RECO EasyLine RM-216 CB.10 User manual

Operating and Installation Instructions
Filter control system
RM-216 CB
EasyLine

RM-216 CB.10 Easy Line Documentation
RDN 10000088 2 07.07.2016
Table of Contents
1 Safety instructions .....................................................................................................................................3
2 Equipment specification ............................................................................................................................3
3 Assembly ...................................................................................................................................................4
4 “Step by step” installation ..........................................................................................................................4
5 “Step by step” settings...............................................................................................................................7
5.1 Function when shipped....................................................................................................................7
5.2 Setting parameters ..........................................................................................................................7
5.3 Parameter list...................................................................................................................................9
6 Operating modes.....................................................................................................................................10
6.1 Test mode.....................................................................................................................................10
6.2 Down time cleaning ......................................................................................................................10
6.3 Cleaning via start / stop input (external ∆p switch).......................................................................10
7 Troubleshooting.......................................................................................................................................11
8 Text messages on the display.................................................................................................................12
9 Details on the equipment function...........................................................................................................13
10 Glossary ................................................................................................................................................14
11 Technical specifications ........................................................................................................................15
Regulations
2014/30/EU
2014/35/EU
Legend
Important note
Important warning

RM-216 CB.10 Easy Line Documentation
RDN 10000088 3 07.07.2016
1 Safety instructions
The filter control system RM-216 CB when connected to the mains poses an electrical hazard. Device
failure, serious or even fatal injuries may occur as a result of improper installation of the connected
equipment. Consequently, follow in particular the points set out below in addition to the general safety
regulations for equipment in industrial electrical installations:
- Installation of the device may be carried out only by qualified experts, in accordance with the
provisions of IEC 364, DIN VDE 0105 for electrical equipment.
- All applicable laws, conditions, orders and regulations governing the setting up of electrical equipment
must be observed in respect of the installation site.
- Setting of equipment with degree of protection IP00 without covers, may only be performed by
authorized expert staff, when disconnected, and whilst observing the local safety and accident
prevention regulations.
The RM-216 CB may only be operated in the permitted operating area.
Switch off the mains supply before replacing the filter control or any components connected to
it. Otherwise the equipment may be damaged.
2 Equipment specification
The RM-216 CB is used to control 24 V DC solenoid valves on filtering separators with compressed air
pulse cleaning. After connecting the supply voltage, the filter control system functions fully automatically
without further activation.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 4 07.07.2016
3 Assembly
4 “Step by step” installation
Supply voltage connection
A separate power supply unit is recommended for the operation of the filter controller with extra
low voltage.
The unit can be operated with a supply voltage of 24 V DC, if no expansion modules are
connected and if the electric cables to the solenoid valves are shorter than 3 meters long.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 5 07.07.2016
Solenoid valve connection
Connection of expansion modules RM-LV8 / RM-LV16
Use shielded cable for all bus lines! The shielding must be connected unilaterally to the
protective earthing (PE).
Signal cables must not be laid parallel to power cables.
Tighten all cable glands in use so the cables are properly enclosed and water cannot
penetrate.
Cable glands that are not in use must be closed or replaced by blind plugs.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 6 07.07.2016
Other connections

