Radionics D2212 User manual

74-07361-000-C 11/11/96 © 1995-1996 Radionics
D2212 Control/Communicator
Installation Manual
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 2
© 1996 Radionics
74-07361-000-C 11/11/96
Notice
The material and instructions covered in this manual have
been carefully checked for accuracy and are presumed to be
reliable. However, Radionics, Inc. assumes no responsibility
for inaccuracies and reserves the right to modify and revise
this manual without notice.
If a discrepancy is found in this documentation, please mail a
photocopy of the corrected material to:
Technical Communications
c/o Radionics, Inc.
1800 Abbott Street
P.O. Box 80012
Salinas, CA 93912-0012
© 1996 Radionics, Inc., Salinas, CA, U.S.A.
All rights reserved.
FCC Notices
Part 15
This equipment generates and uses radio frequency energy.
If not installed and used in accordance with the
manufacturer’s instructions, it may cause interference to
radio and television reception. It has been tested and found
to comply with the specifications in Part 15 of FCC rules for
Class B Computing Devices.
If this equipment causes interference to radio or television
reception, which can be determined by turning the
equipment on and off, the installer is encouraged to correct
the interference by one or more of the following measures:
1) Reorient the antenna of the radio/television. 2) Connect
the AC transformer to a different outlet so the control panel
and radio/television are on different branch circuits. 3)
Relocate the control panel with respect to the radio/
television.
If necessary, the installer should consult an experienced
radio/television technician for additional suggestions, or send
for the “Interference Handbook” prepared by the Federal
Communications Commission. This booklet is available from
the U.S. Government Printing Office, Washington D.C.
20402, stock number 004-000-00450-7.
Part 68
This equipment complies with Part 68 of FCC rules. A label
contains, among other information, the FCC registration
number and ringer equivalence number (REN).
Radionics registered the D2212 Control/Communicator for
connection to the public telephone network using an RJ38X
or RJ31X jack.
Use the ringer equivalence number (REN) to determine the
number of devices you can connect to the telephone line.
Excessive RENs on the telephone line may result in devices
not ringing in response to an incoming call. In most, but not
all areas, the sum of the RENs should not exceed five (5).
Contact the telephone company to determine the maximum
REN for the calling area.
If the D2212 Control/Communicator causes harm to the
telephone network, the telephone company will notify you in
advance. If advance notice isn’t practical, the telephone
company will notify the customer as soon as possible. Also,
you will be advised of your right to file a complaint with the
FCC if you believe it is necessary.
The telephone company may make changes in its facilities,
equipment, operations, or procedures that could affect the
operation of the D2212. If this happens, the telephone
company will provide advance notice in order for you to
make the necessary modifications to maintain uninterrupted
service.
If you experience trouble with the D2212 Control/
Communicator, please contact Radionics Customer Service
for repair and/or warranty information. If the trouble is
causing harm to the telephone network, the telephone
company may request that you remove the D2212 from the
network until the problem is resolved. User repairs must not
be made. Doing so voids the user’s warranty.
Do not install the D2212 on public coin service provided by
the telephone company. Connection to Party Line service is
subject to state tariffs (Contact your state public utilities
commission for information.). You must supply the local
telephone company with the following information at their
request.
•The line you are going to connect the panel to
•Make (Radionics), model (D2212), and serial number
of the panel
•FCC registration number and ringer equivalence for
the panel.
FCC Registration Number: AJ9USA-20644-AL-E
Ringer Equivalence: 0.2B
Service Center in USA: Radionics, Inc.
1800 Abbott Street,
P.O. Box 80012
Salinas, CA 93912-0012
(800) 538-5807
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 3
© 1996 Radionics
74-07361-000-C 11/11/96
Introduction
D2212 Control/Communicator
The Radionics D2212 Control/Communicator is shipped pre-
assembled from the factory. You should receive the following
parts with your D2212 panel.
Panel Assembly
• D2212 Panel
• D2203 Enclosure
• D1640 Transformer
•
Technogram: Smoke Detectors Compatible with the
D2212
(73-07358-000)
• Release Notes (74-07460-000)
Hardware Pack
• One 2k Ωend-of-line resistor for Point 1 (15-03130-010)
• Six 1k Ωend-of-line resistors for Points 2 to 6 (there is
one extra 1k Ωresistor) (30-01098-102)
• Four #6 sheet metal screws
• Five plastic stand-offs for mounting board to enclosure
Ordered Separately
Literature Pack
•
D2212 Installation Manual
(74-07361-000)
•
D2212 Program Entry Guide
(74-07386-000)
•
D2212 Program Record Sheet
(74-07387-000)
D202A LED Keypad
Each D202A includes the following.
•
D202A Keypad
•
Installation Sheet
(74-07118-000)
•
User's Cards
(71-07090-000)
•
Security System User's Guide
(71-07117-000)
•
Getting Started w/Your Security System
(71-07372-000)
•
Three-wire cable assembly
(15-07032-000)
D220A LED Keypad
Each D220A includes the following.
•
D220A Keypad
•
Installation Sheet
(74-07511-000)
•
User's Reference Card
(71-04532-011)
•
Security System User's Guide
(71-07374-000)
•
Getting Started w/Your Security System
(71-07372-000)
•
Three-wire data cable assembly
(15-07032-000)
D222 Text Keypad with Point Expansion
Each D222 includes the following.
•
D222 Text Keypad with Point Expansion (4 points)
•
Installation Sheet
(74-07362-000)
•
User's Reference Card
(71-04523-010)
•
Security System User's Guide
(71-07374-000)
•
Getting Started w/Your Security System
(71-07372-000)
•
Three-wire data cable assembly
(15-07032-000)
•
Six-wire point cable assembly
(15-07251-000)
• Four 1k Ωend-of-line resistors (30-01098-102)
Table of Contents
Introduction ........................................................................ 3
D2212 Control/Communicator ..................................... 3
Ordered Separately...................................................... 3
Enclosure Options........................................................ 4
Listings and Approvals................................................. 4
Getting Started ................................................................... 4
Mount the Enclosure and Board .................................. 4
Run the Premises Wiring ............................................. 4
Connect Earth Ground ................................................. 5
Transformer ................................................................. 5
Battery.......................................................................... 5
Charge the Battery as You Work ...................................... 5
Lock the Standby Switch.............................................. 5
Install Detection Devices,.................................................. 6
Keypads, and Bells ............................................................ 6
No Connections to the Panel Yet................................. 6
Number of Sensors ...................................................... 6
Continue Connections to the Panel ................................. 6
Power Down First......................................................... 6
Alarm Output................................................................ 6
Keypads ....................................................................... 6
Auxiliary Power ............................................................ 7
External Relays............................................................ 7
Connect the Points ............................................................ 7
On-Board Points .......................................................... 7
Point 1.......................................................................... 7
Points 2 to 6 ................................................................. 8
Points 7 and 8 .............................................................. 8
Point Expanders, Wired or RF ..................................... 8
Make the Telephone Connections .................................... 9
Power Up ..................................................................... 9
Program the Panel ....................................................... 9
Unlock the Standby Switch .......................................... 9
Fill out the Point Chart ............................................... 10
Test the System ......................................................... 10
Detailed Panel Description.............................................. 10
Primary (AC) Power Circuit........................................ 10
Secondary (DC) Power .............................................. 10
Power Outputs ........................................................... 11
Telephone .................................................................. 11
Points ......................................................................... 12
Keyswitch................................................................... 12
Installation Guide for UL Applications........................... 13
Introduction ................................................................ 13
Optional Compatible Equipment ................................ 13
System Chart .................................................................... 14
Standby Battery Requirements .................................. 14
System Wiring Diagram, Issue A .................................... 14
Current Rating Chart for Standby Battery Calculations 15
Specifications................................................................... 16
D2212 Terminal Quick Reference ................................... 16
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 4
© 1996 Radionics
74-07361-000-C 11/11/96
Mount the Enclosure and Board
The D2203 enclosure is shown in Figure 1. Mount the
enclosure in the desired location. Then mount the D2212
board in the enclosure using the plastic stand-offs, again,
see Figure 1.
