Schischek InMax CTM Series User manual

EXPLOSIONPROOF
InMax - ... - BF
InMax - ... - CTM
InMax - ... - VAM
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-BF_en
V04 – 9-Nov-2018
Subject to change!
Compact. Easy installation. Universal. Cost effective. Safe.
Product views and applications
Description Highlights
Fire damper Ball valve Throttle valve
Electrical rotary actuators for use in safe areas with
integrated tripping circuit for safety temperature trigger InPro-TT
On-off / 3-pos. control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension
30 – 50 – 60 Nm with safety operation (spring return)
Type Torque Supply Motor running time Spring return Control mode Feedback Wiring diagram
InMax- 30 - BF 30 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 20 s/90° On-off, 3-pos. 2 × aux. switches + tripping circuit SB 7.2/7.3
InMax- 50 - BF 50 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 / 150 s/90° ~ 20 s/90° On-off, 3-pos. 2 × aux. switches + tripping circuit SB 7.2/7.3
InMax- 60 - BF 60 Nm 24...240 VAC/DC 40 / 60 / 90 / 120 s/90° ~ 20 s/90° On-off, 3-pos. 2 × aux. switches + tripping circuit SB 7.2/7.3
InMax- ... - CTM Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
InMax- ... - VAM Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
InMax ¼ turn actuators – size M
►Industrial use
►Universal supply unit from 24…240 VAC/DC
►Motor running times 40– 60–90–120 –150 s/90° adjustable on site
►On-off and 3-pos. control with spring return function, running time ~ 20 s/90°
►Circuit for direct connection of the ...Pro-TT-... safety temperature trigger
►2 integrated auxiliary switches, switching at 5° and 85° angle of rotation
►30– 50–60 Nm actuators in the same housing size
►100 % overload protected
►Compact design and small dimension (L × W × H ~ 288 × 149 × 116 mm)
►Direct coupling to the damper shaft with double square connection 16 × 16 mm
►95° angle of rotation inclusive 5° pretension
►Robust aluminium housing (optional with seawater resistant coating)
or in stainless steel
►IP67 protection
►Simple manual override included + preparation for comfortable manual override
►Gear made of stainless steel and sinter metal
►Weight only ~ 9,5 kg
►Integrated heater for ambient temperatures down to −40 °C
►Integrated safety temperature sensor
►Integrated equipment for manual adjustment (push button, lamp, switch)
►Preparation for adaptable and adjustable auxiliary switches type ...Switch
►Wide range of accessories
The InMax actuators are a revolution for safety, fire and shut-off damp-
ers, VAV systems, ball valves, throttle valves and other motorized appli-
cations for HVAC systems in chemical, pharmaceutical, industrial and
offshore/onshore plants.
IP67 protection, small dimensions, only 9,5 kg weight, universal functions
and technical data, an integrated heater and an optional stainless steel
housing guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. The actuators are
100 % overload protected.
...Max-...-BF actuators are equipped with spring return fail safe function,
with 2 integrated auxiliary switches for end position indication and a
tripping circuit for connecting the ...Pro-TT-... safety temperature trigger.
Standard shaft connection is a double square direct coupling with
16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
1 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-BF_en
V04 – 9-Nov-2018
InMax-...-BF
Special option ... -CTM ... -VAM
Approbations Special solutions and accessories
...-CTM Types in aluminium housing with seawater resistant coating,
parts nickel-plated
...-VAM Types in stainless steel housing, parts nickel-plated
InBox-... Terminal boxes
MKK-M Mounting bracket for boxes type ...Box-... directly on actuator
InPro-TT-... Safety temperature trigger for fire dampers
InSwitch 2 external aux. switches, adjustable
HV-MK Comfortable manual override for ...Max actuators size M
AR-16-xx Reduction part for 16 mm square connection to 14 or 12 mm shafts
Kit-S8 Cable glands nickel-plated
Adaptions for dampers and valves on request