RM-216 CB.10 Easy Line Documentation
RDN 10000088 7 07.07.2016
5 “Step by step” settings
5.1 Function when shipped
The down time cleaning input E1, E2 (terminals 10, 11) is bridged at the factory. Once the supply voltage
is at RM-216 CB, the solenoid valves are controlled consecutively in sequence. The filter control system
automatically detects how many valves are connected.
For connecting an external ∆p switch, see section 6.3 “Cleaning via start / stop input (external ∆p
switch)”.
To activate the down time cleaning, see section 6.2 “Down time cleaning”.
If another function is required or if additional functions are to be activated, the parameter setting of the
RM-216 CB must be changed. For more on this, see section 5.2 “Setting parameters”.
5.2 Setting parameters
To set or check the parameters, proceed as follows:
Use the parameter list in section 5.3 to search for the parameters you want to change or check.
On the RM-216 CB, press buttons and simultaneously, for at least 3 seconds. The
program then changes from operation mode to parameter selection mode. The parameter P01
“Pulse time” is displayed on the text display at its set value.
Press the button to call up all following parameters P02 ... P11 in sequence. The parameters
already displayed can be accessed by repeatedly pressing the button.
To change the value of a displayed parameter, press the ENTER button for at least one
second.
The program then changes from parameter selection mode to parameter setting
mode.
Press the
button to increase the parameter value displayed in increments. Press the
button to decrease the parameter value displayed.
Press the ENTER button for at least 3 seconds. The new parameter value is stored. The text
display will briefly display the message “Store”.
The program automatically returns to the
parameter selection mode.
You can now call up other parameters and check or change their
values.
So that the program changes from parameter selection mode to operation mode, press buttons
and simultaneously for at least 3 seconds.
If the program is still in parameter setting mode, follow the instructions given under point .
The symbols shown on the right will be shown in the
lower left-
hand corner of the text display. They
indicate to the operator which mode the equipment is
currently in.
+ -Operation mode
+^-Parameter selection mode
+>-Parameter setting mode
If no buttons are pressed for 4 minutes, the RM-216 CB automatically returns from parameter
selection mode or parameter setting mode to operation mode with the last values stored.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 8 07.07.2016

RM-216 CB.10 Easy Line Documentation
RDN 10000088 9 07.07.2016
5.3 Parameter list
Param. no.
Text on the display Explanation Factory settings Setting range
P01 P01 Pulse time Pulse time 60 ms 15 ... 2500 ms
P02 P02 Interval Pause time 10 s 1 ... 500 s
P03 P03 DT interval Down time interval time 6 s 1 ...100 s
P04 P04 tot Valve no Total no. of valves* 0 0 ... 128
P05 P05 DT cycles Down time cleaning cycles 6 0, 2 ... 32
P06 P06 Operating h Operating hours – 0 ... 250000 h
P07 P07 Language Language for the display text D D, GB, F, I, NL,
DK, FIN, PL, E
P08 P08 Test Mode 0 = Test mode off
1 = Valve test
2 = Input test
3-5 = For manufacturer
purposes only
Off (0) 0 ... 5
P09 P09 Ser.run hour Service operating hours – –
P10 P10 Ser.run h.ALService operating hours alarm 0 h** 0 ... 25000 h**
P11 P11 Ser.r.h.Code Service operating hours code 0 0 ... 250
*Number of all valves connected to the RM-216 CB and to the expansion modules. The parameter is used by the equipment for
internal monitoring purposes and need only be set, if expansion modules are fitted. If the equipment detects that the total number
of valves set is different from the actual number of valves controlled, an alarm message is issued.
** If the parameter is set to the value 0 h, the alarm is switched off.
The parameters P09 and P10 are only displayed if the service operating hours code
(parameter P11) has been entered.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 10 07.07.2016
6 Operating modes
6.1 Test mode
In test mode, the most important functions in the control sequence are checked and shown on the text
display. To start test mode, call up parameter no. P08 “Test mode” (see section 5.2 for more information)
and select one of the following test modes:
Test mode 1 (Valve test)
Each valve connected is activated in sequence and shown in the text display.
Test mode 2 (Input test)
The signal statuses of the inputs are displayed on the text display.
Test modes 3-5
For manufacturer purposes only
Test mode 0 (test mode off)
Test mode is switched off.
6.2 Down time cleaning
To activate down time cleaning, perform the following steps:
Remove the factory-fitted wire jumper on input E1, E2 (terminals 10, 11).
Connect a free auxiliary contact (make contact) of the fan contactor to terminals 10 and 11. The input
should be operated in isolation.
Set parameter P05 “Down time cleaning cycles” to the required number of cycles (see also section 5.2
“Setting parameters”).
If the fan is switched on, the contact on E1, E2 closes and switches on the cleaning. When switching off
the fan, the contact on E1, E2 opens and activates the down time cleaning. The down time cleaning
cycles set are carried out. The RM-216 CB then shuts down.
6.3 Cleaning via start / stop input (external
∆
p switch)
If the cleaning is controlled via an external ∆p switch, the isolated contact on the ∆p switch must be
connected to the start / stop input D1, D2 (terminals 12, 13).
During down-time cleaning, the start / stop input D1, D2 is inactive.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 11 07.07.2016
7 Troubleshooting
Error Possible causes Recommended action
The “ON” LED is not lit and input
E1, E2 is bridged. - No mains voltage - Check power feed
- Device fuse is defective - Replace fuse
- EMERGENCY STOP
activated
- Check EMERGENCY STOP
No valve activity - No control system release - Bridge input E1, E2
- Wiring to valves interrupted - Check cables and electrical
connections
- Magnet coil faulty - Replace coil
No down time cleaning - Parameter P05 = 0
(down time cleaning cycles)
- Set parameter P05 “Down
time cleaning cycles” to a
different value
- There is no signal from the
fan control
- Activate signal to input I1, I2
Cleaning ineffective - Interval time too long - Set parameter P02 “Interval
time” to a lower value
- Pressure too low - Set pressure to 6 ... 8 bar
(min. 5 bar)
- Set parameter P02 “Interval
time” to a higher value
- Valve faulty - Check / replace valves
- Pulse time too short - Set parameter P01 “Pulse
time” to a higher value
“Alarm” LED on - The number of valves is set
incorrectly
- Set parameter P04 “Total no.
of valves” correctly