Run the Premises Wiring
Run the necessary wiring throughout the premises and pull
the wires into the enclosure. Do not make any connections
yet.
Wire Length
Wire length for Points is limited only by the resistance on the
loop and potential EMI (Electro-Magnetic Interference)
problems.
Wire resistance on the Point 1 sensor loop must be less than
50Ω. Measure the wire resistance before installing smoke
detectors. Short the end-of-line resistor before metering the
wire.
Resistance on the sensor loops for Points 2 to 8 must be
less than 100Ωwith the end-of-line resistor shorted and the
detection devices connected.
Maximum wire length for the transformer is 50 feet (18 AWG,
stranded).
Maximum wire length for all keypads and point expanders
combined is 500 feet (22 AWG).
D223 Text Keypad
Each D223 includes the following.
•
D223 Text Keypad
•
Installation Sheet
(74-07490-000)
•
User's Reference Card
(71-04523-010)
•
Security System User's Guide
(71-07373-000)
•
Getting Started w/Your Security System
(71-07372-000)
•
Three-wire data cable assembly
(15-07032-000)
Battery
Order a D126 Battery (12 V 7.0Ah) to complete a basic
D2212 installation.
Enclosure Options
The D2212 is shipped in the D2203 enclosure. If you want to
mount the D2212 in one of the optional enclosures listed
below, order the D2212M and the enclosure of your choice.
• D8103 Universal Enclosure
• D8108A Attack Resistant Enclosure
• D8109 Fire Rated Enclosure
Listings and Approvals
UL Listings
Fire• Underwriters Laboratories lists the D2212 Control/
Communicator as a Household Fire and Burglary
Warning System Control Unit for NFPA 72 (Chapter 2)
Household Fire Warning.
• CSFM Listing 7167-0801:143
Control Units (Household)
• UL 985 Household Fire Warning Systems
Burglary
• UL 1023 Household Burglary Alarm
• UL 365 Police Station Connect
• UL 609 Local Burglary Alarm
• UL 1076 Proprietary Burglary Alarm
• UL 1610 Central Station
Getting Started
Review this manual before you begin to determine hardware
and wiring requirements for the features you want to use.
Have the following handy as you read through the manual:
•
D2212 Program Record Sheet
(74-07387-000)
•
D2212 Program Entry Guide
(74-07386-000)
•
Security System User's Guide
Figure 1: D2203 Universal Enclosure
Installation Label
Snap plastic stand-offs onto these five
mounting locations.
13
4
5
Snap plastic stand-offs over the
center of the mounting post.
2
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 5
© 1996 Radionics
74-07361-000-C 11/11/96
EMI (Electro Magnetic Interference)
AC wiring can induce EMI (both noise and low level voltage)
into adjacent wiring. Run phone and sensor loop wiring away
from AC conductors, including the transformer wire. Run
keypad wiring away from AC and phone wiring.
EMI may also occur if you install the panel or run system
wires near the following:
• Computer network systems
• Fluorescent fixtures
• Telephone cabling
• Ham radio transmitter sites
• Heavy machinery and motors
• High voltage electrical equipment
• PBX telephone systems
• Public services (police, fire departments, etc.) using
radio communications
• Radio station transmitter sites, or other broadcast
station equipment
• Welding shops
If EMI may be a problem, use shielded cable. The drain wire
for the shielded cable must have continuity from terminal 3,
earth ground on the panel, to the end of the wire run.
If continuity is not maintained, the shielded cable may
aggravate potential noise problems rather than eliminate
them. If you cut the drain wire to install devices, be certain to
splice it together. Solder and tape all splices.
Connecting the drain wire to ground at a location other than
terminal 3 may also produce problems.
Connect Earth Ground
Terminal 3
To help prevent damage from electrostatic charges or other
transient electrical surges, connect the panel to earth ground
at terminal 3 before making any other connections. A
grounding rod or cold water pipe are recommended earth
ground references.
Radionics does not recommend a telephone or electrical
ground for the earth ground connection. Use 18 AWG wire
maximum under the terminal. Use a spade lug or splice for
larger wire.
Do not connect any other panel terminals to earth ground.
The panel’s common terminals and terminal 3, earth ground,
are electrically isolated.
Transformer
Terminals 1 and 2
Connect the transformer to terminals 1 and 2 on the panel
before plugging it into the power source.
Use 18 AWG wire to connect the transformer to the panel.
Wire length should be kept as short as possible. Maximum
length is 50 feet.
Never share the transformer with other equipment:
Foreign grounds on the AC input damage the panel's power
circuit.
Battery
Terminals 4 and 5
Place the battery upright in the base of the enclosure. First
connect the stripped end of the black battery lead to terminal
5 on the panel. Then plug the other end to the negative (-)
side of the battery.
Next connect the stripped end of the red battery lead to
terminal 4 on the panel. Then plug the other end to the
positive (+) side of the battery.
Charge the Battery as You Work
Lock the Standby Switch
Locking the pin in the closed/standby position allows you to
charge the battery as you install the detection devices and
keypads. Lock the pin down now. See Figure 2.
With the Standby Switch locked down, the panel deactivates
the external relay outputs, suppresses reports, and disables
all arming functions.
Lock the Standby Switch down to program the panel
locally, from the keypad, or the D5200.
Releasing the Standby Switch from the closed position
resets the panel. The panel resets all its timers and counters,
and clears all buffers. If the panel is armed, releasing the
standby switch causes the panel to disarm.
Figure 2: Standby Switch
1511 12 16 17 20 21 22 23 24 25 26 27 28 29
1918
1
6
7
8
9
10
3
5
4
2
1413
Standby Switch
Normal (Open)
Standby Switch
Locked (Closed)
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 6
© 1996 Radionics
74-07361-000-C 11/11/96
1. Add together the current draws for all devices
connected to terminal 9. This total is the current
required for the Normal Standby Condition (NSC). This
total must be less than 140mA.
