Rhymebus RM6F5 series User manual

1
2022.08.15 Edition XB200235
Thank you for using RHYMEBUS RM6F5 series drive.
For proper operations and safety purposes, please read manual carefully.
Only the qualified personnel may proceed with the installation.
Scan the QR code on the right side for the complete operation manual.
Please pay attention to the safety precautions marked with “DANGER” or
“CAUTION” in complete manual before installation.
DANGER
User may cause the casualty or serious damages if user does not abide
by the instructions of the manual to execute the tasks.
CAUTION
User may cause injuries to the people or damage the equipment if user
does not abide by the instructions of the manual to execute the tasks.
Power Source
R,S,T
(L1,L2,L3)
AC power source
input terminals
Three-phase; sinusoidal power source input terminals.
○
+, N○
-
DC power source
input terminals
External DC power source terminal.
※Only 2007 ~ 2015, 4007 ~ 4020 models have the terminal.
Motor
U,V,W
(T1,T2,T3)
Drive outputs to
motor terminals
Output three-phase variable frequency and voltage to
motor.
Power
and Braking
P(+), N○
-
Dynamic brake unit
terminal
Connect to dynamic braking unit(option).
P, N
P, PR
External
brakingresistor
terminal
Connect to external brake resistor (option).
P(+), PR
P(+), P1
External reactor
terminal
Connect to DC reactor (DCL) for improving power
factor. The default setting is connected by a jumper.
Grounding
PE(or G)
Grounding terminal
Ground the drive in compliance with the NEC standard
or local electrical code.
RM6F5 Series
Simple Version
Operation Manual
Terminals of Main Circuit

2
RM6F5 IM
R/L1
S/L2
W/T3
V/T2
G
U/T1
PRP N Induction Motor
T/L3
Braking Resistor(option)
R/L1
S/L2
G
T/L3
Model:RM6F5-2001B3~RM6F5-2005B3 ;
Model:RM6F5-4001B3~RM6F5-4007B3
Three-Phase,
50/60Hz AC Power Input
RM6F5 IM
R/L1
S/L2
W/T3
V/T2
U/T1 Induction Motor
T/L3
R/L1
S/L2
T/L3
N
Braking Resistor(option)
Jumper
P(+)PR P1
※1:DC Reactor(DCL; option)
RM6F5 IM
R/L1
S/L2
W/T3
V/T2
U/T1 Induction Motor
T/L3
N
Jumper
P(+) P1
※1:DC Reactor(DCL; option)
Model:RM6F5-2007B3 ~ RM6F5-2020B3;
Model:RM6F5-4010B3 ~ RM6F5-4030B3
Model:RM6F5-2025E3 ~ RM6F5-2100E3;
Model:RM6F5-4040E3 ~ RM6F5-4150E3
Three-Phase,
50/60Hz AC Power Input
Three-Phase,
50/60Hz AC Power Input
RM6F5 IM
R/L1
S/L2
W/T3
V/T2
PE
U/T1
PP1 NӨ
Three-Phase,
50/60Hz AC Power Input
Induction Motor
T/L3
PE
R/L1
S/L2
T/L3
DCL
※1
ACL
Jumper
+
Model: RM6F5-2125E3~RM6F5-2250E3;
Model: RM6F5-4175E3~RM6F5-4700E3
※1
R/L1
S/L2
T/L3
ACL※1
Decription of terminal and wiring diagram
※1.125HP above drives: AC reactor (ACL) is the standard accessory;
200HP above drives: DC reactor (DCL) is the standard accessory.
Please remove the jumper between P1 and P terminal, when connecting the external DC
reactor (DCL). Do Not remove the jumper, when DC reactor (DCL) does not be connected.

3
Control Termianl
Type
Symbol
Function
Description
Control circuit terminal
Control
power
P24
Power terminal;
Control device usage
Output DC+24V; Maximum supplied current is 50mA.
P12/12V
Output DC+12V; Maximum supplied current is 20mA.
GND
(COM)
Common of analog input
control terminals
Common terminal for control power (P12/12V,P24) and
analog input terminal (Vin, Iin).
Input terminals
FWD
Forward command
terminal
Connect the FWD and COM terminals for forward
operation. (F_001=0)
REV
Reverse command
terminal
Connect the REV and COM terminals for reverse operation.
(F_001=0)
X1
Multi-function input
terminal 1
․The function is set by F_052.
․Default setting: Coast to stop command
X2
Multi-function input
terminal 2
․The function is set by F_053.
․Default setting: Open loop selection
X3
Multi-function input
terminal 3
․The function is set by F_054.
․Default setting: Jog command
X4
Multi-function input
terminal 4
․The function is set by F_055.
․Default setting: Secondary accel/decel time command
X5
Multi-function input
terminal 5
Reserve
X6
Multi-function input
terminal 6
Reserve
COM
(GND)
Common of digital input
control terminals
Common of digital input control signal terminals. (FWD,
REV and X1 ~ X4)
Vin
Analog input terminal
Input range: DC 0~10V。
Iin
Analog input terminal
․Input signal selection
JP4: I position (current signal)
JP4: V position (voltage signal)
․Input range: DC 4~20mA (2~10V) or
DC 0~20mA (0~10V)
․The function is set by F_126.
Output terminals
FM+
AM+
Analog output terminals
․Voltage meter with 10V full scale spec.
(meter impedance: 10kΩ above)
․Maximum output current: 1mA
M-
(GND)
Common of
analog output terminals
Common of analog output terminals.
Ta1
Multi-function
output terminals
(relay type)
․N.O (contact a); The function is set by F_060 .
․Default setting: Error detection
․Capacity: AC250V, 0.5A Max, cosθ=0.3
Tb1
․N.C (contact b); The function is set by F_060
․Capacity: AC250V, 0.5A Max, cosθ=0.3
Tc1
Common terminal for Ta1, Tb1.
Ta2
․N.O (contact a); The function is set by F_061
․Default setting: Operation detection
․Capacity: AC250V, 0.5A Max, cosθ=0.3
Tb2
․N.C (contact b); The function is set by F_061
․Capacity: AC250V, 0.5A Max, cosθ=0.3
Tc2
Common terminal for Ta2.
Y1
Multi-function output
terminals
(open collector type)
․The function is set by F_058, F_059.
․Capacity: DC48V, 50mA Max
Y2
CME
Common terminal of Y1, Y2.
External
Communication
Terminal
DX+
Signal transmission
terminal(+)
․Connect the drive by transmission cable, when the drive
controls multiple pumps or RS-485 communication
interface.
․Communication protocol: Modbus
DX-
Signal transmission
terminal(-)
GND
Grounding terminal of
signal transmission
Grounding terminal of shielding wire.