RM-216 CB.10 Easy Line Documentation
RDN 10000088 12 07.07.2016
8 Text messages on the display
Display Explanation
Reset status and text version
The text message is displayed for approx. 1 second after the voltage is
switched on.
Reset RM204VXX
Controller is not enabled through inputs I1 and I2.
Stand By
+ -Val.No
The control has been enabled via input E1, E2 and stopped via input D1,
D2.
Cleaning Off
+ -Val.No
The control has been enabled via input E1, E2 and started via input D1,
D2.
Cleaning On
+ -Val.No
Down time cleaning active
DTC Cleaning ON
+ -000 Pcs
The alarm switching point for the service hours counter has been
exceeded.
Call Service
+ -Val.No
A connected O module RM-LV8 or RM-LV16 is out of order.
or
the total number of valves (parameter P04) is set incorrectly.
RM-LVX Alarm
+ -Val.No

RM-216 CB.10 Easy Line Documentation
RDN 10000088 13 07.07.2016
9 Details on the equipment function
Cleaning
Cleaning starts at the first valve. If the cleaning is interrupted via the starstop input D1, D2, the control
sequence is continued at the next cleaning procedure. The cleaning then starts at the valve following the
last valve activated.
If the control is reactivated following a mains voltage failure, a restart is carried out.
Relay output S1, S2 to control extractor elements (terminals 8, 9)
If automatic components for dust removal (extractor elements) are fitted, these need to be in operation
during cleaning and during down time cleaning. Connect the cut-out for controlling these drive units to the
isolated output S1, S2.
“Alarm” relay output A1, A2, A3 (terminals 5, 6, 7)
As soon as the supply voltage is present on the RM-216 CB, relay contact A1, A2 closes (terminals 5, 6)
and contact A2, A3 opens (terminals 6, 7). In the following situations, relay contact A1, A2 opens and
contact A2, A3 closes:
Supply voltage failure
Failure of a voltage internal to the equipment
Fault in a connected O module
Total number of valves is set incorrectly (parameter P04)

