en
6
S1
S2
S3
S4
S5
S6
S7
S8
R4
R5
IP20
R5
N
R1-R4
100 ... 240 V~
50-60 Hz
T4A
1 (1) A 240 V~
4 (1) A 240 V~
4 (1) A 24V
R5
R3
R2
R1
L' L
GND
Temp. Sensor
PWM/0-10V
RPD
N
Isolate mains before removing cover!
Vor Öffnen Gerät spannungslos schalten!
Use ground common terminal block
Masse-Sammelklemme benutzen
Use neutral conductor common terminal block
Neutralleiter-Sammelklemme benutzen!
Use PE Common terminal block
Schutzleiter-Sammelklemme benutzen
VFD
CS10
V40/S9
VBus
VBus
GND
HC
Made in Germany
input for Grundfos
Direct Sensors™
potential-free relay
sensor ground common
terminal block
sensor terminals
protective conductor
common terminal block (PE)
neutral conductor
common terminal block
PWM (0-10 V) terminals
VBus®
2.2 Electrical connection
WARNING! Electric shock!
Upon opening the housing, live parts
are exposed!
ÎAlways disconnect the con-
troller from power supply
before opening the housing!
WARNING! ESD damage!
Electrostatic discharge can lead to
damage to electronic components!
ÎTake care to discharge prop-
erly before touching the
inside of the device!To do
so, touch a grounded surface
such as a radiator or tap!
Note
Connecting the device to the power supply
must always be the last step of the instal-
lation!
Depending on the product version, cables are already
connected to the device. If that is not the case, please
proceed as follows:
The controller is equipped with 5 relays in total to
which loads such as pumps, valves, etc. can be con-
nected:
Relays 1 ... 4 are semiconductor relays, designed for
pump speed control:
Conductor R1 ... R4
Neutral conductor N (common terminal block)
Protective earth conductor PE (common terminal
block)
Relay 5 is a potential-free relay (normally open contact):
Connections to the R5 terminals can be made with
either polarity.
Temperature sensors (S1 to S9) have to be con-
nected to the terminals S1 ... S9 and GND (either po-
larity).
The terminal S9 can be used as an impulse input for a
V40 flowmeter or a FS08 flow switch.
A V40 flowmeter can be connected to the terminals
S9 /V40 and GND (either polarity).
Connect the irradiation sensor CS10 to the termi-
nals CS10 and GND with correct polarity. To do so,
connect the cable marked GND to the GND com-
mon terminal block, the cable marked CS to the ter-
minal marked CS10.
The terminals marked PWM are control outputs for
high-efficiency pumps.
In the In-/Outputs menu, relays can be allocated to
the PWM outputs.
Connect the digital Grundfos Direct Sensors™ to
the RPD and VFD inputs.
The controller is supplied with power via a mains
cable. The power supply of the device must be
100 ... 240 V~ (50 ... 60 Hz).
The mains connection is at the terminals:
Neutral conductor N
Conductor L
Conductor L' (L' is not connected with the mains
cable. L' is a fused contact permanently carrying
voltage)
Protective earth conductor PE (common termi-
nal block)
WARNING! Electric shock!
L' is a fused contact permanently
carrying voltage.
ÎAlways disconnect the con-
troller from power supply
before opening the housing!
Note
For more details about the initial commis-
sioning procedure, see page 12.