InMax-...-S3 Ambient temperature up to +60 °C, 110...240 V AC/DC, 25 % ED
Torque motor (min.) 30 Nm 50 Nm 60 Nm
Torque spring (F) min. 30 Nm min. 50 Nm min. 60 Nm
Torque blockade In blockade and end positions torques are higher than above specified torques for motor and spring.
Dimensioning of external load Upon spring return the external load should be max. 80 % of torque spring (F), but min. 10 Nm
Supply voltage / frequency 24...240 VAC/DC ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %
Power consumption max. starting currents see Extra information (in acc. with voltage, I start >> I rated ), approx. 5 W holding power, approx. 16 W for heater
Protection class Class I (grounded)
Angle of rotation and indication 95° incl. ~ 5° pretension, mechanical value indication
Working direction Selectable by left/right mounting to the damper/valve shaft
Motor running times 40 / 60 / 90 / 120 / 150 s/90° 40 / 60 / 90 / 120 / 150 s/90° 40 / 60 / 90 / 120 s/90° selectable on site
Motor Brushless DC motor
Control mode On-off and 3-pos. in acc. with wiring, selectable on site
Spring return (F) spring return upon voltage interruption, response time up to 1 sec. after voltage interruption
Spring return running time (F) ~ 20 s/90°
Safety operations at 20 sec. (F) min. 10,000 acc. to construction of damper and ambient
Tripping circuit Circuit to connect the InPro-TT-... safety temperature trigger directly to the actuator with M12 quick connection
Auxiliary switches 2 integrated auxiliary switches, switching at 5° and 85° angle of rotation, potential free. Grid fuse-protection is recommended!
Umax/ Imax AC = 250 V/5 A; Umin AC/DC = 5 V; After one-time operation with U > 24 V AC/DC or I > 100 mA: Umin AC/DC = 12 V
Umax/ Imax DC = 48 V/1 A; Imin AC/DC = 5 mA; Imin AC/DC = 100 mA
Axle of the actuator Double square 16 × 16 mm, direct coupling, 100 % overload protected
Electrical connection Cable ~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm². Connections require a terminal box!
Diameter of cable ~ Ø 9,6 mm ~ Ø 9,6 mm ~ Ø 9,6 mm
Cable gland M16 × 1.5 mm
Manual override Use delivered socket wrench, max. 4 Nm
Heater Integrated, controlled heater for ambient temperature down to −40 °C
Housing material Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTM) or stainless steel housing,
№1.4581 / UNS-J92900 / similar AISI 316Nb (...-VAM)
Dimensions (L × W × H) ~ 288 × 149 × 116 mm, for diagrams see Extra information
Weight ~ 9.5 kg aluminium housing, stainless steel ~ 15 kg
Ambients Storage temperature −40…+70 °C, working temperature −40…+50 °C
Humidity 0...90 % rH, non condensing
Operation mode 80 % ED are permitted (ED = duty cycle)
Maintenance Maintenance free relative to function, maintenance must comply with regional standards, rules and regulations
Wiring diagrams SB 7.2 / 7.3 SB 7.2 / 7.3 SB 7.2 / 7.3
Scope of delivery Actuator, 4 screws M8 × 140 mm, 4 nuts M8, Allen key for simple manual override
Parameter at delivery 30 Nm, 90 s/90° 50 Nm, 90 s/90° 60 Nm, 90 s/90°
CE identification CE
EMC directive 2014/30/EU
Low voltage directive 2014/35/EU
Enclosure protection IP67 in acc. with EN 60529
Technical data InMax- 30 - BF InMax- 50 - BF InMax- 60 - BF
2 / 4
EXPLOSIONPROOF
InMax- 30 -BF ►
InMax- 50 -BF ►
InMax- 60 -BF ►
30 Nm
50 Nm
60 Nm
▼
40 s/90° ►
60 s/90° ►
90 s/90° ►
120 s /90° ►
150 s /90° ►
00
01
02
03
04
05
06
07
08
09
InBoxInPro-TT
a b
+
~
+
~
−
~
−
~
PE
PE
1
1
2
2
3
3
4
4
24...240 VAC/DC
24...240 VAC/DC
PA
PA5
5
8
8
6
6
7
7
9
9
10
10
< 5°
< 5°
> 85°
> 85°
1
1
2
2
°C
°C
InPro-TT
InPro-TT
U < 90 V AC/DC 2 AT 10 AT
U > 90 V AC/DC 5 AT 10 AT
U < 90 V AC/DC 2 AT 10 AT
U > 90 V AC/DC 5 AT 10 AT
S
T
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-BF_en
V04 – 9-Nov-2018
InMax-...-BF
Special option ... -CTM ... -VAM
Electrical connection Parameters, adjustments and failure indication
Parameter selection
Functions, adjustments and parameters
Type
Running times Position of switch (S)
Torques
Example:
InMax-30-BF
Requested parameter:
Torque 30 Nm
