
F
T
BOTTOM
NOTE: The D136
relays are inserted
with the three pins
on the top side.
Figure 6: Relays for Terminals 7 and 8
and Ground Start
OptionalRelaysRequired
Install an optional D136 plug-in relay into socket
J1 to enable the output at terminal 7. Install a
D136 in socket J9 to enable the output at terminal
8. The relay sockets are under the faceplate as
shown in Figure 6.
www.PDF-Zoo.com
firealarmresources.com

D9000/D7000 Series Operation & Installation Manual
Page 20
74-07692-000-C 4/97
Relay Installation
Power down the system before inserting the
D136 relays. The plug-in relays are shorter than
the sockets they plug into. See Figure 6. You can
install them in either the left or right end of the
socket.
Don’t rely on relay labelling:
You shouldn’t rely on the labelling to install D136
relays. Check for the side with three pins. The
three pins go on the top side.
Incorrect insertion does not damage the relay or
the system, however the related circuits do not
function properly.
Terminals 6 and 7
Terminals 6 (relay A) and 7 (relay B), provide
positive (+) 10.2 VDC to 13.9 VDC power output
when activated. Use the power at terminals 6 and
7 to power bells, siren drivers, piezo fire
sounders, electronic horns, or other devices.
Programming determines the format of the output
and the conditions that activate it. One self-
resetting circuit breaker protects terminals 6, 7,
and 8 against shorts.
Available Power
The system combines the 1.4A of primary power
produced by the power supply with the
secondary power source (the battery) to produce
a total of 2.0A of alarm power at 10.2 to 13.9
VDC. Terminals 6 and 7 share the available
alarm power.
Power restricted for fire and combined fire/
burglary systems:
Fire systems are prohibited
from using the battery for determining alarm
power. Use the
Fire System Power Formula
below to calculate the current available for fire
and combined fire/burglary systems.
Fire System Power Formula
To calculate the current available at terminals 6
and 7 for fire and combined fire/burglary systems:
1. Add together the current draws for all
devices connected to terminals 3, 8, 24, and
32, the Expansion Port (J4), and the
Accessory Connector (J2). This total is the
total current required for the Normal Standby
Condition (NSC).
2. The current available for Normal Standby
Condition (NSC) is 1.4A. Subtract the NSC
current required calculated in step 1 from the
NSC current available, 1.4A. The difference
is the Alarm Current available for terminals 6
and 7.
In formula format:
1.4A – NSC current required (step 1) = Alarm
Current available
Refer to the Battery Standby Chart in the
D9000/
D7000 Series Approved Applications
Compliance Guide
(74-07693-000) for module/
accessory current requirements.
Terminal 8
Terminal 8 provides continuous positive (+) 10.2
VDC to 13.9 VDC power. Relay C interrupts the
power at terminal 8 when activated. Use terminal
8 to power smoke detectors or other devices that
are reset by interrupting power. One self-resetting
circuit breaker protects terminals 6, 7, and 8
against shorts.
Verification/Reset Relay
The default program sets relay C (terminal 8) as a
verification/reset relay. See the
Relay Parameters
and
Point Assignments
modules in the
D9000/
D7000 Series Program Entry Guide
(74-07695-
000) for instructions on programming verification/
reset relays and points.
Performing a Sensor Reset at a Command
Center produces a 5 second relay activation of
verification/reset relays. The panel ignores
verification/reset points during the 5 seconds of
relay activation.
www.PDF-Zoo.com
firealarmresources.com
Other manuals for D9000 Series
2
This manual suits for next models
7
Table of contents
Other Radionics Control System manuals