2. Subtract the NSC current required (calculated in step
1) from the Primary Alarm Current, 860mA. The
difference is the Alarm Current Available for terminals
6 and 7.
In formula format:
Primary Alarm Current – NSC current required = Alarm
Current Available
Keypads
Terminals 8, 9, and 10
You can connect a combination of up to eight keypads and
two types of point expanders (wired or RF) to the panel. Four
keypads with expanders can have points assigned to them.
The installation sheet packaged with each keypad contains
mounting instructions. Wire keypads and other devices to
the panel in parallel as shown in Figure 3.
You must use a minimum of five feet of wire (22 AWG)
when connecting the keypad to the panel.
A short on
terminal 9 within five feet of the panel prevents the panel
from operating correctly.
Maximum wire length for all devices connected to terminals
8, 9, and 10 combined is 500 feet (22 AWG).
Extra power needed for more keypads.
Review
Power
Outputs
on page 11 to determine the total power output
requirements for your system. Instructions for using stand
alone power supplies are included.
Install Detection Devices,
Keypads, and Bells
No Connections to the Panel Yet
Install and wire detection devices, keypads, and indicating
devices (bells, sirens, or strobes for example) at their
locations throughout the premises. DO NOT make the
connections at the panel end of the wiring yet.
Number of Sensors
When using Point 1 as a fire point, the number of detection
devices you can connect to its sensor loop is limited. See
Point 1
on Page 7.
The number of detection devices you can connect to the
sensor loops for points 2 to 8 is limited only by the resistance
on the loop. Resistance must be less than 100Ωwith the
detection devices connected.
Continue Connections to the Panel
Power Down First
Unplug the transformer and disconnect the battery to make
the remaining connections to the panel.
Alarm Output
Terminals 6 and 7
Terminals 6 and 7 provide a 10.2 VDC to 13.9 VDC output
when activated.
Terminal 6 provides a steady positive
output.
Terminal 7 provides a pulsed or steady negative
output depending on how it is programmed.
There is always power at Terminal 6:
Use this power for
bells, siren drivers, piezo fire sounders, electronic horns, or
other devices.
Available Power
For burglary installations, the panel combines power
produced by the power supply with power from the
secondary power source (the battery) to produce a total of
1.85A of
alarm
power at terminals 6 and 7.
Power restricted for fire and combined fire/burglary
systems:
Use the
Fire System Power Formula
that follows
to calculate the alarm current available for fire and combined
fire/burglary systems.
Fire System Power Formula
To calculate the current available at terminals 6 and 7 for fire
and combined fire/burglary systems, perform the following
two steps:
ALL ON
SYSTEM OK ON
™
Radionics
123
456
789
0CLEAR
ABC
*
Test Reset
Check
Watch All On
Part On
D222
Blue Wire - Point A
Black Wire - Common
Orange Wire - Point B
Yellow Wire - Point C
Black Wire - Common
White Wire - Point D
Four Expanded Points
Keypad
Connect up to eight in parallel.
Up to 24 points supported.
ABCD
11 12
7
8
9
10
1413
D2212
Green
(Data)
Red
(+12VDC)
Black
(Common)
Figure 3: Keypad Wiring
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 7
© 1996 Radionics
74-07361-000-C 11/11/96
Auxiliary Power
Terminal 9
The continuous current draw for powered devices
connected to terminal 9, including keypads, must not
exceed 1.0 A (140mA for fire and combined fire/burglary
systems). Devices powered from this output must operate
over a range of 10.2 VDC to 13.9 VDC.
You must use a minimum of five feet (22 AWG) of wire
when connecting devices mounted outside the
enclosure to terminal 9.
A short on terminal 9 within five
feet of the panel prevents the panel from operating correctly.
Checking Continuous Current Draw
The panel allows you to check current draw using the
keypad. For more information about this and other keypad
diagnostic features, see the
D2212 Keypad Diagnostics
manual (74-07385-000).
External Relays
Terminals 11 and 12
You can program terminals 11 and 12 to provide outputs for
two external relays. Review
RELAYS
in the
D2212 Program
Entry Guide
for a description of the relay functions available.
Figure 4: External Relay Wiring
D133/D134
Relay Module
N/O 1
COMM1
N/C 1
X1- ( Connect to terminal 12
for External Relay 2)
X1+
1
8
10
13
ExternalRelay 1
ExternalRelay 2
D133/D134
Relay Module
N/O 1 (Closes to COMM1 when relay is activated.)
COMM1 (Common)
N/C 1 (Opens from COMM1 when relay is activated.)
X1- (Connect to terminal 11 for External Relay 1)
X1+ (Connect to terminal 9.)
9
11 12
Ext
1Ext
2
12VDC Aux
14
Connect a D133 Relay Module for each of the external relay
outputs you intend to use, or one D134 Relay Module for two
external relay outputs. The D134 is essentially two D133
modules on a single board. Figure 4 shows the connections.
Warning:
Do not connect wiring for external devices directly
to terminals 11 or 12. Install D133/D134 modules connected
to terminals 11 and 12 in the enclosure with the panel as
shown in Figure 1. The D133 draws 36mA when energized.
When both relays are energized, the D134 draws 72 mA.
Connect the Points
On-Board Points
Point 1
Terminals 13 and 14
Point 1 on the D2212 is a powered, supervised point.
The panel monitors the Point 1 sensor loop for normal,
shorted, or open conditions. Programming determines how
the panel responds to these conditions. See the
D2212
Program Entry Guide
.
Terminal 13 provides positive (+) voltage to 2-wire detection
devices. Terminal 14, the loop return (-), is isolated from
earth ground.
The keypad Reset function interrupts power to this sensor
loop to reset smoke detectors.
Use a 2k Ωend-of-line resistor (P/N 15-03130-010) for Point
1. Figure 5 shows Point wiring.
Connecting Two-Wire Smoke Detectors to Point 1:
Connect up to 15 Radionics D262 two-wire smoke detectors
to Point 1. Refer to the
Technogram: Smoke Detectors
Compatible with the D2212
(73-07358-000), for a complete
list of detectors compatible with the D2212.
Four-Wire Smoke Detectors
Connect any number (limited by available power and the
Authority Having Jurisdiction) of 12 VDC four-wire smoke
detectors to any supervised point. Install a suitable power
supervision device according the manufacturer's instructions.
Route the power for the detectors through a D133/D134
Relay Module. The relay module must be connected to one
of the panel's external relay outputs programmed for the
reset function. See
RELAYS
in the
D2212 Program Entry
Guide
for programming instructions.
Heat Detectors and other Dry Contact Initiating Devices
Connect any number (limited by the Authority Having
Jurisdiction).
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 8
© 1996 Radionics
74-07361-000-C 11/11/96
Point Expanders, Wired or RF
Points are connected by wire to D222 keypads, or if RF
Points are used, they transmit to an RF Receiver.