4
※1.JP5: SINK / SOURCE selection;
The signal input selection of multi-function input terminal(X1~X4), FWD/REV
terminals.
※2.JP4: I / V selection;
I position: Iin-GND terminal is inputted with the current signal.(default)
V position: Iin-GND terminal is inputted with the voltage signal.
※
3.DSW3: The terminal resistor selection for communication; The internal resistance is 100Ω.
When external device control multiple drives, switch the DSW3 to “ON”position at
the first and last drive.
※4.The analog input selection is set by F_126 (default: DC 2~10V(4~20mA))
Voltage Selection Board of Cooling Fan
Description of Terminal and Wiring Diagram
SINK
SOURCE
I
V
FWD
REV
X1
X4
X5
X6
P12
Vin
Iin
GND
(COM)
CME
Y2
Y1
Tc1
Tb1
Ta1
Tc2
Ta2
FM+
AM+
Shielded
Wire Twisted-Pair
Shielded Wire
P
P P P
VR 1KΩ,1/4W
Forward
Reverse
Multi-function Input Terminal 1 (-)
(+)
(+)
Multi-function Output Terminal
(Relay Type)
(AC 250V/0.5A COSθ=0.3)
Multi-function Output Terminal
(Open collector)
(DC 48V/50mA)
※2
M-
(GND)
Analog Output Terminal
(DC 0~10V)
※1
COM
(GND)
Analog input signal
(default: DC 4~20mA)
Analog input control
(default: DC 0~10V)
JP4
Multiple Pump/
Communication Control
Terminal
P
DX+
DX-
GND
P24
JP5
ON
1
DSW3
Multi-function Input Terminal 2
Multi-function Input Terminal 3
Multi-function Input Terminal 4
※3
RM6F5
X2
X3 Tb2
Multi-function Input Terminal 5
Multi-function Input Terminal 6
※Above models RM6F5-4100 have the voltage selection board shown in above figure
when removing the main circuit terminal cover of the drive. Please carefully select the
jumper position according to the power source(actual power voltage level) to avoid the
burnout of the fan or the overheating of the drive.(EX: When the power source is 460V,
selecting the position from 380V to 460V)

5
Wiring Diagram and Setting for Single-pump and Multi-pump Applications
Drive #0
I
V
Pressure
transmitter
Drive #0 Drive #1 Drive #2
I
V
I
V
I
V
Pressure
transmitter
1. JP4: Drive #0 àI position; Drive #1 ~ #3 àV position
2. JP1: Drive #0 àopen; Drive #1 ~ #3 àclose
3. DSW3: Drive #0 and Drive #3 àON position; Drive #1 and #2 à1 position
4. Set the number for every drive by F_016
Single Pump Control(F_015=1)
2. Parallel control for four pumps with one pressure transmitter (special wiring)
1. Parallel control for four pumps with four pressure transmitters (standard wiring)
Drive #0 Drive #1 Drive #2
ON
I
V
I
V
I
V
Pressure
transmitter Pressure
transmitter Pressure
transmitter
1. JP4: Drive #0 àI position; Drive #1 ~ #3 àV position
2. JP1: Drive #0 àopen; Drive #1 ~ #3 àclose
3. DSW3: Drive #0 and Drive #3 àON position; Drive #1 and #2 à1 position
4. Set the number for every drive by F_016
3. Parallel control for four pumps with one pressure transmitter (special wiring)
1. JP4: Drive #0 ~ #3 àI position
2. JP1: Drive #0 ~ #3 àopen
3. DSW3: Drive #0 and Drive #3 àON position; Drive #1 and #2 à1 position
4. Set the number for every drive by F_016
Multi-Pump Control(F_015=2,3,4)
Drive #3
I
V
Pressure
transmitter
Drive #3
I
V
DSW3
JP4 JP4 JP4 JP4
JP4 JP4 JP4 JP4
JP4
ON
DSW3
1
1. JP4: I position
2. JP1: Open
3. DSW3: ON position
4.F_015=1
JP4: Input signal type selection of Iin
JP1: Input impedance selection of Iin
DSW3: Terminal resistor switch
F_015: Selection of Pump Control Mode
F_016: Set Drive’s No for Parallel Control
1
ON
DSW3
1
ON
DSW3
1
ON
DSW3
1
ON
DSW3
1
ON
DSW3
1
ON
DSW3
1
P24 Iin DX+DX- FG
P24 Iin DX+ DX- FG
P24 Iin DX+ DX- FG P24 Iin DX+ DX- FG P24 Iin DX+ DX- FG
P24 Iin DX+DX- FG P24 Iin DX+DX- FG
ON
DSW3
1
P24 Iin DX+ DX- FG
P24 Iin DX+ DX- FG
JP1
JP1 JP1 JP1 JP1
JP1 JP1 JP1 JP1
–+
–+–+–+–+
–+
Drive #0
- +
Drive #1 Drive #2
ON
I
V
I
V
I
V
Pressure
transmitter
Drive #3
I
V
DSW3
JP4 JP4 JP4 JP4
1ON
DSW3
1ON
DSW3
1ON
DSW3
1
P24 Iin DX+DX- FG P24 Iin DX+ DX- FG P24 Iin DX+ DX- FG
P24 Iin DX+DX- FG
JP1 JP1 JP1 JP1
GND GND GND GND