Motor running time 90 s/90°
Result:
Switch position 02
All actuators are equipped with a universal supply unit working at a voltage range from
24...240 VAC/DC. The supply unit is self adjusting to the connected voltage!
The safety operation of the spring return function works if the supply voltage is cut.
For electrical connection a terminal box is required (e.g. InBox).
An over-current protection fuse < 10 A has to be provided by installer.
Note: the initial current is appr. 2 A for 1 second.
Integrated auxiliary switches signal the rotation angle’s position. U
min
and I
min
change once
the switches were operated with higher voltage or current.
Installation
Supply *
24...240 VAC/DC ± 10 %
* electrical wiring see diagrams
Auxiliary switches *
see Technical data
On-off (1-wire) – spring return + tripping circuit SB 7.2
On-off / 3-pos. – spring return + tripping circuit SB 7.3
Tripping circuit for
InPro-TT-... safety
temperature trigger
Test
button
Test
button
Attention!
At 1-wire control
mode the heater
does not work
in case of
open contact.
Tripping circuit for
InPro-TT-... safety
temperature trigger
Integrated auxiliary switches,
Grid fuse-protection recommended.
min. max.
Integrated auxiliary switches,
Grid fuse-protection recommended.
min. max.
A) Self adjustment of angle of rotation
Turn switch (S) to position 02. Press button (T) for a minimum of 3 seconds. The
actuator drives to both end positions and detects the blocking positions. The LED
flashes GREEN during adjustment.
The adjustment takes about 60 seconds (30 sec. “On”, 30 sec. “Off”).
B) Selecting motor running time and torque
Adjust parameters only if actuator is in idle state or without applied potential.
Turn switch (S) to the position required for the intended operation acc. to table
above. The selected parameters will be carried out at the actuator’s next operation.
C) Function of the InPro-TT-... in the tripping circuit
When the ...Pro-TT’s tripping circuit is opened the actuator runs into its end position
with spring return.
D) Additional information for control in 3-pos. operation
a closed, b open = direction I a and b closed = motor doesn’t work
b closed, a open = direction II a and b open = motor doesn’t work
The rotation direction (I and II) depends on left/right mounting of the actuator to the
damper. To reverse the rotation direction (by motor) exchange the electrical wiring
of terminal 3 and 4.
Attention
During commissioning apply a self adjustment drive.
Regard duty cycle at motor running times!
Never use spring return actuators without external load.
Switch – Push button – Lamp
for adjustment
(behind the blanking plug)
10-position switch (S)
3-colour LED
Push button (T)
3 / 4
EXPLOSIONPROOF
www.schischek.com
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]
InMax-M-BF_en
V04 – 9-Nov-2018
InMax-...-BF
Special option ... -CTM ... -VAM
Important information for installation and operation
Accessory InBox – terminal boxAccessory InSwitch – auxiliary switch
Extra information (see additional data sheet)
Additional technical information, dimensions, installation instruction, illustration
and failure indication
A. Installation, commissioning, maintenance
All national and international standards, rules and regulations must be complied with.
Apparatus must be installed in accordance with manufacturer instructions. If the equipment
is used in a manner not specified by the manufacturer, the safety protection provided by
the equipment may be impaired.
For electrical connection a terminal box is required (e.g. InBox-...).
Attention: If the actuator is put out of operation all rules and regulationsmust be applied.
You have to cut the supply voltage before opening the terminal box!
The cablesof the actuator must be installed in a fixed position and protected against
mechanical and thermical damage. Connect potential earth. Avoid temperature transfer
from armature to actuator! Close all openings with min. IP67.
For outdoor installation a protective weather shield against sun, rain and snow should be