You can expand to 24 points using wired and/or RF point
expanders. On board point numbers are fixed from point 1 to
point 8. If you use an on-board point, you must use its point
number. See the
D2212 Program Entry Guide
(74-07386-
000) for more information.
For UL installations, wire a sounding device (e.g. a buzzer)
to one of the external relays (terminal 11 or 12) and to
terminal 6 (alarm output). See Figure 5. Program the relay
for Function 3 to provide annunciation of troubles for all fire
points (see
RELAYS
in the
D2212 Program Entry Guide
).
Points Connected to D222 Keypads or D208 Point
Expanders
Points are supervised, non-powered points. The panel
monitors sensor loops for normal, shorted, or open
conditions. Programming for each point determines how the
panel responds to these conditions. See the
D2212 Program
Entry Guide
.
Terminate each sensor loop with a 1.0k Ωend-of-line
resistor. Figure 5 shows Point wiring.
RF Points
RF Points transmit a radio frequency signal to an RF Point
Expander Module. The module decodes the signal and
sends the RF Point status to the D2212.
Burglary Devices
Connect any number (limited by available power) of burglary
devices to any point. Do not combine fire detection and
burglary devices on the same point.
Points 2 to 6
Terminals 15 to 22
Points 2 to 6 are supervised, non-powered points.
The panel monitors sensor loops for normal, shorted, or
open conditions. Programming for each point determines
how the panel responds to these conditions. See the
D2212
Program Entry Guide
.
Terminate each sensor loop with a 1.0k Ωend of line
resistor. Figure 5 shows Point wiring.
Four-Wire Smoke Detectors
Connect any number (limited by available power and the
Authority Having Jurisdiction) of 12 VDC four-wire smoke
detectors to any supervised point. Install a suitable power
supervision device according the manufacturer's instructions.
Route the power for the detectors through a D133/ D134
Relay Module. The relay module must be connected to one
of the panel's external relay outputs programmed for the
reset function. See
RELAYS
in the
D2212 Program Entry
Guide
for programming instructions.
Heat Detectors and other Dry Contact Initiating Devices
Connect any number (limited by the Authority Having
Jurisdiction).
Burglary Devices
Connect any number (limited by available power) of
burglary devices to any point. Do not combine fire
detection and burglary devices on the same point.
Points 7 and 8
Terminals 23 to 25
Points 7 and 8 are non-powered points that
are not supervised with an end-of-line
resistor.
The D2212 monitors the sensor loops for
Points 7 and 8 for normal (closed) and open
conditions. Programming determines how
the panel responds to these conditions. See
the
D2212 Program Entry Guide
. Figure 5
shows Point wiring.
For UL systems, points 7 and 8 can only
be used for tamper contacts.
Tamper
contacts must be installed within the
protected enclosure. Figure 5: Points
15 16 17 20 21 221918
Point 2 Point 3 Point 4Point 5 Point 6
11 12 1413
Point 1
Powered Sensor Loop
suitable for
Two Wire Smoke
Detectors
2 K ΩResistor required
at End of Line.
For compatible smoke
detectors see
RPN 73-07358-000.
23 24 25
Point 7 Point 8
10
9
8
RF Receiver
(D208RF or
D216RF)
6
Buzzer
Supervised Points
Open 3.7 - 5.0VDC
Normal 2.0 - 3.0VDC
Short 1.50 - 0.0VDC
1.0 K ΩResistor
Required at End of Line
ABCD
RF Transmitter
s
s
Supervised Points
Open 8.9 - 13.9VDC
Normal 2.5 - 8.5VDC
Short 0.0 - 2.0VDC
1.0 K ΩResistor
Required at End of Line
Unsupervised Points
Open 2.4 - 13.9VDC
Normal (Closed)
0.0 - 1.4VDC
No End of Line Resistor
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 9
© 1996 Radionics
74-07361-000-C 11/11/96
Make the Telephone Connections
Phone Jack
To prevent reports from jamming, wire the RJ31X jack
before the in-house phone system to support line seizure.
See Figure 6. Line seizure provides for a temporary
interruption of normal phone usage while the communicator
transmits data.
After installation, confirm that the panel seizes the line,
acquires dial tone, reports correctly to the receiver, and
releases the phone line to the in-house phone system.
Phone Cord
Connect the flying leads of the D164 Phone Cord to the
panel as shown in Figure 7. Connect the modular end to the
RJ31X jack.
Power Up
Connect the battery and then plug in the transformer.
Leave the Standby Switch locked down for now.
Program the Panel
Use the Keypad, the Radionics D5200 Programmer, or a
remote programmer to program the panel. See the
D2212
Figure 7: Phone Cord
D164
Phone Cord
25 26 27 28 29
T1 R R1T
To RJ31X Phone Jack
Black, Yellow,
Orange, and
Blue not used.
Brown
Green
Red
Gray
1
2
3
4
5
6
7
8
Incoming
Telco Line
R
T
R1
T1
Full Modular Phone Jack
Premises Phone
RJ31X Module
(
Figure 6: RJ31X Phone Jack
Program Entry Guide
for programming options and keypad
programming instructions.
If you're programming from the keypad or using the
D5200, make sure the Standby Switch is locked down.
See Figure 8.
If you're using the D5200, Figure 9 shows the location of the
programming jack. See the
D5200 Programmer Operation
Manual
for instructions on using the programmer.
Unlock the Standby Switch
When you're finished programming, return the Standby
Switch back to the normal (open) position. See Figure 8. The
panel sends a RE-BOOT report to the receiver and returns to
the disarmed state. If you programmed for test reports and
left the hours and minutes to next report prompts at 0 (zero),
the panel sends a test report with the RE-BOOT report.
RAM II ResetBye does not disarm the panel:
After you
unlock the standby switch, the panel returns to a disarmed
state. Using RAM II
ResetBye
, however, does not affect the
armed state of the panel.
Figure 9: Programmer Jack
11 12
9
10
1
Local Programmer Connect
Lock standby switch to program.
Figure 8: Standby Switch
1511 12 16 17 20 21 22 23 24 25 26 27 28 29
1918
1
6
7
8
9
10
3
5
4
2
1413
Standby Switch
Normal (Open)
Standby Switch
Locked (Closed)
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 10
© 1996 Radionics
74-07361-000-C 11/11/96
Lead Acid Batteries Only: The panel charging circuit is
only calibrated for lead-acid batteries. Do not use gel-cell or
nicad batteries.
Battery Replacement
Radionics recommends battery replacement every three to
five years under normal use. Exceeding the maximum output
ratings, or installing the transformer in an outlet that is
routinely switched off, causes heavy discharges. Routine
heavy discharges can lead to premature battery failure.
D135A Prevents Deep Discharge:
The D135A Low Battery
Cutoff Module protects the battery from deep discharge
during extended power outages. Deep discharge can cause
permanent battery damage.
Battery Supervision
When the battery drops to 12.1 VDC, the keypad indicates a
trouble condition. The panel will transmit a BATTERY LOW
report.
