STA-W
© RESOL09058_STA-W_monen.indd
5 |
The following status are signalled via the VBus® -LED
• off: no VBus®-connection
• red flashing: error:
STA-W does not recognise the de-
vice connected or the heat quantity
measurement option of the controller
has not been activated.
• red/green flashing: initialisation phase:
the device connected has been recog-
nised and the VBus®data packets are
processable. The potential-free contact
has not yet been operated.
• green: normal operation:
VBus®data packets are processable,
the potential-free contact is being
operated.
3. VBus®-LED
The STA-W is an interface that transmits heat quantity
measurement values between RESOL devices and external
appliances. It is to be connected to a RESOL controller or
calorimeter via the RESOLVBus®.The STA-W receives and
processes the VBus®data packets of the device connected
and calculates the difference in heat quantity measurement
values.
Whenever the new kWh value exceeds the previous by
1 kWh, the STA-W operates a potential-free contact which
can e.g. be connected to a building management system
(BMS). For example: if the new value exceeds the previous
by 5 kWh, the STA-W will operate the contact five times.
The number of accumulated contacts can thus be visualised
as a heat quantity value in the BMS software.
4. Function
A maximum of five contacts per second is possible.
If the STA-W does not receive a processable VBus®data
packet for a period of one minute, the next incoming heat
quantity measurement value will be set as a base value for
the next difference calculation. The potential-free contact
will be operated as soon as the new base value is exceeded
by at least 1 kWh in a following data packet.
The increase in heat quantity during the malfunction will not
be recorded and must, if necessary, be manually corrected
in the BMS.
An increase of more than 50 kWh between twoVBus®data
packets cannot be processed.In such a case, the STA-W will
set the new heat quantity measurement value as a base value
for the next difference calculation, but will not operate the
potential-free contact.