InstallationIndications, functions and optionsMessages Commissioning Operation and function
Display channels
Channel Description Connection terminal Page
INIT x* ODB initialisation active - 38
FLL x* ODB lling time active - 38
STAB x* ODB stabilisation in progress - 38
COL x Temperature collector S1 38
TSTB x Temperature store 1 base S2 38
TSTT x Temperature store 1 top S3 38
TDIS s* Thermal disinfection temperature
(thermal disinfection)
S3 17
S4 x Temperature sensor 4 S4 39
TR x* Temperature return sensor S4 38
n1 % x Speed R1 R1 39
h P1 x Operating hours R1 R1 40
h P2 x Operating hours R2 R2 40
kWh x* Heat quantity in kWh - 39
MWh x* Heat quantity in MWh - 39
CDIS s* Countdown of monitoring period
(thermal disinfection)
-40
SDIS s* Starting time display (thermal disinfection) -39
DDIS s* Heating period display (thermal disinfection) -39
TIME x Time -40
Adjustment channels
Channel Description Factory setting Page
Arr x System 3 41
DT O xSwitch-on temperature difference 6.0 K [12.0 °Ra] 41
DT F xSwitch-off temperature difference 4.0 K [8.0 °Ra] 41
DT S x Set temperature difference 10.0 K [20.0 °Ra] 42
RIS x Rise R1 2 K [4 °Ra] 42
n1MN x Minimum speed R1 30 % 42
S MX x Maximum store temperature 60 °C [140 °F] 42
OSEM xStore emergency shutdown option OFF 43
EM x
Collector emergency temperature 130 °C [270 °F] 43
Collector emergency temperature, if OBST is
activated:
95 °C [200 °F] 43
OCC x Collector cooling option OFF 43
CMX x* Maximum collector temperature 110 °C [230 °F] 43
OSYC x System cooling option OFF 44
DTCO x* Switch-on temperature difference cooling 20.0 K [40.0 °Ra] 44
DTCF x* Switch-off temperature difference cooling 15.0 K [30.0 °Ra] 44
OSTC x Store cooling option OFF 44
OHOL x* Holiday cooling option OFF 44
THOL x* Holiday cooling temperature 40 °C [110 °F] 44
Adjustment channels
Channel Description Factory setting Page
OCN x Collector minimum limitation option OFF 45
CMN x* Collector minimum temperature 10 °C [50 °F] 45
OCF x Antifreeze option OFF 45
CFR x* Antifreeze temperature 4.0 °C [40.0 °F] 45
OTC x Tube collector option OFF 47
TCST x* OTC starting time 07:00 47
TCEN x* OTC ending time 19:00 47
TCRU x* OTC runtime 30 s 47
TCIN x* OTC standstill interval 30 min 47
OHQM xHeat quantity measurement option OFF 47
FMAX x* Maximum ow rate 6.0 l 47
MEDT x* Heat transfer uid / Antifreeze type 1 48
MED% x* Antifreeze concentration 45 % 48
AH O sSwitch-on temperature for thermostat 1 40 °C [110 °F] 16
AH F sSwitch-off temperature for thermostat 1 45 °C [120 °F]16
t1 O s Thermostat switch-on time 1 00:00 16
t1 F s Thermostat switch-off time 1 00:00 16
t2 O s Thermostat switch-on time 2 00:00 16
t2 F s Thermostat switch-off time 2 00:00 16
t3 O s Thermostat switch-on time 3 00:00 16
t3 F s Thermostat switch-off time 3 00:00 16
ODB xDrainback option OFF 48
tDTO x* ODB switch-on condition - time period 60 s 48
tFLL x* ODB lling time 5.0 min 49
tSTB x* ODB stabilisation time 2.0 min 49
OTD s Thermal disinfection option OFF 17
PDIS s* Monitoring period 01:00 17
DDIS s* Heating period 01:00 17
TDIS s* Disinfection temperature 60 °C [140 °F] 17
SDIS s* Starting time 00:00 17
MAN1 x Manual mode R1 Auto 49
MAN2 x Manual mode R2 Auto 49
ADA1 xHE pump control OFF 49
LANG x Language dE 50
UNIT x Temperature unit °C 50
RESE x Reset - back to factory settings 50
######## Version number
Legend:
Symbol Description
x Channel is available
x* Channel is available, if the corresponding option is activated
sSystem-specic channel
s* System-specic channel, only available if the corresponding option is activated