In the Demand circulation mode, the secondary pump will be activated for the
adjustable runtime Circ. run, when a draw-off has been detected.The Toff circ.
switch-off temperature serves as the switch-off condition.
Thermal
In the Thermal circulation mode, the secondary pump is activated and deactivat-
ed depending on the adjustable temperaturesTon circ. and Toff circ. Additionally,
three time frames can be adjusted for each day of the week. Outside these time
frames, the circulation remains inactive.
Therm.+Dem.
In theTherm.+Dem. circulation mode, both switching conditions are valid. Demand
takes priority: the secondary pump will be activated upon a draw-off, even if the
switch-on conditions for the Thermal circulation mode are not ful lled. The Toff
circ. switch-off temperature serves as the switch-off condition.
Depending on the circulation mode selected,further adjustment channels will appear:
Circulation ow rate calibration
The circulation ow rate calibration enables the controller to detect a DHW
draw-off even while the secondary pump is running.
The circulation ow rate calibration can be carried out in the Circ. ow rate
submenu.
The calibrated value for the circulation ow rate and the date of the last calibration
are available.
If the Calibration menu item is selected,the secondary pump is activated at 100%
speed and the ow rate is measured at the VFD. The value measured is stored as
the circulation ow rate and will be displayed in the Circ. ow rate channel.This
value then serves as the reference value for the draw-off detection.
In the "last" display channel, the date of the last calibration is indicated.
Note
If a circulation is implemented, make sure to run a calibration! Until the
calibration has been carried out, the secondary pump is blocked!
In this case, the acknowledgeable message Run calibr. circ. pump is
displayed when leaving the menu.
Note
In order to run the calibration, all draw-off points must be closed.
If the ow rate exceeds the reference value while the secondary pump is active, the
controller detects a draw-off and the circulation pump will be deactivated.
Circulation switch-on temperature
Ton circ.
Adjustment range: 30 … 59 °C
Factory setting: 40 °C
Circulation switch-off temperature
Toff circ.
Adjustment range: 31 … 60 °C
Factory setting: 45 °C
If the Thermal or Therm.+Dem. circulation mode has been selected, a switch-
on temperature Ton circ. can be adjusted for the circulation.The switch-off tem-
perature Toff circ. can be adjusted in all circulation modes (except for none).
If the temperature at sensor S3 in the secondary circuit falls below the switch-on
temperature, the controller activates the secondary pump.