Rosslare MD-N32 Installation guide

MD-N32
Serial to Ethernet Gateway
Installation and Operating Guide

Copyright © 2014 by Rosslare. All rights reserved.
This manual and the information contained herein are proprietary to ROSSLARE
ENTERPRISES LIMITED and/or its related companies and/or subsidiaries’
(hereafter: "ROSSLARE"). Only ROSSLARE and its customers have the right to
use the information.
No part of this manual may be re-produced or transmitted in any form or by any
means, electronic or mechanical, for any purpose, without the express written
permission of ROSSLARE.
ROSSLARE owns patents and patent applications, trademarks, copyrights, or
other intellectual property rights covering the subject matter in this manual.
TEXTS, IMAGES, AND ILLUSTRATIONS INCLUDING THEIR ARRANGEMENT IN
THIS DOCUMENT ARE SUBJECT TO THE PROTECTION OF COPYRIGHT LAWS
AND OTHER LEGAL RIGHTS WORLDWIDE. THEIR USE, REPRODUCTION, AND
TRANSMITTAL TO THIRD PARTIES WITHOUT EXPRESS WRITTEN PERMISSION
MAY RESULT IN LEGAL PROCEEDINGS.
The furnishing of this manual to any party does not give that party or any third
party any license to these patents, trademarks, copyrights or other intellectual
property rights, except as expressly provided in any written agreement of
ROSSLARE.
ROSSLARE reserves the right to revise and change this document at any time,
without being obliged to announce such revisions or changes beforehand or
after the fact.

Table of Contents
MD-N32 Installation and Operation Manual iii
Table of Contents
1. Introduction ................................................................7
2. Specifications ..............................................................8
3. Connection and Configuration ...................................9
3.1 Hardware Requirements .......................................................... 9
3.2 Software Requirements ........................................................... 9
3.3 Connecting the MD-N32 ......................................................... 9
3.3.1Network Connection ....................................................................10
3.3.2 Serial Connection .........................................................................10
3.3.3 Power Connection ........................................................................11
3.3.4 Network Connection Diagram ......................................................11
3.4 Configuring the AS-IP01........................................................ 11
3.4.1 MAC Address Table ......................................................................12
3.4.2 Buttons.........................................................................................13
3.4.3 Network Section ...........................................................................13
3.4.4 Device Type ..................................................................................14
3.4.5 Serial Speed ..................................................................................14
3.4.6 Options Section ............................................................................14
3.4.7 Status ...........................................................................................15
3.5 Configuring the MD-N32....................................................... 15
A. Limited Warranty ......................................................18

List of Figures
iv MD-N32 Installation and Operation Manual
List of Figures
Figure 1: Front View of the MD-N32 ...............................................................10
Figure 2: Rear View of the MD-N32.................................................................10
Figure 3: TCP/IP Network Connection..............................................................11
Figure 4: AS-IP01 Configuration Utility GUI .....................................................12
Figure 5: AS-IP01 Configuration Utility – Search Button Results.......................16

List of Tables
MD-N32 Installation and Operation Manual v
List of Tables
Table 1: AS-IP01 Configuration Utility Buttons ................................................13
Table 2: Network Section Fields .......................................................................13

Notice and Disclaimer
vi MD-N32 Installation and Operation Manual
Notice and Disclaimer
This manual’s sole purpose is to assist installers and/or users in the safe and
efficient installation and usage of the system and/or product, and/or software
described herein.
BEFORE ATTEMPTING TO INSTALL AND/OR USE THE SYSTEM,THE INSTALLER AND THE
USER MUST READ THIS MANUAL AND BECOME FAMILIAR WITH ALL SAFETY
REQUIREMENTS AND OPERATING PROCEDURES.
The system must not be used for purposes other than those for which it
was designed.
The use of the software associated with the system and/or product, if
applicable, is subject to the terms of the license provided as part of the
purchase documents.
ROSSLARE exclusive warranty and liability is limited to the warranty and
liability statement provided in an appendix at the end of this document.
This manual describes the maximum configuration of the system with the
maximum number of functions, including future options. Therefore, not all
functions described in this manual may be available in the specific system
and/or product configuration you purchased.
Incorrect operation or installation, or failure of the user to effectively
maintain the system, relieves the manufacturer (and seller) from all or any
responsibility for consequent noncompliance, damage, or injury.
The text, images and graphics contained in the manual are for the purpose
of illustration and reference only.
All data contained herein subject to change without prior notice.
In no event shall manufacturer be liable for any special, direct, indirect,
incidental, consequential, exemplary or punitive damages (including,
without limitation, any and all damages from business interruption, loss of
profits or revenue, cost of capital or loss of use of any property or capital or
injury).
All graphics in this manual are for reference only, some deviation between
the image(s) and the actual product may occur.
All wiring diagrams are intended for reference only, the photograph or
graphic of the PCB(s) are intended for clearer illustration and
understanding of the product and may differ from the actual PCB(s).

