RECO RM-310 C User manual

Operating and installation instructions
R-IMC-BUS
Filter control systems
RM-310 C
RM-310 CT
RM-310 C Plug and Play
RM-310 CT Plug and Play

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 2 14.07.2020
Contents
1 Safety instructions .....................................................................................................................................3
2 Device descriptions....................................................................................................................................4
3 Assembly ...................................................................................................................................................7
4 Installation -.......................................................................................................................................9
5 Setting procedure ....................................................................................................................................14
5.1 Function in "as delivered" condition ..............................................................................................14
5.2 Operating and display elements....................................................................................................14
5.3 Parameter selection level..............................................................................................................15
Parameter blocks .........................................................................................................................15
Activated and deactivated parameters / faded in and faded out parameters...............................15
Parameter display examples ........................................................................................................15
5.4 Parameter setting level .................................................................................................................17
5.5 Code input to clear locked parameters .........................................................................................17
5.6 Return to the operating level .........................................................................................................17
5.7 Short guide for parameter setting .................................................................................................18
5.8 Overview of menu navigation........................................................................................................19
5.9 Parameter list................................................................................................................................23
5.10 Parameter description and explanation of function.....................................................................25
6 Operating modes .....................................................................................................................................30
6.1 Time-controlled cleaning (parameter E1, E5, D1) ........................................................................30
6.2 Forced cleaning (parameter E8) ...................................................................................................30
6.3 Differential pressure-controlled cleaning (parameter D5, D6, D1)................................................30
6.4 Downtime (parameter E9).............................................................................................................30
6.5 Cleaning skip range (parameter EC) ............................................................................................30
6.6 Valve test mode ............................................................................................................................30
7 Troubleshooting .......................................................................................................................................31
8 Text messages on the display .................................................................................................................33
8.1 Program start ................................................................................................................................33
8.2 Operating message 1....................................................................................................................33
8.3 Operating messages 2 to 4...........................................................................................................35
8.4 Operating message 5 –only with active service operating hours counter..................................35
8.5 Service and alarm messages .......................................................................................................36
9 Glossary...................................................................................................................................................38
10 Technical specifications.........................................................................................................................40
Regulations
2014/30/EU
2014/35/EU

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 3 14.07.2020
1 Safety instructions
The filter controls RM-310 C / RM-310 CT or RM-310 C Plug and Play / RM-310 CT Plug and
Play carry hazardous electrical voltage when connected to the mains.
Improper installation of
the connected electrical equipment may cause device failure, serious or even fatal injuries. In
addition to general safety rules for equipment in in
dustrial electrical installations, pay particular
attention to the following points:
The equipment must only be installed by qualified persons according to the provisions of the
standards IEC 364 and DIN VDE 0105 for electrical equipment.
All applicable la
ws, conditions, rules and regulations governing the installation of electrical
equipment must be observed.
Equipment with protection rating IP00 without covers must only be configured by authorised ex-
pert staff when disconnected and whilst observing the lo
cal safety and accident prevention
rules.
The filter controls RM-310 C / RM-310 CT or RM-310 C Plug and Play / RM-310 CT
Plug and
Play must only be operated within the permitted application range.
Switch off the supply voltage before replacing the filter controller
s or components connected to
them. Failure to do so may cause equipment damage.
Symbol explanation
Warning of physical and health hazards or damages to the product and other properties.
Important note

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 4 14.07.2020
2 Device descriptions
RM-310 C / RM-310 CT
The RM-310 C / RM-310 CT controller is the master control of the modular filter control system for filtering
separators with compressed air pulse cleaning. The front of the device with text display, membrane key-
pad and status LEDs is used to display operating and alarm messages and to set parameters. The intelli-
gent I/O modules handle decentral measuring and control tasks. The R-IMC-Bus (RECO – Inter Module
Communication) employed for data transfer between the individual control components was developed
specifically for use in industrial environments. Once the supply voltage and the intelligent I/O modules
have been connected the RM-310 C / RM-310 CT filter control works fully automated without further han-
dling.
The following diagram shows the general layout of an R-IMC bus controller environment with the controller
RM-310 C / RM-310 CT and the I/O modules RM-V 8 and RM-V 16 provided for this controller type for use
as a pulse filter.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 5 14.07.2020
RM-310 C Plug and Play / RM-310 CT Plug and Play
The controller types RM-310 C Plug and Play / RM-310 CT Plug and Play differ from the types
RM-310 C / RM-310 CT in that the prefabricated cables from RECO are used to connect the I/O modules.
This means that the time required for electrical installation is considerably less. The RM-V 6 I/O modules
intended for this plug-and-play system are available with 6 (RM-V 6/6), 5 (RM-V 6/5), 4 (RM-V 6/4) or 3
(RM-V 6/3) valves.
Since the controller types RM-310 C / RM-310 CT and RM-310 C Plug and Play / RM-310 CT
Plug and Play do not otherwise differ, for the sake of simplicity only the types RM-310 C /
RM-310 CT are mentioned in the further descriptions of this manual. The complete type desig-
nations only appear where there are differences.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 6 14.07.2020
Comparison of controller types
Controller type
Plug-and-play
system*
I/O module types
With a Δpsensor on
the controller board
RM-310 C
–
RM-V 8
RM-V 16
–
RM-310 CT
–
RM-V 8
RM-V 16
RM-310 C Plug and Play
RM-V 6/3
RM-V 6/4
RM-V 6/5
RM-V 6/6
–
RM-310 CT Plug and Play
RM-V 6/3
RM-V 6/4
RM-V 6/5
RM-V 6/6
*The I/O modules are connected to the controller and with each other via prefabricated cables.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 7 14.07.2020
3 Assembly
RM-310 C
RM-310 CT