When battery voltage returns to 13.0 VDC and there is AC
power at terminals 1 and 2, the keypad returns to normal
operation. The panel will transmit a BATTERY RESTORAL
report.
Investigate low battery reports right away
: If primary
(AC) power is off and the discharge continues, the panel
becomes inoperative when the battery voltage drops below
10.2 VDC.
If the battery is disconnected,
it takes 60 seconds for the
panel to recognize the condition.
Battery Charging Circuit Float Charge
The float voltage for the battery charging circuit is 13.9 VDC.
Deduct any continuous load for devices connected to the
panel from 1.0 A to find the maximum current available for
charging. At 13.9 VDC, the battery is fully charged and is
maintained with a trickle charge of approximately 5.0mA.
Battery Discharge/Recharge Schedule (No AC Power)
Discharge Cycle
AC OFF The keypad indicates trouble
AC Fail reports if programmed
13.9 VDC Charging float level
12.1 VDC Low Battery reports
10.2 VDC Panel stops processing below 10.2 VDC
Recharge Cycle
AC ON Panel restarts, battery charging begins,
AC restoral report sent
13.0 VDC Battery restoral reports sent, the keypad
returns to normal operation
13.9 VDC Battery float charged
Fill out the Point Chart
Radionics recommends that you fill out the
Point Chart
on
the Installation Label located on the inside of the D2203
Enclosure cover.
You must fill out the point chart if you programmed
Point 1 for Fire with Verification (Digit 1 = 2).
See
POINT
CODES
in the
D2212 Program Entry Guide
for more
information.
Use the
Program Record Sheet
to gather the information you
need to fill out the point chart.
Test the System
After finishing the installation and programming, perform a
complete functional test of the system. Test the panel and all
devices for proper operation. Test after you first program the
panel and after any subsequent programming sessions.
Clear after test:
To clear the alarm memory and report
buffer, place the Standby Switch in the closed position for
two seconds and then release it. The panel returns to
service in the disarmed state.
Detailed Panel Description
Primary (AC) Power Circuit
A 16.5 VAC, 40VA transformer (Radionics model D1640) is
the primary power source for the panel.
The AC power circuit provides 1.5 Amps of rectified DC
power. The panel reserves 140mA of this power for internal
operations and 1.0 A for continuously powered devices.
Under alarm conditions, 1.0 A of power is available for
continuously powered and alarm indicating devices
combined.
Transient suppressors and spark gaps protect the circuit
from power surges. This protection relies on the ground
connection at terminal 3. Make sure you connect terminal 3
to a proper ground.
AC Power Failure
The panel indicates an AC power failure when power at
terminals 1 and 2 is missing for 60 seconds. The
AC Fail
Buzz/Rpt
program item sets the panel response to detected
AC failure. The panel indicates an AC power restoral 60
seconds after power restores to terminals 1 and 2.
Secondary (DC) Power
A 12V, 7.0 Ah sealed lead-acid rechargeable battery
(Radionics D126) supplies secondary power for auxiliary and
alarm outputs. The battery also powers the system during
interruptions in primary (AC) power.
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 11
© 1996 Radionics
74-07361-000-C 11/11/96
Power Outputs
D2212 Circuit Protection
Two self-resetting protection devices protect the panel from
short circuits on both the auxiliary and alarm power outputs.
Bell circuit protection:
A short on the alarm power output
while the bell is ringing disables this output until it times out
or a panel reset has been performed.
Extra Power for Keypad or Other Powered Devices
You may need to add one or more D8132 Battery Charger/
Power Supply Modules for the number of keypads you want
to use. Figure 10 shows the D8132 powering keypads in a
stand-alone configuration.
For UL certificated accounts, use a UL listed power supply.
The D8132 is not UL listed as a stand-alone power supply
for fire and burglary applications.
D2212 and D8132 (or other power supply) must share
COMMON:
Note that Figure 10 shows the common from the
D8132 module connected to both the keypads' common and
terminal 10 on the panel.
A stand-alone power supply powering any device connected
to the panel must also be connected to terminal 10 on the
panel.
Do not connect the stand-alone power supply to
earth ground
.
Telephone
Dialing Format
The panel can be programmed to use DTMF or pulse
dialing. See
Phone Parameters
in the
D2212 Program Entry
Guide
.
Communication Failure
After 5 attempts to reach the receiver (10 attempts if two
phone number are programmed), the panel goes into
communication failure. The panel clears any reports in its
phone buffer. The panel sounds a tone at the keypad
indicating trouble.
Pressing the Clear key silences the tone. When
communication restores (a report is acknowledged by the
receiver), the keypad returns to normal operation.
Ground Start
Some telephone systems require a momentary ground input
to initiate dial tone. To interface with a ground start system,
connect a D133/D134 relay as shown in Figure 11.
See
RELAYS
in the
D2212 Program Entry Guide
for
instructions on programming the external relay output for
Ground Start.
Terminal 3 on the panel must be connected to an earth
ground reference.
Warning:
You cannot use ground start phone systems for
fire or combined fire burglary systems.
Figure 10: Power for Keypads
11 12
7
8
9
10
1413
D2212
Black
(Common)
Green
(Data)
Red
(+12VDC)
D8132 Battery
Charger Module
(Stand-Alone Power
Supply Configuration)
+12VDC Common
Keypad
Connect up to
eight in parallel.
Expanders,
Keypads, RF
Receivers:
Connect up to
eight devices on
the panel.
Up to four devices
can have points
assigned.
Figure 11: D133/D134 for Ground Start
15 16 17 20 21 22 23 24 25 26 27 281918
10
1413
9
11 12
D164
Phone Cord
T1 R R1T
To RJ31X Phone Jack
Brown
Green
Red
Gray
29
See RELAYS in D2212 Program Entry Guide
to program External Relay 1 for Ground Start.
D133/D134
Relay Module
N/O 1
COMM1
N/C 1
X1- ( Connect to terminal 11
for External Relay 1)
X1+
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 12
© 1996 Radionics
74-07361-000-C 11/11/96
Keyswitch Operation
Shorting and restoring the point sensor loop toggles the
system On and Off. All faulted points are bypassed. See
POINT CODES
in the
D2212 Program Entry Guide
.
Silencing the Bell
To silence the bell (stop Alarm output) if the system is On (or
Part On), operate the keyswitch to turn the system Off. If the
area is Off, operating the keyswitch only silences the bell. It
does not turn the system On.
Easikey
You can use a Radionics Easikey access system to turn the
system Off. Program the
Keyswitch
prompt to Easikey (see
the
D2212 Program Entry Guide
for instructions). You must
use a 12VDC option for the Easikey installation. See the
Easikey Installation and Operation Instructions
. Easikey is
not for use in UL installations.
Connect the Easikey door controller to the panel using a
D133/D134 Relay Module as shown in Figure 13. Make
certain to connect the common for the Easikey's 12VDC
power supply to terminal 10 on the panel.
