
Irritrol Part No. 500641 Rev. B Page 1
Rain Master® TWICE Surge Suppression Specification
¾How it Works:
Surge protection using proper grounding (rods and plates) and TWICE Lightning Arrestors (TW-
LA-1) provides the best possible protection against surge damage due to lightning or other
electrical surge events. Conformance to this surge suppression specification is necessary to retain
warranty protection under Rain Master’s warranty terms.
Proper installation of grounding rods and wire connections are essential to providing good surge
suppression. All installations should conform to manufacturer’s instructions, and must meet or
exceed the American Society of Irrigation Consultants (ASIC) Earth Grounding Guideline 100-
2002.
http://www.asic.org/uploads/assets/011007_121320_ASIC_GROUNDING_GUIDELINES.doc
While no technology currently available can fully protect against damage from massive surges
such as those caused by direct lightning strikes, outfitting your Rain Master@ TWICE system with
surge grounding and surge protection as outlined in this document will protect your system from
most if not all naturally occurring electrical surges. (Additional documentation may also be found
on Rain Master’s website ~ www.rainmaster.com.)
¾Grounding Rods and Plates…
In all cases where it does not conflict with appropriate grounding grid design for the site in
question, Ground Rods or Plates as referred to in this specification shall conform to the following
standards:
1. All grounding rods shall be bare copper of 5/8” diameter or greater, and 8’ length or
greater.
2. All grounding plates shall be 5 square feet, typically 4” by 96”, as outlined in ASIC Earth
Grounding Guideline 100-2002.
3. A measured resistance reading of no more than 25 ohms is necessary at each TW-LA-1
(Lightning Arrestor). ASIC Spec: Section 7.0 – Measuring resistance, item A.
Ground rods and plates shall be located at a minimum distance to assure that the two-wire path is
outside of the electrode sphere of influence for the grounding rod. For an 8’ grounding rod, this
means that the grounding rod must be connected at least 8’ away from the two-wire path, at a
right angle to the two-wire path. See the section below for details on connecting the grounding
rod or plate to the device or lightning arrestor. (Under no circumstance should a ground rod or
ground plate be installed in or under a valve box, meter box or electrical box.)