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 8 14.07.2020
RM-310 C Plug and Play
RM-310 CT Plug and Play

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 9 14.07.2020
4 Installation
-

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 10 14.07.2020
Power supply
Connection of the I/O modules RM-V8 / RM-V16 to the controller types
RM-310 C / RM-310 CT
Digital inputs E1 ... E6, 24 V DC
Input
Factory-set function
E1
Release of the control when 1-signal is present
E2
The function is set with the parameter F2
E3
Acknowledge alarm
E4
Continuous cleaning with Interval 1
E5
Cleaning off (priority over Cleaning on)
E6
Cleaning release
The function of the inputs can be individ-
ually set via parameter group F0-F6. See
appendix 7 "Input and output signal par-
ametrisation, special parameter".
The prefabricated cables from RECO are
used to connect the RM
-V6/X I / O modules
to the controller types RM 310 C Plug and
Play /
RM 310 CT Plug and Play.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 11 14.07.2020
4-20mA input / 4-20mA output / 0-10V output
The function depends on the position of the jumpers JP 401 and JP 402
Differential pressure transmitter with a 4-20 mA output signal
4-20mA remote display (RM-310 CT or RM-310 C with I/O module and ∆psensor)
0-10V remote display (RM-310 CT or RM-310 C with I/O module and ∆psensor)

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 12 14.07.2020
Relay outputs A1 ... A4 connection, potential-free
Output
Factory-set function
A1
The relay contact closes as soon as the supply
voltage is applied to RM-310 C / RM-310 CT. It
opens any time an alarm is present (Group
Alarm).
A2
Contact closes when cleaning and downtime are
active.
A3
Contact closes at Δp-Min. Alarm
A4
Contact closes at Δp-Max. Alarm
The function of the outputs can be individually set via parameter group G0-G8. See appendix 7
"Input and output signal parametrisation, special parameter".
Shielded cables must be used for all bus and analogue signal lines! The shielding is to be ap-
plied one-sided and as short as possible.
Signal cables are not allowed to be installed parallel to power cables.
All cable glands must be firmly tightened to make sure the cables a
re solidly enclosed and no
water can enter.
Unused cable glands must be closed and replaced with blind plugs.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 13 14.07.2020
Differential pressure measurement cables
(only types RM-310 CT and RM-310 CT Plug and Play)

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 14 14.07.2020
5 Setting procedure
5.1 Function in "as delivered" condition
The following parameters must be set before operating the RM-310 C / RM-310 CT:
E0 Cleaning control functions
EA Number of valves
EB Number of I/O modules
The RM-310 C / RM-310 CT operates automatically once the cleaning control functions, number of valves
and number of I/O modules have been set.
Cleaning starts when the filter’s differential pressure Δp has reached the "DP-Start" value (factory set-
ting: 1200 Pa). The solenoid valves are controlled sequentially. By cleaning the differential pressure drops
after a certain period of time. Once the differential pressure has reached the value “DP-Start” minus
“DP-Hyster.” (factory setting: 300 Pa), i.e. the differential pressure is 1200 Pa - 300 Pa = 900 Pa, clean-
ing stops.
If a different function is desired or additional functions shall be activated, the parameter setting of the
RM-310 C / RM-310 CT must be changed. See sections 5.3 "Parameter selection level" to 5.9 "Parameter
list" on this.
5.2 Operating and display elements
- key
In parameterisation mode* to select parameters or values
(in up-arrow direction)
In operating mode to call text messages not shown
(in up-arrow direction)
ENTER key
In parameterisation mode* to confirm parameters
If a service or alarm message is present, to acknowledge the
message
- key
In parameterisation mode* to select parameters and values
(in down-arrow direction)
In operating mode to call text messages not shown
(in down-arrow direction)
* the RM-310 C / RM-310 CT is on the parameter selection or parameter setting level.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 15 14.07.2020
"ALARM" LED Lights when an alarm is present
"SERVICE" LED Lights when the filter requires maintenance.
"ON" LED Lights when the device is in operation
Does not light when the device is on the parameter selection level
Flashes when the device is on the parameter selection level
Display To display text messages (4 x 20 characters)
5.3 Parameter selection level
To view the parameters and their values the user must switch from the operating level to the parameter
selection level. The and keys must be pressed simultaneously until the green “ON“ LED goes off
(approx. 3 seconds).
All parameters with their set values can now be viewed in sequence by repeatedly pressing the or
key. Inactive or hidden parameters are automatically skipped (see section "Activated and deactivated pa-
rameters / faded in and faded out parameters" on this page).
Parameter blocks
To ensure an uncluttered view of the device’s parametrisation parameters referring to the same function
are grouped into blocks (C0, D0, E0, etc.). For example, the block D0 “Δp-controls” includes all parame-
ters (D1, D2, D3, etc.) referring to the differential pressure-dependent cleaning control (short: Δp-
controls).
Activated and deactivated parameters / faded in and faded out parameters
Two different types of parameter blocks are available: those that can be activated and deactivated and
those that can be faded in and faded out. A deactivated block is inactive. All parameters assigned to it are
without function and are not shown. With faded out parameter blocks the associated parameters are ac-
tive, that is, functioning. They are just not shown.
To activate a disabled parameter group or to fade in a faded out parameter group switching to
the parameter setting level is required (see section 5.4 "Parameter setting level" on page 17 on
this).
Parameter display examples
Parameter block C0, deactivated
Display Meaning
Parameter block C0 "Service operating hours"
The block is inactive (deactivated)
The block is protected by Code 5
C0 Ser.ope.hours
0 inactive
Parameter code 5