6
Digital Type Keypad (KP-605)
Operation of Keypad
Display the actual pressure
ON: Auto constant pressure
mode / stand by
OFF: Manual mode / stop
Start auto constant
pressure mode
Change functions and
parameters
1. Drive stops
2. Error reset
1. Enter the parameter setting mode
2. Back to the function setting mode
3. Switch the monitor mode
1. Enter the function setting mode
2. Back to the monitor mode
1. Indicate the lead drive
2. In multi-pump control modes, the
indicator will be off after pressing
OFF key.
3.Blinking:Parallel connection error
Blink: Under acceleration or
deceleration
ON: Constant speed
OFF: Stop
POT Knob
Running
Display the setting pressure
ON: Maual mode/ Stand by
OFF: Auto mode/Stop
Enter manual mode
The operation of the digital keypad includes fault messages and three modes. The switching
methods are shown as below figure:
Monitor mode Function setting mode Parameter setting mode
Fault message
FUN
DATA
PROG FUN
DATA
OFF
RESET
PROG
PROG
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
The operation steps are shown as below table (by default setting)
Operation Steps
Display
1.Start the drive and enter the monitor mode.
SV
KEYPAD
PV
Running
2.Press
PROG
key and enter the function setting mode.
SV
KEYPAD
PV
Running
3.Press
FUN
DATA
key and enter the parameter setting mode.
SV
KEYPAD
PV
Running
4.Press
FUN
DATA
key and return to the function setting mode.
SV
KEYPAD
PV
Running
5.Press
PROG
key and return to the monitor mode.
SV
KEYPAD
PV
Running

7
Parameter List
Description of Monitor Mode
There are eight displays can be selected in the monitor mode. Press
FUN
DATA
to switch the
display in accordance with below sequence under monitor mode. User can determine one of
eight displays as the main display from function F_006 (Selection of Main Display). Please
refer to the following illustrations:
Display 1
(Output Frequency) Display 2
(Frequency Command) Display 3
(Output Voltage)
Display 5
(Output Current)
Display 6
(Terminal Status and
Heat Sink Temperature)
Monitor
Mode
FUN
DATA
FUN
DATA
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
FUN
DATA
FUN
DATA
Display 4
(DC Bus
Voltage)
PV
Running
SV
KEYPAD
PV
Running
SV
KEYPAD
FUN
DATA
FUN
DATA
FUN
DATA
Display 7
( SV & PV)
Display 8
(Actual flow)
FUN
DATA
Func.
Name
Description
Range of
Setting
Unit
Default
F_000
Drive Information
0: Software version
1: Drive model number
2: Drive running hours
3: Drive supply power time
4: Software checksum code
5: Reserved
─
─
─
F_001
Start Command
Selection
Start command
Rotation direction
command
0~11
─
3
0:
FWD or REV terminal
FWD or REV terminal
1:
FWD terminal
REV terminal
2:
Keypad “AUTO RUN”
key
FWD, REV terminal
3:
Forward direction
4:
Reverse direction
5~7:
Reserved
Reserved
8:
Communication
interface
Communication
interface
9:
Communication
interface
REV terminal
10:
FWD terminal
Communication
interface
11:
Keypad “AUTO RUN”
key
Communication
interface
a. Select one of eight displays as the main display from function F_006 (Selection of Main
Display).
b. Determine one of eight displays as the main display according to the application. When
the parameter of function is completed without pressing key, the drive will automatically
switch back to the main display after 3 minute.

8
Func.
Name
Description
Range of
Setting
Unit
Default
F_002
Frequency
Command
Selection
0: Frequency command by analog signal
1: Frequency command by keypad.
2: Pressure command by keypad.
3: Frequency command by communication.
4: Pressure command by communication.
5: Pressure command by analog signal
6: Frequency command by Pot on the keypad
7: Pressure command by Pot on the keypad
0~7
─
2
F_003
Selection of “STOP”
Key Validity
0: Start command by terminal, “STOP” key disabled.
1: Start command by terminal, “STOP” key enabled.
0,1
─
1
F_004
SettingValue(SV)
Selection
0: In the monitor mode, setting value cannot be
changed.
1: In the monitor mode, setting value can be changed.
0,1
─
1
F_005
Auto-Storing of
Setting Value
Selection
0: In the monitor mode, setting value auto-storing
disable.
1: In the monitor mode, setting value auto-storing after
3 minutes.
0,1
─
1
F_006
Selection of
Main Display
Select 1 of 8 “monitor modes” as the main display.
1~8
─
7
F_007
Pressure
Transducer Setting
Set upper limit value of pressure in accordance with
pressure transducer specification.(pressure setting
value is corresponding to maximum voltage or current.
0.0~160.0
bar
10.0
F_008
Maximum Allowabel
Operating Pressure
Set the maximum operating pressure value
(F_007*F_008) in accordance with the specification of
pump.
0~100
%
100
F_009
Starting Frequency
The starting frequency of drive.
0.1~10.0
Hz
0.5
F_010
Starting Voltage
The voltage corresponds to the starting frequency.
0.1~50.0
V
8.0
(Note1)
0.1~100.0
12.0
(Note2)
F_011
Base Frequency
The frequency corresponds to the base voltage in V/F
pattern.
0.1~400.0
Hz
60.0
F_012
Base Voltage
The voltage corresponds to the base frequency in V/F
pattern.
0.1~255.0
V
220.0
(Note1)
0.1~510.0
380.0
(Note2)
F_013
Selection of Pump
Shift Operation
(Parallel control)
0: Disable.
1: Shift the pump operation arriving the operating time
(F_024).
2: Shift the pump operation after a drive stops.
3: Both 1 and 2 enabled.
0~3
─
3
F_015
Control Mode
Selection
(Parallel control)
0: Disable the functions related to pump.
1: Single pump application.
2: Multi-pump applications; (E-mode)
3: Multi-pump applications; (F-mode)
4: Multi-pump applications; (M-mode)
5: Multi-pump applications; (S-mode)
6: Air conditioning multiple control.
7: Proportional feedback control.
0~7
─
1
F_016
Set Drive’s No. for
Parallel Control
Set the individual number for every drive.
#0 as the lead drive to command others.
0~7
─
0
F_017
Maximum Output
Frequency
The maximum output frequency of drive.
0.1~120.0
Hz
60.0
F_018
Reference
Frequency of
Accel/Decel Time
The frequency corresponding to accel/decel time.
0.01~
120.00
Hz
60.00
F_019
Primary
Acceleration Time
The acceleration time from stop to reference
frequency.
0.0~
3200.0
sec
1.0
F_020
Primary
Deceleration Time
The deceleration time from reference frequency to
stop.
0.0~
3200.0
sec
1.0

