Heating circuits
The controller has two internal, weather-compensat-
ed heating circuits and is able to control up to 5 ex-
ternal heating circuits by means of extension modules.
In the menu appearing when New heating circuit is
selected, it is possible to choose between the internal
heating circuits and, if available, registered modules.
If one or more extension modules are connected,
they have to be registered with the controller. Only
registered modules are available in the heating circuit
selection.
Extension modules can be registered in the In-/Out-
puts / Modules menu (see controller manual). If an
internal or external heating circuit has been selected,
a new menu opens. In this menu, all sensors and relays
required for the heating circuit can be allocated, and
all adjustments can be made.
The controller calculates the set fl ow temperature for
each heating circuit by means of the outdoor temper-
ature and the selected heating curve. If the measured
fl ow temperature deviates from the set fl ow tempera-
ture, the mixer is activated in order to adjust the fl ow
temperature correspondingly.
If the outdoor temperature falls below the point
where the calculated set fl ow temperature would ex-
ceed the maximum fl ow temperature, the maximum
fl ow temperature is treated as the set temperature
for as long as the condition remains.
If the outdoor temperature sensor is defective, an
error message is indicated. For the duration of this
condition, the maximum fl ow temperature -5 K is as-
sumed as set fl ow temperature.
With the timer, the day / night operation can be ad-
justed. During day phases, the set fl ow temperature is
increased by the adjusted day correction value, during
night phases it is decreased by the night correction
value (night setback).
Summer mode
The Mode channel adjustment determines how the
heating circuit is set to summer mode:
Summer off: The summer mode becomes active
when the outdoor temperature exceeds the adjusted
summer temperature TSummer.
Ext. switch: A switch is connected to a selected sen-
sor input. If the switch is operated, the heating circuit
is set to summer mode regardless of the outdoor
temperature.
Both: As long as the switch is not operated, summer
mode control works as described for Summer off.
Summer mode is activated regardless of the outdoor
temperature when the switch is operated.
Summer temperature
If Summer off or Both has been selected in the
Mode channel, the summer temperature TSummer
can be adjusted. If the outdoor temperature exceeds
the value adjusted in TSummer, the heating circuit
pump is switched off.
For the summer temperature, a daytime time frame
can be adjusted with the channels Daytime on and
Daytime off. Outside this time frame, the adjustable
temperature TNight replaces TSummer.
With the Room thermostat option, up to 5 room
thermostats can be integrated into the control logic.
To each room thermostat, a sensor input can be al-
located. The temperature at the allocated sensor is
monitored. If the measured temperature exceeds the
adjusted Room temperature value at all activated