REVENTON AERIS 90EN-3P Guide

Technical documentation
ELECTRIC HEATED AIR CURTAIN
MODELS:
REVENTON GROUP AERIS 90EN-3P
REVENTON GROUP AERIS 120EN-3P
REVENTON GROUP AERIS 150EN-3P

For heated rooms, set the steering wheel in the opposite direction to the room
with the curtain at an angle of 0 -15 degrees (see figure).
For canteens, kitchens, set the steering wheel towards the room with the curtain
at an angle of 0 -15 degrees (see figure).
2. DEVICE CHARCTERISTICS
2.1 DIMENSIONS
1. INTRODUCTION
1.1.PRECAUTIONS
1.2.TRANSPORT
1.3.PACKAGE CONTENT
1.4.USE
2.DEVICE CHARCTERISTICS
2.1 DIMENSIONS
2.2 TECHNICAL DATA
3. INSTALLATION
3.1. GENERAL PRINCIPLES
3.2. ASSEMBLY „STEP BY STEP”
4. INSTALLATION INSTRUCTIONS
4.1 CONNECTION OF THE DEIVCE TO THE ELECTRICAL SYSTEM
5. PRECAUTIONS AND WARNINGS
6. CONTROLS
7.CONNECTION SCHEMES
8.TERMS OF WARRANTY
1. INTRODUCTION
Thank you for purchasing Reventon Group air curtain. We would like
to congratulate on good choice. Please read and save these instructions.
1.1 PRECAUTIONS
The buyer and the user of the device should read carefully the following
instructions and proceed to the content recommendations. Proceeding
due to the following instruction guarantees the correct usage and safety. In case
of any doubts please contact the Reventon Group Sp. z o.o. The Supplier reserves
the rights to make changes to the technical documentation without previous
notice. The Supplier is not responsible for the damages which occur
due to improper installation, not keeping the device in repair or using the device
out of line. The installation should be carried out by the professional installers,
who possess the qualifications to install these types of devices. The installers
are responsible for making the installation as instructed in the technical data.
Regulations and safety rules must be followed. During the installation,
use, service and periodical inspections all regulations and safety rules must
be followed. In case of unserviceable please plug out the device and contact
with the authorized person or the Supplier. All safety requirements must
be taken into account during installation, use or inspection.
1.2 TRANSPORT
During the acceptance of goods it is needed to check the device in order
to exclude any damages. During the transport it is needed to use the proper
equipment, it is necessary to carry the device by two people. In case
of any damages please fill in the damage report in presence of the Supplier
or the carrier.
1.3 PACKAGE CONTENT
- air curtain
- operation and maintenance manual and warranty card
- assembly panel
- door sensor
1.4 USE
Air curtains are widely installed at the entrances of supermarkets, theaters,
meeting rooms, hotels, offices, storages etc. They can reduce penetration
of insects, outside dust, unconditioned air into a conditioned space by forcing
an air stream over the entire entrance. In winter they prevent uncontrolled heat
loss and in summer they prevent heat from the room (see figures). However,
air curtains should not be used in corrosive environments for aluminum, copper
and steel as well as in highly dusty environments (above 0,3 g/m ).The devices
should also not be installed in rooms where they would be exposed
to high humidity or direct contact with water.
For air-conditioned rooms, the steering wheel must be set at an angle of 0-15
degrees towards the air-conditioned room (see figure).
ENG
T ECHNICAL DATA
MODEL
REVENTON GROUP
AERIS 90EN-3P
REVENTON GROUP
AERIS 120EN-3P
REVENTON GROUP
AERIS 150EN-3P
A B C D E F
900
1200
1500
132
90 19.0
22.5
GN.W (KG)
15.5
440
--- ---
--- ---
--- ---
247
218
H
INSIDE OUTSIDE
A CLIMATED ROOM
HEATED ROOM
INSIDE OUTSIDE
SECURITY AGAINST INSECTS
AND ODORS
INSIDE OUTSIDE
3