9
Func.
Name
Description
Range of
Setting
Unit
Default
F_021
Launch Detection
Time
(Parallel Control)
In multi-pump control systems, If the pressure
decreasing gradually, set the detection time to launch
auxiliary drive.
0.0~25.0
sec
6.0
F_022
Launch
Detection Level
(Parallel Control)
In multi-pump control systems, set the detection level
when the pressure decreasing gradually.
0.0~25.0
bar
0.4
F_023
Cut-off Frequency
(Parallel Control)
In multi-pump control systems,set the cut-off
frequency and start frequency for lead/auxiliary drive
stopping.
0.0~60.0
Hz
50.0
F_024
Pump
Auto Shift Time
(Parallel Control)
The time of pump shift operation in multi-pumps
control system.
0~240
hr
24
F_025
Cut-off Time
(Parallel Control)
In multi-pump control systems, the detection time of
pump departs from operation.
0.0~25.0
sec
10.0
F_026
Communication
Baud Rate
(Parallel Control)
The communication baud rate setting for multi-pump
control systems.
0~3
─
1
F_027
Secondary
Acceleration Time
Switch to secondary acceleration time by
multi-function input terminal.
0.0~
3200.0
sec
0.5
F_028
Secondary
Deceleration Time
Switch to secondary deceleration time by
multi-function input terminal.
0.0~
3200.0
sec
0.5
F_029
Set S-curve for
Accel/Decel Time
Set S-curve to slow the acceleration and deceleration
time at start and stop.
0.0~5.0
sec
0.0
F_030
V/F Pattern
Selection
0: Linear
1: Square curve.
2: 1.7th power curve.
3: 1.5th power curve.
0~3
─
1
F_031
Primary
Speed
Jog
command
Multi-speed
level 3
command
Multi-speed
level 2
command
Multi-speed
level 1
command
0.00~
120.00
Hz
0.00
OFF
OFF
OFF
OFF
F_032
Preset Speed 1
OFF
OFF
OFF
ON
20.00
F_033
Preset Speed 2
OFF
OFF
ON
OFF
25.00
F_034
Preset Speed 3
OFF
OFF
ON
ON
30.00
F_035
Preset Speed 4
OFF
ON
OFF
OFF
45.00
F_036
Preset Speed 5
OFF
ON
OFF
ON
50.00
F_037
Preset Speed 6
OFF
ON
ON
OFF
55.00
F_038
Preset Speed 7
OFF
ON
ON
ON
60.00
F_039
Jog Speed
ON
X
X
X
7.00
F_040
Vin Gain
Analog input “Vin” gain ratio adjustment.
0.00~2.00
─
1.00
F_041
Vin Bias
Analog input “Vin” bias ratio adjustment.
-1.00~1.00
─
0.00
F_042
Frequency Upper
Limit
The upper limit of output frequency= F_017(Maximum
Output Frequency )*F_042
0.00~1.00
─
1.00
F_043
Frequency Lower
Limit
The lower limit of output frequency=F_017(Maximum
Output Frequency )*F_043
0.00~1.00
─
0.00
F_044
Analog Output
Signal Selection
(FM+)
0:Output frequency
1:Frequency command
2:Output current
3:“Vin” analog input signal
4:“Iin” analog input signal
0~4
─
0
F_045
Gain(FM+)
Analog output gain ratioadjustment.
0.00~2.00
─
1.00
F_046
Motor Overload
Protection (OL)
0: Disable
1: Overload protection for dependent cooling fan type
motor:Enabled(OL)
2: Overload protection for independent cooling fan
type motor: Enabled(OL)
0~2
─
1
F_047
Filter Setting of
Analog Input Signal
Filter the analog input signal when the frequency
command is controlled by analog input. (F_002=0).
0~255
─
20
F_048
Motor Rated Current
Set the value according to the motor rated current.
10%~150%
of drive
rated current
A
According
to the
rated
current of
motor

10
Func.
Name
Description
Range of
Setting
Unit
Default
F_049
Motor No-Load
Current
Set the value according to the motor’s no-load
condition.
0~motor
rated current
A
1/3 motor
rated
current
F_050
Motor Slip
Compensation
According to the load condition, set the compensation
for motor running at constant speed. (0.0: off)
-9.9~10.0
Hz
0.0
F_051
Operation Condition
Memory
Record the last status of drive before power off.
0: Enable (F_001=2,3,4)
1: Disable
0,1
─
0
F_052
Multi-function
Input Terminal
(X1)
=0:
Manual control
command 1 of
M-mode
(F_015=4)
±1: Jog command
±2: Secondary accel/decel time
command
±3: Multi-speed level 1 command
±4: Multi-speed level 2 command
±5: Multi-speed level 3 command
±6: Reset command
±7: External fault command(thr)
±8: Interruption of output
command(bb)
±9: Coast to stop command(Fr)
±10: Speed tracing from the
maximum frequency
±11: Speed tracing from the setting
frequency
±12: Holding command
±13: UP command
±14: DOWN command
±15: Clear UP/DOWN frequency
command
±16: Analog input source selection
±17: Stop command with 3-wire
start/stop circuit
±18: Under close-loop control
condition (F_153≠0),
open-loop selection.
±19: Reset the integrator at
close-loop control condition
(F_153≠0)
±20: Stop command
±21:
Multi-speed level 4 command
±22: Sequential operation control.
±23: Flow switch input
-23~ +23
(Note 3)
─
9
F_053
Multi-function
Input Terminal
(X2)
=0:
Manual control
command 2 of
M-mode
(F_015=4)
13
F_054
Multi-function
Input Terminal
(X3)
=0:
Manual control
command 3 of
M-mode
(F_015=4)
1
F_055
Multi-function
Input Terminal
(X4)
=0:
Reserve
2
F_058
Multi-function
Output Terminal
(Y1)
0: Disable
±1: Standby detection
±2: Constant speed detection.
±3: Zero speed detection.
±4: Frequency detection.
±5: System overload detection. (OLO)
±6: Stall prevention detection.
±7: Low voltage detection. (LE)
±8: Braking detection.
±9: Restart after instantaneous power failure
detection.
±10: Restart after error condition detection
±11: Error detection.
±12: Overheating warning detection. (Ht)
±13: Over pressure detection. (OP)
±15: Auxiliary pump 1 detection.
±16: Auxiliary pump 2 detection.
±17: Fan detection during operation.
±18: PTC overheating warning dection
-18 ~+18
(Note 7)
─
1
F_059
Multi-function
Output Terminal
(Y2)
2
F_060
Multi-function
Output Terminal
(Ta1,Tb1)
-11
F_061
Multi-function
Output Terminal
(Ta2/Tc2)
-3
F_062
Frequency
Detection Range
Set the bandwidth of frequency detection range.
0.0~10.0
Hz
2.0
F_063
Frequency
Detection Level
Set the frequency detection level of multi-function
output terminal.
0.0~120.0
Hz
0.0
F_064
Automatic Torque
Compensation
Range
According to the load condition, adjust the output
voltage of the V/F pattern. (0.0: off)
0.0~25.5
─
1.0

