SAFETY AND EMC INSTRUCTIONS
Please carefully read the following user manual and the safety instructions before installing the unit or
operating the unit!
IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS!
1-1. TRANSPORTATION AND STORAGE
Please transport the UPS system only in the original packaging to protect against shock and impact.
The UPS must be stored in a ventilated and dry location.
1-2. PREPARATION
Condensation may occur if the UPS system is moved from a cold to a warm environment. The
UPS system must be absolutely dry before being installed. Please allow at least two hours for the
UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments or where it would be
exposed to direct sunlight or a nearby heater.
Do not block the ventilation holes on the UPS.
1-3. INSTALLATION
This UPS series is ONLY intended to be installed in an indoor temperature-controlled
environment that is free of conductive contaminants. This UPS series is not intended for use in a
computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing
Equipment ANSI/NFPA75.
Do not connect appliances or devices which would overload the UPS (e.g. big motor-type equipment) to
the UPS output.
Route cables in such a way that no one can step on or trip over them.
Do not block the air vents on the UPS. The UPS must be installed in a location with good ventilation.
Ensure enough space on each side for ventilation.
UPS has provided an earthed terminal, in the final installed system configuration,
equipotential earth bonding to the external UPS battery cabinets.
The UPS can be installed only by qualified service personnel.
An appropriate disconnect device for short-circuit protection should be provided in the
building wiring installation.
An integral single emergency switching device which prevents further supply to the load by the UPSin
any mode of operation should be provided in the building wiring installation.
Connect to the earth grounding before connecting to the building wiring terminal.
Installation and Wiring must be performed in accordance with the local electrical codes and regulations.