Points
Point Parameters
On-Board Point 1
Point 1 is a powered sensor loop. Review the Radionics
Technogram: Smoke Detectors Compatible with the D2212
(73-07358-000) for a list of compatible detectors.
Point 1 is supervised with a 2.0K EOL resistor. The voltage
range for two-wire smoke detectors is 10.2 to 13.9 VDC.
Points 2 to 6
Points 2 to 6 are supervised with 1.0K EOL resistors.
Open Loop = Greater than 8.9 VDC, but less than
13.9 VDC.
Normal Loop = Greater than 2.5 VDC, but less than
8.5 VDC.
Shorted Loop = Greater than 0.0 VDC, but less than
2.0 VDC.
Points 7 and 8
Points 7 and 8 are
not
supervised with EOL resistors.
Open Loop = Greater than 2.4 VDC, but less than
13.9 VDC.
Normal (Closed) Loop = Greater than 0.0 VDC, but
less than 1.4 VDC.
Point Response Time
The panel scans point sensor loops every 500 milliseconds.
A point must be faulted for 2 scans (one second) before the
panel initiates an alarm.
Keyswitch
Description
You can connect a momentary contact arming station
(keyswitch) to turn the D2212 on and off. Connect the
keyswitch to any point sensor loop (except points 7 and 8).
You can use the external relay outputs and D133/D134
Relay Modules to activate arming status lights for keyswitch
arming stations. See the
Relays
section in the
D2212
Program Entry Guide
.
Programming
See
POINT CODES
in the
D2212 Program Entry Guide
for
the correct programming for points used for keyswitches.
Installation
Connect the end-of-line resistor for the point at the keyswitch
so that the switch shorts the resistor when it operates. An
open on the circuit produces an alarm if the area is armed
and a trouble if it is disarmed. See Figure 12. Figure 13: Easikey
Figure 12: Keyswitch
Short and restoral
on circuit toggles
arming state.
CO
MM
O
N
POINT INPUT
End of Line
Resistor
N/O 1
COMM 1
N/C 1
X1 -
X1 +
D133
Relay Module
Connect to any supervised
point programmed for
Keyswitch (Digit 1 = A, see
D2812 Program Entry Guide).
Shorting and restoring point
turns system OFF.
End of Line Resistor
+-
EasiKey Control
To 12VDC, Switched
parallel to door strike.
P2
15 16 17 20 211918
10
141311 12
Connect the common for the Easikey's 12 VDC
supply to the terminal labeled Aux- on the panel.
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 13
© 1996 Radionics
74-07361-000-C 11/11/96
Optional Compatible Equipment
You can use UL listed components that do not require evaluation for
electrical compatibility in many applications when installed according
to the manufacturer’s instructions.
Burglary Applications
You can use UL listed burglary alarm sensors that do not require
evaluation for electrical compatibility in burglary applications. In
some cases you must use a UL listed Radionics interface module in
conjunction with the sensors. Consult the individual component
specification and installation documents to determine suitability.
In burglary applications with one 7.0Ah, 12 VDC battery the panel
supports an auxiliary output of 1 A and an alarm (bell) output of
1.85A configured as necessary. For additional loadings refer to the
Current Rating Chart for Standby Battery Calculations.
For commercial burglary installations use a maximum of 45 seconds
of entry delay and a maximum of 60 seconds of exit delay.
Test weekly:
UL Standard 1023 requires a weekly test. Configure
the User System Test to test the battery. See
User Configuration
in
the
D2212 Program Entry Guide
for instructions.
Fire Applications
You can use UL listed fire initiating devices not requiring electrical
compatibility evaluation in any application. For example: four-wire
smoke detectors, heat detectors, waterflow switches, and manual
pull stations are suitable fire initiating devices. Consult the individual
component specification and installation documents to determine
suitability.
When using four-wire smoke detectors, install a suitable power
supervision unit according to the manufacturer’s instructions. Use
the D133 Relay Module to provide reset capability.
In fire applications with one 7.0Ah, 12 VDC battery the panel
supports an auxiliary output of 140mA; it supports a total combined
continuous and alarm current daw
during alarm conditions
of 1 A.
For additional loadings refer to the
Current Rating Chart for Standby
Battery Calculations.
Two-wire detectors must be electrically compatible, and must be UL
listed for use with the D2212. See the Radionics Technogram
Smoke Detectors Compatible with the D2212
(73-07358-000), or
you may contact the detector manufacturer.
Test weekly:
Radionics recommends testing fire and combined fire/
burglary systems weekly. Configure the User System Test to test the
battery. See
User Configuration
in the
D2212 Program Entry Guide
for instructions.
For all Burglary applications the panel must be programmed to send
a supervisory signal to the central station a minimum of once every
24 hours.
Do not set or program an automatic telephone dialer or similar
device to place a call to a police station number that is not
specifically assigned by that station for such service.
Sounding Device
The sounding device shall operate for at least four minutes before
an automatic cutoff for Household Burglary applications and at least
15 minutes for Commercial Burglary applications.
For all Commercial Burglary applications the system must be
programmed to sound the audible device every time the system is
armed.
Enclosures
The D2203 enclosure is suitable for Household Fire and Burglary
applications only.
Enclosure tamper protection causing an immediate alarm signal is
required for all burglary applications.
Radionics offers three optional enclosures.
The D8103 enclosure is suitable for residential fire and/or burglary
installations and commercial applications. See
System Chart
for
acceptible applications.
The D8109 is normally used for fire alarm applications. The D8109
is approved by Factory Mutual, California State Fire Marshal, and
the New York City Materials and Equipment Acceptance System.
The D8108A is attack resistant. It is intended primarily for UL
commercial burglary alarm and mercantile safe and vault
applications requiring a local bell. You can use the D8108A in any
burglary application where the D8103 or D8109 enclosure is
suitable. The D8108A is approved by Factory Mutual, California
State Fire Marshal, and the New York City Materials and Equipment
Acceptance System.
The D2212 control panel is suitable for Police Station connect
applications, including Grade A Mercantile Premises and Grade A
Mercantile Safe and Vault alarm systems. Suitable for Grade AA
Mercantile Premises and Grade AA Mercantile Safe and Vault alarm
systems when the Model D2212 DACT unit is installed in
conjunction with the Model D8122 derived channel subscriber
terminal unit. For all Police Station applications and grades, the
Model D8108A Attack Resistant Enclosure with a UL Listed local
sounding device is required. Per UL 365, keyswitches mounted
outside the protected area must employ high security locking
cylinders complying with the requirements for key locks, UL 437.
Tamper protection must also be provided.
The D2212 control panel is suitable for Local, Grade A Mercantile
Premises and Local, Grade A Mercantile Safe and Vault alarm
systems. For all Local applications and grades, the Model D8108A
Attack Resistant Enclosure and a UL Listed local sounding device
are required. Per UL 609, when keyswitches are mounted outside
the protected area, tamper protection must be provided.