11
Func.
Name
Description
Range of
Setting
Unit
Default
F_065
System Overload
Detection (OLO)
0: Disable
1: Enable
0,1
─
0
F_066
System Overload
Detecting Selection
0: Detection during constant speedonly
1: Detection during operation only
0,1
─
0
F_067
Output Setting after
System Overload
0: Drive keeps operation when “OLO” is detected
1: Drive trips to protection when “OLO” is detected
0,1
─
0
F_068
System Overload
Detection Level
When the output current of drive is higher than the
level (F_068 * drive’s rated current) with the duration
of F_069, the drive will trip to protection.
30%~160%
of drive
rated current
%
160
F_069
System Overload
Detection Time
0.1~25.0
sec
2.0
F_070
Stall Prevention
Level at
Acceleration
If stall is occurred during acceleration, the motor keeps
running at constant speed. (200%: off)
30%~160%
of drive
rated current
%
140
F_071
Stall Prevention
Level at Constant
Speed
If the stall is occurred during constant speed, the
motor decreases the speed.(200%: off)
30%~160%
of drive
rated current
%
130
F_072
Acceleration Time
Setting after Stall
Prevention under
Constant Speed
Set the acceleration time after stall prevention under
the constant speed.
0.1~
3200.0
sec
15.0
F_073
Deceleration Time
Setting for Stall
Prevention under
Constant Speed
Set the deceleration time at the stallprevention under
the constant speed.
0.1~
3200.0
sec
15.0
F_074
Stall Prevention
Setting at
Deceleration
0: Disable
1: Enable
0,1
─
1
F_075
DC Braking Level
Set the current level of DC braking.
0~120%
of drive
rated current
%
50
F_076
Time of DC Braking
after Stop
Set the time for DC braking after drive stopped.
0.0~20.0
sec
0.5
F_077
Time of DC Braking
before Start
Set the time for DC braking before drive started.
0.0~20.0
sec
0.0
F_078
Operation Selection
at Instantaneous
Power Failure
0: Drive cannot be restarted
1: Drive can be restarted
0,1
─
0
F_079
Auto-Restarting
Selection for Error
Trip Condition
0: Short time interval to auto-restart according to the
setting of F_080 (OC,OE,GF only).
1: Long time interval to auto-restart according to the
setting of F_080 and F_083(all errors except Fb Lo).
0,1
─
1
F_080
Maximum Reset
Time of Auto-Restart
at Drive’s Error Trip
Set the counting number for drive auto-restart when
errors occur.
0~16
─
10
F_081
Switching
Frequency
The setting value is higher and the motor noise is
lower.
0~6
─
1
F_082
Stop Mode
0: Ramp to stop
1: Coast to stop
2: Coast to stop+ DC braking
0~2
─
0
F_083
Time Interval before
Auto-Restart
Set the error tripping time interval before drive auto
restarts for F_079 when the drive trips to stop.
1~200
10sec
6
F_084
Pressure Boost
(Water Usage
Detection)
Boost the pressure up to detect if the water is used.
0.01~1.00
bar
0.15
F_085
Time Interval of
Pressure Boost
(Water Usage
Detection)
Set the time interval for F_084 to detect if the water is
used. (0: off)
0~250
sec
35
F_086
(ON/OFF Mode)
Starting Rate
Setting
In constant pressure control mode and under low flow
condition, setting the starting rate of drive to activate
ON/OFF mode. (0: disable)
0~100
%
0
F_087
(ON/OFF Mode)
Pressure Dead
Band Setting
In ON/OFF mode, drive will auto start/stop the pump in
accordance with the setting value.
*Start level=SV(Setting pressure) - F_087
Stop level=SV(Setting pressure) + F_087
0.1~25.0
bar
0.3