Introduction
MD-N32 Installation and Operation Manual 7
1. Introduction
The MD-N32 is a Serial to Ethernet Gateway. One MD-N32 unit is
required (unless it is connected to a Rosslare software product that
supports direct TCP/IP operation, in which case the PC's internal LAN
card may be used).
A Serial to Ethernet Gateway allows connectivity for systems with
Legacy serial interface communication, such as RS-232 or RS-485,
with local networks and Internet.
The concept is to send and receive information between varied PC-
managed products (access control systems, guard control, security
systems, and so on) via a local network or Internet, thereby saving on
serial cabling installation, and enabling connections to remote sites
(most modern offices are already networked).
As a compact plug-in module, the MD-N32 can easily connect to
most products without modification. The module receives serial
communication, converts it to TCP/IP format, and sends it over the
LAN or Internet to the PC. From the other end, the module converts
communications sent from the PC over the network back to serial
format into the device.
All the setting and configuration is done using the AS-IP01
Configuration Utility PC software or by other Rosslare software that
supports a direct connection to hardware through TCP/IP (refer to the
software manuals of the specific products.) Once the module is
configured, the information is saved in a non-volatile memory within
the module.
The MD-N32 has two indication LEDS – the green LED indicates LAN
connectivity (Link) and the red LED indicates power supply operation
(Power).

Specifications
8 MD-N32 Installation and Operation Manual
2. Specifications
Electrical Characteristics
Input Power 10 to 16 VDC
Power Consumption Typical: 75 mA
Maximum: 115 mA
Transmission and Connectivity Characteristics
Hardware Protocols TCP, UDP, IP, ARP, ICMP, Ethernet MAC
Network Interface 10/100 Base-T Ethernet (Auto Detection) RJ-
45 jack for LAN connection
Serial Port D9 Male Connector RS-232
Data 1, 4, 6, 7, 8, 9 – N.C.
2 – Rx
3 – Tx
5 – GND Signal
MCU 32 bit micro-controller
Serial Line Format 8-N-1, 8-O-1, 8-E-1, 7-O-1, 7-E-1
Serial Flow Control None, XON/XOFF
Transmission Speed 1200 bps to ~115 Kbps
Environmental Characteristics
Operating Temp. Range 0°C to 70°C (32°F to 158°F)
Operating Humidity Range 10 to 90% (non-condensing)
Dimensions
Height x Width x Depth 110 x 63 x 39 mm (4.33 x 2.48 x 1.54 in.)
Weight 92 g (3.25 oz)

Connection and Configuration
MD-N32 Installation and Operation Manual 9
3. Connection and Configuration
3.1 Hardware Requirements
The following are the hardware units required to connect the MD-
N32 to the remote unit.
Standard LAN cables – RJ-45 plugs on both sides
12 VDC (400 mA) power adaptor, connected to the unit's DC
jack
MD-14 RS-485 to RS-232 Converter (for RS-485 units or RS-232
cable)
3.2 Software Requirements
The following are the requirements for the software installation of the
AS-IP01 Configuration Utility PC software.
Your PC configuration must be able to support one of the following
operating systems:
Windows®98/ME
Windows®NT/2000/XP
One of the above operating systems must be installed on your
computer.
The PC must have a LAN network connection to configure the MD-
N32. Both the PC and external unit must be connected to the same
LAN through a hub. It is also possible to use the MD-N32 over a
WAN, but this requires network router settings. (It is recommended
that system administrators be responsible for setting network routers.)
3.3 Connecting the MD-N32
Before setting, ask your network administrator for an IP address,
ports, and subnet masks for each MD-N32.