The D2212 control panel is suitable for Central Station, Grade C
applications. It is suitable for Central Station, Grade B applications
when the Model D2212 DACT unit is installed with a UL Listed local
sounding device. Also suitable for Central Station Mercantile, Grade
AA applications when installed with the Model D8122 derived
channel subscriber terminal unit.
Installation Guide for UL
Applications
Introduction
The
System Chart
references components evaluated and listed by
Underwriters’ Laboratories for compatibility with the panel. These
components meet the basic system requirements for the applicable
standard.
The
System Wiring Diagram, Issue A
shows the relationship
between the panel and the accessory components referred to in the
System Chart.
See the installation and operation instructions for
each component for detailed instructions.
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 14
© 1996 Radionics
74-07361-000-C 11/11/96
Standby Battery Requirements
Household Burglary and Commercial Burglary
Four hours of standby battery capacity required.
Standby Battery Calculation for Fire Alarm Applications
NFPA 72 (Ch. 2) Household Fire Warning Equipment
The NFPA 72 (Chapter 2) Household Fire Warning
Equipment Standard requires 24 hours of standby + 4 min.
(.067 hrs) of alarm operation at the end of the 24 hr. period.
You must use battery ampere hour (Ah) calculations to verify
compliance. The formula below includes a 10% contingency
factor for depletion of battery capacity with age.
NFPA 72 (Ch. 2) Ampere-Hour Calculation Formula
(Total B ___ x 24 Hrs) + (Total C ___ x .067 Hrs) + (10%
Contingency) = Total Ah required.
Total Ah requirements must not exceed Ah capacity of
batteries.
The D2212 control panel is suitable for Proprietary Burglar Alarm,
Grade C applications. Also suitable for Proprietary Burglar Alarm,
Grade B applications when the Model D2212 DACT unit is installed
with a UL Listed local sounding device. Also suitable for Proprietary
Burglar Alarm, Grade AA when the Model D2212 DACT is installed
with the Model D8122 derived channel subscriber terminal unit.
The D2212 control panel is suitable for Household, Grade A
applications.
UL Standard 681 for Installation and Classification of Mercantile and
Bank Burglary Alarm systems requires foil lining or equivalent
protection of the control unit enclosure. The D8108A enclosure does
not have a foil lining, but acceptable protection can be provided by
mounting listed electronic vibration sensors inside the enclosure.
Proximity alarms (capacitance) cannot be used for this
purpose
.
Install electronic vibration sensors in the D8108A enclosure that are
identical to those used to protect the safe or vault. Sentrol 5402,
Potter EVD-S, or Arrowhead S-3810 electronic vibration detection
(EVD) systems which can be mounted inside the enclosure meet the
requirements of UL 681. Mount the electronic vibration sensor
directly inside the metal cabinet of the D8108A. Do NOT install the
sensor within a quarter inch (1/4”) of the components or traces of the
printed circuit assembly.
System Chart
Household Burglar
(Grade A)
Household Fire
Household Fire/
Burglary Combined
Central Station
Burglary (Grade C)
Police Connected
Burglary
Local Burglary
Proprietar
y
Bur
g
lar
y
NFPA Standard 72 72
Min. Hours of Standby
Battery 424 +
4 min
alarm
24 +
4 min
alarm
4444
D2203 Enclosure Included with panel No No No
D8103 Enclosure Optional * No No No
D8108A Enclosure Optional Choose Req. Req. Req.
D8109 Enclosure Optional One No No No
D126 Batter y 1111111
D127 Rever sing Relay Opt. No Opt. Opt. Opt. Opt. Opt.
D164 Telephone Cord Required to connect panel to RJ31X Telco Block
D205, D206 Command
Center
1+ 1+ 1+ 1+ 1+ 1+ 1+
D262 Smoke Detector Head
D261 Base 1• 1•
D431, D435, D438, D440,
D442, D448 Indicating
Device
1+ 1+ 1+ Opt. uuu
D133, D134 Relays Opt. Opt. Opt. Opt. Opt. Opt. Opt.
D1640 Tr ansform er Required for all applications
D8004 Tr ansform er
Enclosure
Opt. Opt. Opt. Opt. Opt. Opt.
D8122 Derived Channel
S.T.U.
Opt. Contact TelCo for availability of derived channel service
D8130 Release M odule Optional
The D2212 is not listed for these applications: Local Fire/Burglary Combined, Local Fir e, Local and
Central Station Fir e Com bined, Local and Centr al Station Fire/Bur glary (Gr ade C), Central Station
Fir e/Burglary (Grade C) , Central Staion Fir e, and Electrically Actuated Transmitter.
Key
No =Not acceptable for this
application.
Req =Required for this
application.
Opt. =Optional for this application.
1+ = One or m ore r equired for
this application. Consult the
appropriate standar d.
2+ = Two or m ore r equir ed for
this application. Consult the
appropriate standar d.
1• = At least one detector
requir ed. You can substitute
other 2-wire detector s
listed for use with the
D2212. You could use the
D262 with the D270 4- wir e
base or other
manufacturer’s 4-wir e
detectors. You m ust use a
listed power supervision
relay with 4-wir e detectors.
u= Listed bell (siren) housing
requir ed for burglary alarm
bell or siren.
¨=(Empty Box) Not used with
this application.
*= D101 required for D8103
enclosur e.
www.PDF-Zoo.com
firealarmresources.com

D2212 Installation Manual
Page 15
© 1996 Radionics
74-07361-000-C 11/11/96
AC Power On AC Power Off In Alarm
Normal Current Minimum Current Maximum Current
Model Number Each Each Each
Number Used Unit Total Unit Total Unit Total
D2212 1 125 _____ 125 _____ 190 _____
D202A ____ 45 _____ 45 _____ 125 _____
D220A ____ 30 _____ 30 _____ 125 _____
D222 ____ 30 _____ 30 _____ 140 _____
D223 ____ 30 _____ 30 _____ 140 _____
D208RF ____ 50 _____ 50 _____ 50 _____
D216RF ____ 50 _____ 50 _____ 50 _____
______ ____ ____ _____ ____ _____ ____ _____
______ ____ ____ _____ ____ _____ ____ _____
Total A1= _____ Total B= _____ Total C2=_____
1 If Total A exceeds 1 A (140mA for fire and combined fire/burglary systems), a stand-alone power supply is required to
provide additional current.
2 If Total C exceeds 860 mA for fire systems, a stand-alone power supply is required to provide additional current.
Current Rating Chart for Standby Battery Calculations
All currents are in milliamperes (1 ampere=1000 milliamperes).
System Wiring Diagram, Issue A
s
s
PPP
D164 Phone
Cord to RJ31X
for Phone Line
Listed Audible
Signaling Device
Rated At 10.2 TO 13.9
VDC (Do NOT Use
Vibrating Type Horns)
P
P
P
P
D133/
D134
Relay
P
P
Supervised with 1k Ω
EOL Resistor.
Typical Initiating
Devices are Door
Contacts NO/NC,
Floor Mats, Motion
Sensors, Glass Break
Detectors, etc.
NOT
Supervised,
Normally
Closed.