2.2.TECHNICAL DATA
TECHNICAL DATA AERIS 90EN-3P
AC90EN3P
Product code
AERIS 120EN-3P
AC120EN3P
AERIS 150EN-3P
AC150EN3P
Heater power [kW] 8 10 12
Rated heater current [A] 11,5 14,5 17,3
III STAGE
II STAGE
I STAGE
Maximum
airflow [m3/h]
III STAGE
II STAGE
I STAGE
Maximum air speed
[m/s]
Power supply [V] / Frequency [Hz]
III STAGE
II STAGE
I STAGE
III STAGE
II STAGE
I STAGE
Motor power
[W]
Rated
motor current
[A]
Class of isolation /Protection degree IP [-]
Net weight [kg]
III STAGE
II STAGE
I STAGE
Noise
[dB]
1600 2400 3150
1450 2150 2850
1300 1950 2550
11 11 11
10 10 10
9 9 9
400/50 400/50 400/50
260 380 490
230 355 445
200 330 400
1,13 1,65 2,13
1,00 1,54 1,93
0,87 1,43 1,74
15,5 19,0 22,5
61 62 63
60 61 62
59 60 61
E/IP20 E/IP20 E/IP20
3. INSTALLATION
3.1. GENERAL PRINCIPLES
The following figures show the recommended distances between the air curtain
and the building partition:
The width of the curtain should be greater or equal to the width of the door
frame. When the entrance is wider than the unit, it is recommended to install two
or more units in parallel. In this case, provide 10-40 mm gaps between the units.
3.2. ASSEBLY “STEP BY STEP”
The curtain can be assembled on wall or ceiling. If any components
are not included in the kit, you should buy them yourself and make sure
they are suitable for this type of installation.
a) wall mounting
- unscrew the fixing screws to remove the mounting plate from the back
of the main body
- install mounting plate on the wall
-install the main body. Set the main body onto the upper end of the mounting
plate and clamp it as shown
WIRE SIZE FOR WIRING
WARNING: Forbid to overload operation for a long time!
Power supply
Power of heater [kW]
Minimum wire size of 2
Minimum wire size of
3-PHASE (400 V~,MAIN WIRE CONDUCTOR L1, L2, L3, N)
3 4 5 6 8 10 12 14
1,5
1,5
2,0 4,0
2,5
6,0
4,0
1,0
main wire conductor [mm ]
ground wire conductor [m ]
2

4. INSTALLATION INSTRUCTIONS
4.1. CONNECTION OF THE DEIVCE TO THE ELECTRICAL SYSTEM
- all works concerning electrical installation should be made by the qualified
personnel (who possess required authorizations to install electrical equipment),
based on wiring schematic diagrams (see 7)
- the electrical installation of the building shall have a residual current device
- check the electrical installation and automation before the first start
5. PRECAUTIONS AND WARNINGS
During operation of the device, the following must be respected:
- all works concerning electrical installation (disassembly, repair etc.) should
be made by the qualified personnel, who possess the qualifications
due to the domestic and local norms, regarding electrical installations
- do not limit or cover the inlet and outlet of the device
- do not install, service the device with wet hands or barefoot
- the device should be kept out of reach of children and animals
- when no need heating, turn off the heat source to use it as an unheated
air curtain
- after the turn off, the elements of device may be warm
- after operating time of the device, please utilize it concerning the local norms
and regulations
- don’t allow water or any liquid to enter the motor
- maintenance and repair work must be carried out by a qualified personnel
familiar with local regulations and standards
- always unplug or disconnect the appliance from the power supply before
installation, servicing or cleaning the unit
- never use petrol, benzene, thinners or any other chemicals for cleaning the unit
- periodic maintenance work should be carried out at least once a year by:
ź cleaning the heater and other elements from dust
ź cleaning of plastic parts with water with the addition of soap
ź cleaning the casing with a soft cloth
- failure to comply with cleaning obligations may have a negative effect
on technical parameters of the device
- if the device is not used for a longer time disconnect the voltage supply
- if any abnormality happens, turn off the product immediately and check
the problem
6. CONTROLS
Usage of automatic control dedicated to the electric air heaters of Reventon
Group gives great possibilities of adjusting the efficiency of the curtain
in different, depending on needs, degree of automation of its operation. We also
offer additional controls:
Regulator is used to regulate devices equipped with 3-stage fans. It has a 3-stage
speed control and built-in thermostat switches the device of automatically when
the preset temperature is reached.
Voltage/ Frequency: 230 V AC / 50 – 60 Hz
Maximum current output: 3 A
Temperature range: 10°C - 30°C
Operating mode: continious or thermostatic
Control accuracy: <1°C
Dimensions: 130 x 85 x 40 mm
Weight: 210 g
Degree of casing's protection: IP 30
3-stage speed regulator with thermostat HC-3S