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 16 14.07.2020
Parameter block C0, activated
Display Meaning
Parameter block C0 "Service operating hours"
The group is active (activated without message)
The block is protected by Code 5
C0 Ser.ope.hours
1 act.w/o mess.
Parameter code 5
Parameter C1 of parameter block C0
Parameter block C0 "Service operating hours"
Parameter C1 “Counter mode”
Set value of the parameter C1
C0 Ser.ope.hours
C1 Counter mode
3 DP / Clean on
Parameter block D0, faded out
Parameter group D0 "Δp-control"
The block is faded out (parameter not visible)
The block is protected by Code 3
D0 DP-controls
0 faded out
Parameter code 3
Parameter block D0, faded in
Parameter group D0 "Δp-control"
The block is faded in (parameters are visible)
The block is protected by Code 3
D0 DP-control
1 faded in
Parameter code 3
Parameter D1 of parameter block D0
Parameter block D0 “Δp-controls“
Parameter D1 “ΔpCleaning mode“
Set value of the parameter D1
Parameter D1 is protected by Code 3
D0 DP-controls
D1 Cleaning mode
1 DP cont.clean.
Parameter code 3
Parameter block B0
Parameter block B0 “Display language”
The block consists only of parameter B0
Set value of the parameter B0
The block is not protected by a code
B0 Disp.language
0 D - Deutsch

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 17 14.07.2020
5.4 Parameter setting level
To change the value of a selected parameter or to activate and deactivate or fade in or fade out a parame-
ter block the user must switch from the parameter selection level to the parameter setting level. To do so,
the ENTER key must be pressed until the text display switches over (for parameters locked by a code) or
the green LED "ON" begins to flash (with unblocked or previously unblocked parameters).
For parameters blocked by a code, the entry of a 4-digit code is required to release the parame-
ter (refer to section 5.5 "Code input to clear locked parameters" on this).
Subsequently, the parameter value can be changed or the parameter block activated or deactivated or
faded in and faded out by pressing the or key.
To save the set value or the status of the parameter block (activated / deactivated or faded in / faded out)
and return to the parameter selection level the ENTER key must be pressed until the green LED “ON”
goes out (approx. 1 second).
5.5 Code input to clear locked parameters
There are 3 different codes that are used to allow access to certain parameters to authorised persons on-
ly. In the parameter selection mode, the row 4 of the display shows what code has to be entered to re-
lease the displayed parameter (parameter code 3, 4 or 5). If nothing is displayed in the row 4, the relevant
parameter can be accessed without code. The required codes can be found in section 5.9 "Parameter list"
on page 23.
The 4-digit code must be entered as follows:
1. The code digit is selected by briefly pressing the ENTER key.
2. The digit value is set by briefly pressing the or key.
3. The set code is confirmed by prolonged pressing of the ENTER key.
If the code entered is wrong the message “!Invalid input!” appears for 2 seconds. The code input
must be repeated.
If the code entered is correct the message “!!!! OK !!!!” appears for 2 seconds.
All parameters that were blocked by the same code are now released for setting. The parameters are
blocked again if no key of the device is pressed for 20 minutes.
5.6 Return to the operating level
To get to the operating level the and keys must be pressed simultaneously until the green LED lights
(approx. 3 seconds).

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 18 14.07.2020
5.7 Short guide for parameter setting
The ON LED indicates the current level of
the device.
LED lights Operating level
LED off Parameter selection level
LED flashing Parameter setting level
If no key has been pressed for 3 minutes the RM-310 C / RM-310 CT
automatically returns
from the parameter selection or the parameter setting level with the last values stored to the
operating level.

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 19 14.07.2020
5.8 Overview of menu navigation

Documentation RM-310 C / RM-310 CT / RM-310 C Plug and Play / RM-310 CT Plug and Play
RDN 10001104 20 14.07.2020
This manual suits for next models
3