12
Func.
Name
Description
Range of
Setting
Unit
Default
F_088
Speed Tracing
Current Level
When the current is higher than the “speed tracing
current level”, the output frequency will trace
downward.
0~160%
of drive
rated current
%
150
F_089
Delay Time before
Speed Tracing
Set the delay time before the speed tracing and
coast stop+ DC braking.
0.1~5.0
sec
0.5
F_090
The V/F Pattern of
Speed Tracing
Set the percentage of V/F output voltage at the speed
tracing.
0~100%
%
100
F_091
Error Record
Display the latest 5 error records.
─
─
─
F_092
Parameter Setting
Lock
0: Parameters are changeable. Maximum frequency
cannot exceed 120.0Hz.
1: Parameters are locked. Maximum frequency cannot
exceed 120.0Hz.
2: Reserved
3: Reserved
0~3
─
0
F_093
Automatic Voltage
Regulation (AVR)
0: Disable
1: Enable
0,1
─
1
F_094
Drive Overload
(OL1)
0: Disable
1: Thermal protection
2: Current limit overload protection
3: Both 1 and 2 enable
0~3
─
3
F_095
Power Source
Set the value according to the actual power source.
190.0~
240.0
V
220.0
(Note1)
340.0~
480.0
380.0
(Note2)
F_096
Analog Frequency
Dead Band
When the signal noise is large, appropriately increase
the dead band to stabilize the frequency. But this will
reduce the tuning linearity.
0.00~2.55
Hz
0.00
F_097
Digital Input
Response Time
When the digital input signal is under the setting time,
program will not be activated.
1~16
ms
10
F_098
Grounding Fault
Protection (GF)
0: Disable
1: Enable(GF)
0, 1
─
1
F_099
External Indicator 1
Select themonitor mode of external indicator 1
0: Disable
0~10
─
1
F_100
External Indicator 2
Select themonitor mode of external indicator 2
0: Disable
0~10
─
5
F_101
External Indicator 3
Select themonitor mode of external indicator 3
0: Disable
0~10
─
2
F_102
PID Compensation
Gain
Compensate the gain for pressure command control
under constant pressure control.
0.1~8.0
─
1.0
F_103
PID Control Mode
Selection
0: Open-loop operation
1: Forward control; D postposition
2: Forward control; D preposition
3: Reverse control; D postposition
4: Reverse control; D preposition
0~4
─
1
F_104
P Selection
0: P postposition
1: P preposition
0,1
─
1
F_105
Proportional Gain(P)
Set the gain value for deviation adjustment.
(0.0: P control disabled)
0.0~25.0
─
3.0
F_106
Integration Time(I)
Set the integration time for deviation adjustment. (0.0: I
control disabled)
0.0~25.0
sec
1.2
F_107
Derivative Time(D)
Set the derivative time for deviation adjustment. (0.00:
D control disabled)
0.00~2.50
sec
0.00
F_108
Derivative Time of
Feedback
Set the derivative time for feedback signal.
0.00~2.50
sec
0.00
F_109
Integration Upper
Limitation
Set the upper limitation value of integrator.
0~200%
of maximum
frequency
%
100
F_110
Integration Lower
Limitation
Set the lower limitation value of integrator.
-100~100%
of maximum
frequency
%
0
F_111
Offset Adjustment
for Integration Time
Adjust the integration time offset.
-100~100%
of maximum
frequency
%
65

13
Func.
Name
Description
Range of
Setting
Unit
Default
F_112
PID Buffer Space
Set the buffer space of PID output value.
0~255
─
2
F_113
Feedback Signal
Filter
Filter the feedback signal.
0~255
─
10
F_114
Feedback Signal
Trip Detection
0: Disable
1: Enable (at F_126=0)
0,1
─
1
F_115
(Water Usage)
Pressure Boost
Time
Set the time of F_084 (Pressure Boost for Water
Usage Detection) to detect if the water is used.
0.1~25.0
─
0.6
F_116
Parameter Selection
0: F_000 ~ F_134
1: F_000 ~ F_194
0,1
─
0
F_117
PID Start Range
In constant pressure control mode (F_103≠0), drive
will activate PID control when the feedback signal
exceeds the dead band.
0.0~10.0
bar
0.3
F_118
(Water Shortage
Detection)
Auto-restart
Selection
0: Disable
1: Trip (Fb Lo): Press “RESET” key to reset.
2: Trip (Fb Lo): Power ON again to reset.
3: Trip (Fb Lo): Drive will auto-restarts according to the
setting of F_122 (Drive Shutdown Time for Water
Shortage)
0~3
─
1
F_119
(Water Shortage
Detection) Pressure
Level
Set the pressure level to detect if pump
suffers from water shortage conditions.
(0: Disable)
0~100% of
pressure
command
%
40
F_120
(Water Shortage
Detection)
Current Level
Set the current level to detect if pump suffers from
water shortage conditions.
(0: Disable)
0~100% of
motor
rated
current
%
0
F_121
(Water Shortage
Detection)
TimeDetection
Set the detection time for F_119 and F_120 to detect if
a pump suffers from water shortage.
0~250
sec
60
F_122
(Water Shortage)
Drive
Shutdown Time
Drive will auto-restart after the time setting, when a
pump suffers from water shortage. F_118 =3.
(0:off)
0~200
min
5
F_123
Analog Input
Selection
F_103=0
F_103≠0
0~3
─
0
0
Vin+Iin
Vin: Frequency
command
Iin: Feedback signal
1
Vin-Iin
2
Iin-Vin
3
Vin or Iin(switch by
multi-function input
Terminal X1~X4)
F_124
Proportion Type of
Pressure
Transducer
0: Direct proportion signal.
1: Inverse proportion signal.
0,1
─
0
F_125
Speed Command
Source Selection
under Open- Loop
Condition
In the closed-loop control, select the speed command
source when PID is disabled by multi-function input
terminal.[ multi-function input terminal= ±13
(F_103≠0)or press
HAND
ON
]
0: Analog input terminal(Vin).
1: Keypad or key setting
2: Keypad knob
3: RS-485 Communication interface
0~3
─
1
F_126
Iin Range Selection
0: 4~20mA (2~10V)
1: 0~20mA (0~10V)
0,1
─
0
F_127
Iin Gain (Analog
Input)
The gain ratio of analog input terminal Iin.
0.00~2.00
─
1.00
F_128
Iin Bias (Analog
Input)
The bias ratio of analog input terminal Iin.
-1.00~
1.00
─
0.00