7. CONNECTION SCHEMES
LEGEND:
1. Power
2. Main switch, overcurrent circuit breaker *
3. Water heated air curtain AERIS
4. 3-stage speed controllers with thermostat HC3S
A-work in continuous mode
B-operation in thermostatic mode
5. Door switch
* main switch and overcurrent circuit breaker are not included in the unit

8. TERMS OF WARRANTY
I. Reventon Group Sp. z o.o. [Ltd.] 3B Montazowa Street , 43-300
Bielsko-Biała,Poland, is the producer of the Reventon Group brand.
The warranty concerns the following devices and it is valid for 2 (two) years:
- electric heated air curtain AERIS 90EN-3P
- electric heated air curtain AERIS 120 P
- electric heated air curtain AERIS 150
II. Warranty is valid in the European Union.
III.The terms of warranty are valid from purchasing the device (the date issuing
a document confirming the purchase of the device) but not further
than 30 months from leaving the producer’s warehouse.
IV. Reventon receives the inoperative device or its components, and then sends
back the repaired or replaced product (component) free of charge within
14 working days.
V. In the exceptional cases, the manufacturer reserves the right to extend
the time limit for examination of warranty, especially if the defect
is not permanent and its determination requires a longer period of time.
Any such extension must be notified by the manufacturer before
the end of the 14th day (working).
VI. Warranty does not cover the parts of the device subject to normal
maintenance and the cases as below:
a) mechanical damage of the product;
b) defects and damages through:
- improper storage or transportation;
- improper use or maintenance not in accordance with the instructions;
- using the device in the improper conditions (too high humidity, too high
or too low temperature, impact of the surrounding, sun etc.);
- unauthorized (by the user or other unauthorized persons) repair, modification
or construction changes;
- connecting additional equipment, which is not recommended by the producer
or inconsistent with the technical documentation;
- improper power supply.
EN-3
EN-3P
c) elements which wear and tear such as discolor or using
If there is any of the above, you will be charged for transport and / or repairs.
VII. Any changes in the Warranty Terms, improper use of the product (careless
handling, exposure to liquids, moisture, corrosion), as well as traces of self-
repairing (except for the Reventon Group manufacturer's service), alterations
or attempts to make structural changes to the product, (revealed during
the performance of warranty service), makes warranty not valid.
VIII. To obtain the service it is needed to send to the producer warranty card
with the signature, document confirming the purchase, (copy of the invoice)
and correctly filled the warranty form.
IX. Not following to any of warranty regulations makes the warranty not valid.
X. All correspondence, returns, complains should be send to the following
address: Reventon Group Sp. z o.o. 3B Montazowa Street, 43-300 Bielsko-Biała,
Poland or e-mail:
The producer reserves the rights to make changes to the technical
documentation without previous notice.

Warranty card
Reventon Group [Ltd.] 3B Montazowa Street, 43-300 Bielsko-Biała, Poland
:
:
::
:

Reventon Group [Ltd.] 3B Montazowa Street, 43-300 Bielsko-Biała, Poland, www.reventongroup.eu
This manual suits for next models
2
Table of contents
Other REVENTON Heater manuals

REVENTON
REVENTON AERIS 90EN-3P Guide

REVENTON
REVENTON WALLER 64 Instruction Manual

REVENTON
REVENTON AERIS 100E-1P Guide

REVENTON
REVENTON Farmer Series User manual

REVENTON
REVENTON AERIS 100WN-1P Guide

REVENTON
REVENTON AERIS 100EN-1P Guide

REVENTON
REVENTON Aeris Series Guide

REVENTON
REVENTON AERIS 100E-1P Guide

REVENTON
REVENTON AERIS 100E-1P Guide

REVENTON
REVENTON AERIS Series Guide