Typical
Initiating
Devices are
Door Contacts,
Floor Mats,
Motion
Sensors,
Tamper
Switches, etc.
All devices
open on alarm.
P
S
Supervised with 2k Ω
EOL Resistor.
P/N 15-03130-010
P
S
P
S
P
S
P
S
P
SP P
KEYPADS,
EXPANDERS
AND RF
RECEIVERS.
INSTALL UP
TO EIGHT
DEVICES ON
THE PANEL.*
1
2
3
4
5
6
7
8
9
10
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29
P
S= POWER LIMITED
= SUPERVISED
P
SP
S
P
S
P
S
ABCD
Supervised with 1k ΩEOL Resistor.
Typical Initiating Devices are Door Contacts
NO/NC, Floor Mats, Motion Sensors, Glass Break
Detectors, etc.
Up To Four Point
Expansion Devices
Can Be Connected
Standby Switch
Programmer
Connector
* Depending on the panel's available auxiliary power.
D133/
D134
Relay
PS D2212
S
-+
D126
Battery
12V 7Ah
16.5 VAC
40 VA
60 HZ
Transformer D1640 D8004
Transformer
Enclosure
www.PDF-Zoo.com
firealarmresources.com

Specifications
Primary Power Supply
• 16.5 VAC, 40 VA class 2 plug-in transformer (D1640)
Secondary Power Supply
• 12 VDC, 7.0 Ah sealed lead acid rechargeable battery.
Auxiliary Power Output
• 1 A maximum at 10.2 VDC to 13.9 VDC for devices powered at
terminal 9 (140mA for Fire and combined Fire/Burglary systems).
Alarm Power Output
• 1.85 A maximum at 10.2 VDC to 13.9 VDC output. Output may
be steady or pulsed depending on programming.
•Fire and Fire/Burglary Systems
To comply with UL 985 listing standards for household fire alarm
systems, the total combined continuous and alarm current draw
for the system during alarm conditions must be limited to 860
mA provided by the primary power supply (rectified AC).
Operating Voltage
• 10.2 VDC (minimum) 13.9VDC (maximum)
Telephone Connection
• RJ31X or RJ38X jack interfaced with D164 phone cord.
Environmental
• Temperature: 32°-122°F (0°-50°C)
• Relative Humidity: 5-85% at 86°F (30°C) non-condensing
D2203 Enclosure Dimensions
Height: 14.75 inches, Width: 12.75 inches, Depth: 3.5 inches
Arming Stations
• D202A Keypad, D220A Keypad, D222 Keypad,D223 Keypad
• D204RF Keypad
• Keyswitch
• Easikey
Compatible Enclosures
• D2203 or D8103 Universal Enclosures
• D8109 Fire Enclosure
• D8108A Attack Resistant Enclosure
Compatible Accessories (see Radionics catalog for complete list)
• D126 12V, 7 Ah Rechargeable Battery
• D127 Reversing Relay
• D132 Smoke Detector Reversing Relay Module
• D133 Relay Module
• D134 Dual Relay Module
• D135A Low Battery Cutoff Module (not UL listed)
• D164 Phone Cord
• D192C Bell Supervision Module
• D202A Keypad
• D204RF Keypad (not UL listed)
• D208 8-Point Expansion Module
• D220A Keypad
• D222 Keypad
• D223 Keypad
• D250 Heat Detector Base
• D254 135°Heat Detector Head
• D255 190°Heat Detector Head
• D440 (6"), D442 (10") Bells
• D448 12 VDC Horn
• D1640 16.5 VAC 40 VA Transformer
• D5200 Programmer
• D5300 Remote Account Manager II
• D8004 Transformer Enclosure
• D8121A/D8122 Derived Channel S.T.U. (D8122 for UL systems)
• Easikey (not for use in UL systems)
• D261A Smoke Detector Base
• D262 Smoke Detector Head
• D208 RF Receiver
• D216 RF Receiver
Radionics, Inc., 1800 Abbott Street Radionics, 1 Park Gate Close, Bredbury
Salinas, California 93901 Stockport, Cheshire, SK6 2SZ, England
Customer Service: (800) 538-5807 Technical Support: (061) 494 0851
™The Radionics logo is a registered trademark of Radionics, Inc., Salinas, CA, U.S.A. ©1995 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved
D2212 Terminal Quick Reference
Terminal Descript ion
1,2 AC Input Connect 16.5 VAC, 40 VA transform er for
prim ary power source.
3 Earth Ground Connect to earth ground. A cold water
pipe or grounding rod is preferred.
Do not connect to telephone or electr ical
ground.
4 Battery
Positive
Connect Positive terminal of 7.0 Ah
battery to this terminal.
5Battery
Negative
Connect Negative terminal of 7.0 Ah
battery to this terminal
6 Alarm Output
Positive
Supplies 1.85 Amps at 10.2 to 13.9 VDC
for alarm output.
This term inal provides a constant output.
Negative is switched.
7 Alarm Output
Negative
Negative terminal for alarm output. This
ter minal switches for pulsed or steady
alarm output.
8 Data Data for Keypads, RF Receivers, etc.
9 Auxiliary Power
Positive
One Amp at 10.2 to 13.9 VDC for
auxiliary power, keypads, and relay
outputs.
10 Common Common for Auxiliary Power and Relay
Drivers.
11 External
Relay 1
Connect D133/D134 Relay for Form C
Dry Contact.
12 External
Relay 2
Connect D133/D134 Relay for Form C
Dry Contact.
13 Positive
Point 1
Positive power for Point 1. Switched for
sensor r eset.
Use approved 2-wire smoke or glass
break detectors.
14 Negative
Point 1
Negative power for Point 1.
15 Comm on Comm on for Point 2.
16 Input Point 2 Input for Point 2.
17 Input Point 3 Input for Point 3.
18 Comm on Comm on for Points 3 and 4.
19 Input Point 4 Input for Point 4.
20 Input Point 5 Input for Point 5.
21 Comm on Comm on for Points 5 and 6.
22 Input Point 6 Input for Point 6.
23 Input Point 7 Input for Point 7 (no EOL resistor).
24 Comm on Comm on for Points 7 and 8.
25 Input Point 8 Input for Point 8. No EOL Resistor.
26 T1 Tip of phone line to prem ises phone.
27 T Tip of incoming phone line.
28 R Ring of incom ing phone line.
29 R1 Ring of phone line to prem ises phone.
www.PDF-Zoo.com
firealarmresources.com
Table of contents
Other Radionics Control System manuals
Popular Control System manuals by other brands

Horizon Hobby
Horizon Hobby Dynamite FU2E instruction manual

Siemens
Siemens SINUMERIK 840D sl Commissioning manual

Promag
Promag AG19 Hardware user's guide

ADTRAN
ADTRAN Total Access 300 Series Installation and maintenance guide

OPTO 22
OPTO 22 SNAP PAC MOTION CONTROL user guide

Burkert
Burkert 8624 operating instructions