14
Func.
Name
Description
Range of
Setting
Unit
Default
F_129
AM+ Analog Output
Signal Selection
0: Output frequency.
1: Frequency command.
2: Output current.
3: Vin frequency command.
4: Iin frequency command.
0~4
─
2
F_130
Gain (AM+)
AM+ analog output adjustment ratio.
0.00~2.00
0.01
1.00
F_131
Constant Speed
Detection Range
Set the bandwidth of constant speed detection range.
0.0~10.0
0.1Hz
2.0
F_132
DC Braking
Frequencyat Stop
Active frequency level of DC braking at stop.
0.1~60.0
0.1Hz
0.5
F_133
(Water Usage
Detection)
Drive Standby level
When the frequency during the operation is lower than
the setting value, drive will decelerate to 0Hz and
entering stand by status.
0~120
Hz
10
F_134
Default
Setting
0: Disable
─
─
0
CLF: Clear fault records
dEF60: Restore the default value of drive for 60Hz.
dEF50: Restore the default value of drive for
constant pressure setting (single pump)
dEF51: Restore the default value of drive for for
constant pressure setting (machine tool)
SAv: Save the setting value.
rES: Restore the setting value.
rd_EE: Read the parameters from drive to digital
keypad
Wr_EE: Write the parameters from digital keypad to
drive
Cpy: In multi-pump control system, copy lead drive’s
parameter.
F_135
Set Standby Drives
In multi-pump control systems, setting the drives
standby numbers.
0~7
─
0
F_136
Noise Prevention
0: Disable. 1: Enable.
0,1
─
0
F_137
Delay Time at Pump
Shift Operation
The delay time setting is to remain the stable pressure
of the system at the interchanging of the pump
operation.
0~250
sec
10
F_138
200% Current Limit
0: Disable. 1: Enable.
0,1
─
0
F_139
Analog input
selection (Vin)
0: Frequency command
1: PTC temperature
0,1
─
1
F_140
NTC Thermistor
0: Disable. 1: Enable.
0,1
─
1
F_141
Drive Overheating
Warning Selection
0: Disable
1: Warning (Ht): Continue operation.
2: Warning (Ht): Drive de-rates the switching
frequency automatically per 5 minutes.
3: Warning (Ht): Stop operation.
0~3
─
0
F_142
Drive Overheating
Warning Level
Set the warning level to prevent drive overheating.
45~85
1℃
70
F_143
Drive Overheating
Dead Band
Set the temperature dead band of F_142 and F_145.
2.0~10.0
0.1℃
3.0
F_144
Fan Control
Selection
0: Forced air: Start the fan at power ON.
1: Operation air: Start the fan at running.
2: Temperature level setting: Start the fan according to
the setting of F_145.
0~2
─
1
F_145
Temperature Level
of Fan Activation
Set the temperature level of fan activation.
25~60
1℃
50
F_146
Minimum Operation
Time of Fan
Set the minimum operation time of fan when the fan
stops.
0.1~25.0
0.1min
0.5
F_147
Over Pressure
Disposal
0: Disable
1: Alarm: Drive keeps operation.
2: Alarm: Drive stops output.
3: Error trip: Drive trips to stop.
0~3
─
0

15
Func.
Name
Description
Range of
Setting
Unit
Default
F_148
Over Pressure Level
According to the setting value of F_007 (Pressure
Transmitter Setting) to set the over pressure level.
0~100
%
100
F_149
Over Pressure of
Detection Time
When the actual pressure exceeds over pressure level
(F_007*F_148) with duration (F_149), the detection is
activation.
0.0~25.5
sec
2.0
F_150
Continuous Water
Supply Control
0:Disable
1:Enable
0,1
─
0
F_151
Set the
Minimum Pumps
during Operation
In parallel control system, set the minimum quantity of
pumps during operation.
1~8
─
1
F_152
PTC Overheat
Alarm Level
Set the alarm level of PTC Overheat.(OH1)
0.0~10.0
V
1.2
F_153
PTC Overheat
Alarm Selection
0: Keep running
1: Stop running
0,1
─
0
F_154
PTC Overheat
Trip Leve
Set the trip level of PTC Overheat.(OH2)
0.0~10.0
V
2.4
F_155
Comm. Address
The host uses the address to send and receive
messages from the drive.(0: Disable)
0~254
─
0
F_156
Baud Rate
0: 4800bps
1: 9600bps
2: 19200bps
3: 38400bps
0~3
─
1
F_157
Comm. Protocol
0: 8,N,2
1: 8,E,1
2: 8,O,1
3: 8,N,1
0~3
─
1
F_158
Comm. Overtime
(Cot)
When the data transmission during communication
transmission is interrupted, has no data transmitting,
or delays, drive displays “Cot” message
(0.0: Communication overtime disable)
0~1000
sec
0.0
F_159
Comm.
Overtime Disposal
0: Warning (Cot): Continue operation.
1: Warning (Cot): Ramp to stop
2: Warning (Cot): Coast to stop
0~2
─
0
F_160
Multi-Function
Input Selection
0: Multi-function inputs from multi-function terminals
1: Multi-function inputs from communication control
0,1
─
0
F_162
Frequency
Upper Limitation by
Manual Mode
Setting manual mode for upper limit of frequency
command
0~100%
maximum
of output
frequency
%
100
F_163
Frequency Lower
Limitation by Manual
Mode
Setting manual mode for lower limit of frequency
command
0~100%
maximum
of output
frequency
%
0
F_165
Pump Delay Start
Time
In the PID control, when the feedback signal exceed
the dead band, pump will start after the setting time.
0~9999
sec
0
F_166
K Value of Flow
Sensor
Setting value accord with specification of flow sensor
0.1~100.0
L/Pulse
10.0
F_167
Rate of Flow Sensor
Setting rate of flow sensor
0.00~2.00
─
1.00
F_168
Unit of Flow Sensor
0: LPS
1: CMH
0,1
─
0
F_170
Flow Switch
Dectect time
When the multiple-input terminal is set to
±23, and the trigger time is longer than the setting
value. The drive will enter to ON/OFF mode
automatically.
0~600
sec
15
F_171
Shutoff Head(H)
Setting shutoff head of pump
0~160
bar
12.0
F_172
Maximum Flow (Q)
Setting maximum flow of pump
0.0~
6000.0
L/min
300.0
F_173
Compensation for
Pipe Friction Loss
0:Disable
1:Enable
0,1
─
0
F_174
The Current in
Maximum Flow
(IQmax)
Setting current in maximum flow(IQmax)
1~200% of
drive rated
current
%
100
F_175
The Current in
Minimum Flow
(IQmin)
Setting current in minimum flow(IQmin)
0~200% of
drive rated
current
%
30
F_176
Pump Flow Rate
Compensation for
Pipe Friction Loss
(HCOMP max)
Setting maximum flow for pipe friction loss
0.1~160
bar
0.0