RM-216 CB.10 Easy Line Documentation
RDN 10000088 14 07.07.2016
10 Glossary
Term Explanation
Cleaning Cleaning the filter elements using compressed air pulses.
Compressed air pulse
cleaning
Cleaning of the filter elements using compressed air pulses
Down time cleaning Cleaning the filter elements after the system is shut down for a set
duration or number of cycles.
Down time cleaning cycles The number of cleaning cycles performed in the down time cleaning.
Down time cleaning input Input on the RM-216 CB for starting the down time cleaning.
Down time interval time Pause time during the down time cleaning.
Expansion module If the filter has more than 16 valves, expansion modules of type RM-LV8
(for 8 valves) or RM-LV16 (for 16 valves) are required. A maximum of 7
type RM-LV16 expansion modules can be connected to the main
RM-216 CB equipment. With the outputs on the main equipment, this
makes a maximum of 128 valve outputs available.
Extractor element Device for extracting the filter casing from the dust deposited. E.g.
cellular wheel sluice, trough conveyor worm.
Extractor element contactor Contactor which switches the drive unit for an extractor element on and
off.
I/O module Input/output module (module for the input and output of control signals)
Operation mode Status of the RM-216 CB in which the equipment is ready for operation.
Parameter selection mode Status of the RM-216 CB in which the equipment operator can select a
parameter.
Parameter setting mode Status of the RM-216 CB in which the equipment operator can set a
parameter.
Pause time
(also Interval time)
Time period between two consecutive control pulses from the valve
outputs when the cleaning is running.
Pulse time Duration of a control pulse on the valve outputs
Service operating hours
alarm
Alarm issued when the operating hours set for the maintenance interval
has elapsed.
Service operating hours
code
Code which needs to be entered to change the set value for the service
operating hours.
Solenoid valve (also relay valve) electromagnetically operated valve for the pneumatic
triggering of the filter membrane valves. The membrane valves in turn
release the compressed air strokes for filter cleaning.
Starstop input Input on the RM-216 CB for starting and stopping the cleaning via an
external ∆p switch.
Total no. of valves Number of all valves connected to the RM-216 CB and to the expansion
modules.
∆p switch Switch which is triggered by a differential pressure value set and which
activates the filter cleaning.

RM-216 CB.10 Easy Line Documentation
RDN 10000088 15 07.07.2016
11 Technical specifications
Application Data
Supply voltages
230 V AC ±10%
110 V ... 120 V AC ±10%
26 V … 28 V DC*
Signal inputs
24 V DC, operate ensuring isolation
Signal output
Relay outputs, max. 2 A, 250 V
or 1 A, 30 V DC
Control outputs for valves
For valves with a rated voltage of 24 V DC,
can be expanded to 128 outputs,
Output power in pulse mode 42 Watt
Outputs for expansion
modules
Supply voltage and pulse wires to the expansion modules
Fuses
230 V: T 0.4 A, 250 V, 5 x 20 mm
110 V: T 0.8 A, 250 V, 5 x 20 mm
Extra low voltage: Fusing via PTC resistor
Temperature range
-20°C to +60°C
Degree of protection
Casing IP-66 / NEMA 4
Dimensions
See chapter 3 “Assembly”
Weight
approx. 0.8 kg
Installation height
max. 3000 m above M.S.L.
*The unit can be operated with a supply voltage of 24 V DC, if no expansion modules are connected and if the electric cables to
the solenoid valves are shorter than 3 meters long.
Disclaimer
The contents of this documentation has been verified for correctness and completeness. Nevertheless, errors can not be excluded
so that we cannot guarantee the correctness of this information. Subject to alterations at any time.
Table of contents
Other RECO Control System manuals
Popular Control System manuals by other brands

Geobrugg
Geobrugg GBE-500A-R product manual

Crystal Vision
Crystal Vision Indigo CoCo 3G user manual

Marshall Electronics
Marshall Electronics Network Control Box for IMD Monitors... operating instructions

Saferoads
Saferoads HV2 Safety Barrier product manual

Well Straler
Well Straler 3003EU user guide

Siemens
Siemens SINUMERIK 808D user manual