applied to the actuator as well as a constant supply at terminal 1 and 2 for the integrated
heater. During commissioning apply a self adjustment drive.
Actuators are maintenance free. An annual inspection is recommended. Actuators must
not be opened by the customer.
B. Manual override
Manual override only if supply voltage is cut. Use delivered socket wrench with slow
motions, usage can be tight.
Attention: Releasing or letting go the Allen key too fast at manual operating actuators
with spring return causes risk of injury!
C. Shaft connection, selection of running time
Actuators are equipped with a direct coupling double square shaft connection of 16 × 16 mm.
The housing of the actuator is axially symmetrically built to select Open-close direction
of the spring return function by left-right mounting. Using the 10-position switch different
motor running times and spring return running times can be selected on site in acc. to
the actuator type.
D. Temperature trigger ...Pro-TT-...
The actuator ...Max-...-BF will work only with the temperature trigger InPro-TT-...
E. 3-position control mode
...Max actuators are in the best way suitable for the 3-pos. operation. To protect such
elements as gears and mounting elements against harmful influences like minimum
pulse time, ...Max actuators are protected via internal electronics. It ignores impulses
< 0,5 s, the cyclic duration must be min. 0,5 s. At changing direction the pause is 1 s.
F. Spring return
Spring return function works only if the supply voltage for terminal 1 or 2 is cut. In the
event of an electrical interruption, the spring returns to its end position even if supply
voltage is available again during return function. Thereafter operation will continue.
G. Operation at ambient temperatures below −20 °C
All actuators are equipped with a regulated integrated heating device designed for
employments down to −40 °C ambient temperature. The heater will be supplied automatically
by connecting the constant voltage supply on the clamps 1 and 2.
1. After mounting the actuator must bei immediately electrically connected.
2. The heater switches on automatically when actuator reaches internally −20 °C. It
heats up the actuator to a proper working temperature, then heater switches off
automatically. Actuator will not run during heating process.
3. The adjustment options are only ensured after this heating up period.
H. Excess temperatures
All actuators are protected against excess temperature. The internal thermostat works
as a maximum limiter and, in the event of failure at incorrect temperatures, shuts off the
actuator irreversible. An upstream connected temperature sensor stops the actuator
before reaching its max. temperature. This safety feature is reversible, after cooling down
the actuator is completely functional again. In this case the failure must be eliminated
immediately on site!
I. Synchron mode
Do not connect several actuators to one shaft or link mechanically together.
J. Mechanical protection
Actuators must be operated with a minimum external load.
After installing the actuator to the damper/armature a self adjustment drive has to be
performed in order to protect the damper/armature against mechanical overload.
During operation the actuator reduces briefly its speed (motor power) before reaching
the end position for a “gentle” blockade/stop.
K. Routine tests of fire dampers
For periodic inspection of fire dampers cut off the supply line (current of actuator).
The test button at InPro-TT-... is only for test aims of actuator’s function.
For an end or inclined position indication it is possible to
retrofit external, adjustable auxiliary switches type
InSwitch.
The ...Switch is mounted directly to the actuator. The
switches deliver a potential free output and can be adjusted
separately. They are connected by cable.
For electrical connection of the ...Max actuator a terminal
box is required.
To adapt the ...Box directly to the actuator housing a mounting
bracket is required.
InBox- BF for ...Max-...-BF
4 / 4