16
Func.
Name
Description
Range of
Setting
Unit
Default
F_177
Response Time
Compensation of
Pipe Friction Loss
Setting pump for response time compensation of
friction loss
1~255
─
40
F_180
Sequetial
Operation for Start
Control
0: Disable
1: Enable
0~1
─
0
F_181
Date/ Time
Setting
Y: Year
2000~
2099
─
─
M: Month
1~12
d :Day
1~31
W: Week
Sun.7~
SAt.6
H: Hour
0~23
MM: Minute
0~59
F_182
Date/ Time
Display
Y: Year
M: Month
d: Day
W: Week
H: Hour
MM: Minute
-----: Reserved
─
─
─
F_183
Sequential
Operation Mode
0: Every week
1: Every day
0,1
─
0
F_184
Sector 1
Sequential
Operation
S: Level selection
OFF,ON
─
OFF
W: Week
Sun.7: Sunday
Mon.1: Monday
TUE.2:Tuesday
Wed.3:Wednesday
THU.4:Thursday
Fri.5:Friday
SAt.6:Saturday
Sun.7~
SAt.6
─
Sun.7
H: Hour
0~23
hour
0
MM: Minute
0~59
min
0
C: Pressure command
0.1~160.0
bar
0.0
SL: Inclined time
0.1~600.0
sec
0.0
F_185
Sector 2 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_186
Sector 3 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_187
Sector 4 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_188
Sector 5 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_189
Sector 6 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_190
Sector 7 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_191
Sector 8 of
Sequencial
Operation
Refer to F_184 setting descrption
─
─
─
F_192
Unit of pressure
setting
0: bar
1: %
Note: only work in F_084 and F_117
0~1
─
0
F_193
Reduce the
Switching
Frequency during
overloading
0: If the drive is overloaded, the swithing frequency
can not be adjusted with amount of current.
1: If the drive is overloaded, the switching frequency
can be adjusted with amount of current.
0~1
─
1

17
Func.
Name
Description
Range of
Setting
Unit
Default
F_194
Default Setting
0: Disable
─
─
0
CLF: Clear error records
dEF60: Restore the default value of drive for 60Hz.
dEF50: Restore the default value of 60Hz single pump
constant pressure control application
dEF52: Restore the default value of 60Hz multi-pump
constant pressure control application.
dEF53: Restore the default value of 50Hz single pump
constant pressure control application
dEF57: Restore the default value of 60Hz
multi-pump constant pressure control
(S-mode)application
SAv: Save the setting value.
rES: Restore the setting value.
rd_EE: Read the parameters from drive to digital
keypad
Wr_EE: Write the parameters from digital keypad to
drive
CPy: In multi-pump control system, copy lead drive’s
parameter.
The color as means the functions can be set during operation.
Note:
1. Specification of 200V series.
2. Specification of 400V series.
3.+: Represents a contact (N.O) -: Represents b contact (N.C)

18
Error Trip Messages of Drive
Display
Description
Display
Description
(EEr)
SV
KEYPAD
PV
Running
EEPROM error
(OLO)
SV
KEYPAD
PV
Running
System overload
(AdEr)
SV
KEYPAD
PV
Running
A/D converter error
(thr)
SV
KEYPAD
PV
Running
External fault
(SC)
SV
KEYPAD
PV
Running
Fuse open
(PAdF)
SV
KEYPAD
PV
Running
Keypad interruption
during copy
(LE1)
SV
KEYPAD
PV
Running
Under voltage
during operation
(OH)
SV
KEYPAD
PV
Running
Drive overheating
(OC)
SV
KEYPAD
PV
Running
Drive over current
(OL)
SV
KEYPAD
PV
Running
Motor overload
(GF)
SV
KEYPAD
PV
Running
Grounding fault
(OL1)
SV
KEYPAD
PV
Running
Drive overload
(OE)
SV
KEYPAD
PV
Running
Over voltage
(ntCF)
SV
KEYPAD
PV
Running
NTC thermistor sensor
fault
(no Fb)
SV
KEYPAD
PV
Running
PID feedback
signal error
(OP)
SV
KEYPAD
PV
Running
Over pressure

19
Warning Messages of Drive
Display
Description
Display
Description
(LE)
SV
KEYPAD
PV
Running
Power source
under voltage
(Err_00)
SV
KEYPAD
PV
Running
Err_00: Keypad cable
trip.(before connecting)
(bb)
SV
KEYPAD
PV
Running
Drive output
interruption
(Err_01)
SV
KEYPAD
PV
Running
Err_01: Keypad cable
trip.(connected)
(Fr)
SV
KEYPAD
PV
Running
Coast to stop
(Wr_F)
SV
KEYPAD
PV
Running
Different software
version inter-copy
(db)
SV
KEYPAD
PV
Running
Over voltage at
stop
(OP)
SV
KEYPAD
PV
Running
Over pressure
(dtF)
SV
KEYPAD
PV
Running
Direction command
error
(Ht)
SV
KEYPAD
PV
Running
Drive overheat
(PrEr)
SV
KEYPAD
PV
Running
Program fault
(CPy)
SV
KEYPAD
PV
Running
Parameter copy
complete
(Cot)
SV
KEYPAD
PV
Running
Communication
overtime
(CPyF)
SV
KEYPAD
PV
Running
Parameter copy error
Other manuals for RM6F5 series
2
This manual suits for next models
16
Table of contents
Other Rhymebus DC Drive manuals
Popular DC Drive manuals by other brands

Philips
Philips Xitanium LED Xtreme SR Design-in guide

Danfoss
Danfoss VACON 20 X manual

Vacon
Vacon 100 INDUSTRIAL Applications manual

INVT
INVT Goodrive350A Series Operation manual

Hubbell
Hubbell Universal Cable Reel-Direct Drive UE28 Installation and maintenance instructions

Rockwell Automation
Rockwell Automation 14C214 instruction manual