
16
Assembly Instructions for
Service Personnel
Important instructions prior to installation
Prior to actual assembly, the following items have to be
checked and complied with:
àEnsure that the contents of the package are com-
plete and that the units have no visible damage re-
sulting from transport.
Any problems must be communicated directly to
your contract partner and the shipping company.
àPlace the unit in its original packaging as close as
possible to the location where it will be assembled to
prevent damage from transport.
àSelect a location to set up the unit where air can flow
freely in and out of the device, where the unit is not
in direct sunlight and is not close to other sources of
heat.
àAir should be distributed optimally throughout all ar-
eas of the room to be cooled and no drafts should be
created.
àPrior to installation, check that the electrical connec-
tion values and the data on the type plate are consis-
tent.
àMake sure that all electrical connections meet the
DIN-VDE requirements.
àLift the cassette on the corners and not with the re-
frigerant or condensation connections.
àPrior to unit assembly, the connection adaptors for
the adjacent room connection and the fresh air con-
nection must be attached.
àCarefully plan where the condensation line will be
laid.
àMake sure that, if laid horizontally, there is an ade-
quate incline.
At least 2 %.
àThe integrated pump can bridge a maximum height
difference of 250 mm on top of the unit.
But only if the condensation line flows immediately in
a vertical direction after leaving the unit and then
continues at an incline.
àRemove the protective caps of the unit connections
just before connecting the refrigerant lines.
àThe power supply is only connected to the outdoor
part. The control lines to the indoor unit should be
placed together with the refrigerant lines.
Common installation mistakes
When performing the installation, make sure to observe
the following to ensure smooth operation:
àDo not install the unit in the direct vicinity of objects
that emit intense heat (e.g. lights). Install it in the
middle of the room instead.
Wall lead-throughs
Wall lead-throughs are necessary to establish the con-
nection between the indoor unit and the outdoor part.
Please observe the following:
àFor the connection line to the outdoor part, a lead-
through of at least 70 mm in diameter must be cre-
ated.
àThe lead-through must be placed at an incline of at
least 2% from the inside to the outside.
àMake sure that there are no supply lines located in
the vicinity of the wall lead-through.
àThe air intake and outlet openings may not be
blocked by furniture, curtains, etc.
àPrevent unnecessary bends in the refrigeration lines
to minimise the pressure loss and ensure that the
compressor oil can recirculate properly.
àIf the outdoor part is mounted above the indoor unit,
take steps to recirculate the oil.
àIf this line is connected to the drainage line, an odour
seal must be installed the upper edge of which may
not extend beyond the lower edge of the indoor unit.
àThe refrigerant lines may not be bent or pressed.
àProtect open refrigerant lines from moisture with
suitable caps or adhesive.
àMake sure that all refrigerant lines including all con-
nectors and valves are adequately insulated against
heat.
àMount the outdoor part in such a way that the differ-
ence height to the indoor unit is not more than 10 m.
àMake sure that the maximum length of 15 m for the
basic length of the refrigerant line is not exceeded.
àUse a balance to position the unit precisely which will
prevent condensation from leaking out.
àEquip the ventilation lines for adjacent room cooling
and/or the fresh air connection including the connec-
tor piece with diffusion-sealed heat insulation.
àMake sure that the electrical connections have been
properly attached to the terminals.
Control line
Refrigerant
intake line
Condensation line
Refrigerant
injection line
àWe recommend cushioning the inside of the hole or
lining it to prevent the lines from being damaged.
Suitable materials are, for example, PVC pipes with
an inner diameter of 70 mm.
àAfter assembly is complete, the wall lead-through
must be sealed with a suitable sealing compound.
Do not use any materials containing cement or lime!