Other manuals for InMax CTM Series

1

This manual suits for next models

5

Other Schischek Controllers manuals

Schischek RedMax BF-VA Series User manual

Schischek

Schischek RedMax BF-VA Series User manual

Schischek ExMax CY Series User manual

Schischek

Schischek ExMax CY Series User manual

Schischek ExMax F3 Series User manual

Schischek

Schischek ExMax F3 Series User manual

Schischek ExReg-V CT Series User manual

Schischek

Schischek ExReg-V CT Series User manual

Schischek InMax SF3 Series User manual

Schischek

Schischek InMax SF3 Series User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek Redmax Series Quick start guide

Schischek

Schischek Redmax Series Quick start guide

Schischek ExMax BF User manual

Schischek

Schischek ExMax BF User manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Schischek InMax CTM Series User manual

Schischek

Schischek InMax CTM Series User manual

Schischek InMax-8-F1 User manual

Schischek

Schischek InMax-8-F1 User manual

Schischek ExMax Series User manual

Schischek

Schischek ExMax Series User manual

Schischek RedMax BF Series User manual

Schischek

Schischek RedMax BF Series User manual

Schischek ExMax-50.75 Owner's manual

Schischek

Schischek ExMax-50.75 Owner's manual

Schischek RedMax-30-BF User manual

Schischek

Schischek RedMax-30-BF User manual

Schischek ExRun Y Series User manual

Schischek

Schischek ExRun Y Series User manual

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek RedMax User manual

Schischek

Schischek RedMax User manual

Schischek RedMax-8-F1 User manual

Schischek

Schischek RedMax-8-F1 User manual

Schischek ExMax CTM Series User manual

Schischek

Schischek ExMax CTM Series User manual

Schischek RedMax-Y Series User manual

Schischek

Schischek RedMax-Y Series User manual

Schischek ExMax CTS Series User manual

Schischek

Schischek ExMax CTS Series User manual

Schischek InMax-100 User manual

Schischek

Schischek InMax-100 User manual

Schischek ExMax User manual

Schischek

Schischek ExMax User manual

Popular Controllers manuals by other brands

Heyl Softmaster ROE 2 operating instructions

Heyl

Heyl Softmaster ROE 2 operating instructions

MecVel ALI4 Use and maintenance handbook

MecVel

MecVel ALI4 Use and maintenance handbook

Amico 401 Series Operation & maintenance instructions

Amico

Amico 401 Series Operation & maintenance instructions

GeneralAire Water Savor installation instructions

GeneralAire

GeneralAire Water Savor installation instructions

PS Automation PSAP.2A installation instructions

PS Automation

PS Automation PSAP.2A installation instructions

CKD ECG Series instruction manual

CKD

CKD ECG Series instruction manual

YASKAWA PROFINET V1000 Technical manual

YASKAWA

YASKAWA PROFINET V1000 Technical manual

Omron CPM2C Operation manual

Omron

Omron CPM2C Operation manual

ICP DAS USA Compact Embedded Controller LinCon-8000 Hardware user manual

ICP DAS USA

ICP DAS USA Compact Embedded Controller LinCon-8000 Hardware user manual

HomLiCon LCH5T quick start guide

HomLiCon

HomLiCon LCH5T quick start guide

Garnet SPILLSTOP ULTRA 815-UHP user manual

Garnet

Garnet SPILLSTOP ULTRA 815-UHP user manual

Omron MECHATROLINK-II MP2100 datasheet

Omron

Omron MECHATROLINK-II MP2100 datasheet

DeVilbiss KK-4456 Service manual

DeVilbiss

DeVilbiss KK-4456 Service manual

National Instruments cRIO-9023 User manual and specifications

National Instruments

National Instruments cRIO-9023 User manual and specifications

ICP DAS USA XP-9 88-IoT Series quick start

ICP DAS USA

ICP DAS USA XP-9 88-IoT Series quick start

FlowCon FT.0.3 Installation and operation instruction

FlowCon

FlowCon FT.0.3 Installation and operation instruction

Innovative SIMPLE1 operating manual

Innovative

Innovative SIMPLE1 operating manual

Agilent Technologies 78581B Installation and service guide

Agilent Technologies

Agilent Technologies 78581B Installation and service guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.