Connection and Configuration
10 MD-N32 Installation and Operation Manual
3.3.1 Network Connection
Connect each MD-N32 to the LAN using the LAN cables through the
RJ-45 connector on each unit of the MD-N32 (Figure 1).
Figure 1: Front View of the MD-N32
Make sure that the units are connected to the same LAN through a
hub.
3.3.2 Serial Connection
3.3.2.1 Unit Side
Connect the unit to the MD-N32 D9 jack using an RS-232 cable
(Figure 2), or use Rosslare's MD-14 when necessary (RS-485 to RS-232
Converter).
Figure 2: Rear View of the MD-N32
3.3.2.2 PC Side
If the MD-N32 is connected to the PC’s serial port, connect the MD-
N32's D9 jack to the PC using a cross-linked RS-232 cable.
D9-RS-232 Jack
Power Jack
RJ-45 Jack

Connection and Configuration
MD-N32 Installation and Operation Manual 11
3.3.3 Power Connection
Connect a 12 VDC (200 mA) power adaptor to each MD-N32 unit.
Ensure that the MD-N32 Power LED is on.
3.3.4 Network Connection Diagram
Figure 3 shows the network connection using an MD-N32 and PC
network card.
Figure 3: TCP/IP Network Connection
3.4 Configuring the AS-IP01
Once you have installed the AS-IP01 Configuration Utility according to
the installation's automated steps, the GUI appears as shown in
Figure 4.
TCP/IP
Network

Connection and Configuration
12 MD-N32 Installation and Operation Manual
Figure 4: AS-IP01 Configuration Utility GUI
The AS-IP01 Configuration Utility includes the following features:
A MAC address table in the left pane
Network, Modes, Device Type, Serial, and Options sections in the
right pane
Search, Apply, About, and Exit buttons in the bottom left pane
Each section of the AS-IP01 Configuration Utility and its parameters
are labeled in Figure 4. An explanation of each section and parameter
is provided in the following subsections.
3.4.1 MAC Address Table
3.4.1.1 MAC Address
When the MD-N32 units connected to the network are found, the
units are displayed as MAC addresses in the table.
The MAC number is a long 12-digit number that can be found
on a sticker located on the bottom side of the MD-N32 unit.

Connection and Configuration
MD-N32 Installation and Operation Manual 13
3.4.1.2 Version
The MD-N32 firmware version is displayed.
3.4.2 Buttons
Table 1 presents the buttons that appear in the AS-IP01 Configuration
Utility.
Table 1: AS-IP01 Configuration Utility Buttons
Field Description
Search Clicking Search retrieves all operating MD-N32 units
connected to the network. The results are displayed as MAC
addresses in the table.
Apply Clicking Apply changes the configuration of the selected
MD-N32 unit; the selected unit is initialized with the newly
entered values.
About Clicking About displays the details of the AS-IP01
Configuration Utility.
Exit Clicking Exit exits the software
3.4.3 Network Section
Once a unit is selected in the MAC Address table, the network
information of the selected unit is displayed in this section.
You can change the network configuration of the unit by inserting
and/or revising the information in the following parameters of the
Network section.
Table 2 presents the fields in the Network section.
Table 2: Network Section Fields
Field Description
Local IP and
Local Port The IP address of the unit
Subnet The subnet address of the unit
Gateway The gateway address
Server IP and
Server Port
Defines the server's IP and port when the unit is set to
operate in Client mode

Connection and Configuration
14 MD-N32 Installation and Operation Manual
Field Description
Modes The network mode of operation:
•Client mode – Unit operates in Client mode and
attempts to connect to the specified server's IP address
and port
•Server mode – Unit operates in Server mode and listens
in on the specified Listen port and awaits client
connection
In Client mode, the inactivity time should be set above 30
seconds (the default is 45 seconds). In Server mode, the
inactivity timer of the server is set to 0 by default. The client
closes and restarts the socket every 45 seconds. When the
server is reset, the link between the client and the server is
resumed after 45 seconds. While data transfer may fail when
the socket is restarted, the transfer should be successful the
next time the socket is restarted.
Data transfer does not fail as long as “keep alive” data is
maintained in the TCP socket.
A socket connection should be in place when the data is sent
from a serial device. If not, a connection may be initiated to the
server IP and port, and the data may then be resent.
3.4.4 Device Type
This section contains the name of the product (MD-N32).
3.4.5 Serial Speed
This section lists the product’s speed, which can be configured as
desired.
Click Apply for any changes in the device type or serial speed to take
effect.
3.4.6 Options Section
The Options section includes the following parameters:

Connection and Configuration
MD-N32 Installation and Operation Manual 15
3.4.6.1 Inactivity Time
The inactivity time is intended for use with the TCP channel when a
link is established. If the inactivity timer has expired, the channel is
closed to data transfer. Data transfer resumes once the MD-N32 has
been set to the client. The inactivity timer range may be 0 (the
default, TCP channel is always ON) or from 30 to 65,535 seconds.
3.4.6.2 Data Packing
This options allows you to designate conditions for Serial to Ethernet
data transmission. The two conditions are Time and Size, with Time
packing as the default.
Time – Designates a time frame for periodic transmission,
between 0 and 10,000 milliseconds.
Size – Select the checkbox to enable the size packing feature, and
then designate the data size for transmission based on data
packet size, between 10 and 255 bytes.
After changes are made, click Apply for the changes to take effect.
3.4.7 Status
The Status describes the status of the selected MAC (for example,
Configured).
3.5 Configuring the MD-N32
To configure the MD-N32:
1. Run the AS-IP01 Configuration Utility PC software.
2. Click Search.
The
Processing
window appears.
3. When the search is complete, ensure that the correct MD-N32
MAC addresses appear in the MAC Address table (Figure 5).

Connection and Configuration
16 MD-N32 Installation and Operation Manual
Figure 5: AS-IP01 Configuration Utility – Search Button Results
It is not possible to run two sets of AS-IP01 simultaneously on
the same PC or on the same network. It is also not
recommended that AS-IP01 be run simultaneously with some
software applications either based on Microsoft®Visual Basic 6
or featuring TCP/IP support, since the AS-IP01 may malfunction.
For example, it is not recommended to run AS-
IP01 on the same
PC and at the same time as Rosslare’s AxTraxNG™ software.
4. Select the MAC Address of the MD-N32 unit that is connected to
the applicable networked unit.
5. In the Network section, in the Local IP and Local Port text boxes,
enter the first IP Address and port number (1000 recommended)
supplied by your network administrator.
6. In the Subnet text box, enter the supplied subnet.
7. In the Server IP text box, enter the second IP address and port
number (1000 recommended).
8. In Modes, select either Client or Server, as required.

Connection and Configuration
MD-N32 Installation and Operation Manual 17
9. Click Apply to send the configuration to the unit.
10. Run the applicable application software for the networked unit.

Limited Warranty
18 MD-N32 Installation and Operation Manual
A. Limited Warranty
The full ROSSLARE Limited Warranty Statement is available in the
Quick Links section on the ROSSLARE website at
www.rosslaresecurity.com.
Rosslare considers any use of this product as agreement to the
Warranty Terms even if you do not review them.

MD-N32
Asia Pacific, Middle
East, Africa
Rosslare Enterprises Ltd.
Kowloon Bay, Hong Kong
Tel: +852 2795-5630
Fax: +852 2795-1508
support.apac@rosslaresecurity.com
United States and
Canada
Rosslare Security Products, Inc.
Southlake, TX, USA
Toll Free: +1-866-632-1101
Local: +1-817-305-0006
Fax: +1-817-305-0069
support.na@rosslaresecurity.com
Europe
Rosslare Israel Ltd.
Rosh HaAyin, Israel
Tel: +972 3 938-6838
Fax: +972 3 938-6830
support.eu@rosslaresecurity.com
Latin America
Rosslare Latin America
Buenos Aires, Argentina
Tel: +54-11-4001-3104
support.la@rosslaresecurity.com
China
Rosslare Electronics (Shenzhen) Ltd.
Shenzhen, China
Tel: +86 755 8610 6842
Fax: +86 755 8610 6101
support.cn@rosslaresecurity.com
India
Rosslare Electronics India Pvt Ltd.
Tel/Fax: +91 20 40147830
Mobile: +91 9975768824
sales.in@rosslaresecurity.com
0706-0960055+02
Other manuals for MD-N32
1
Table of contents
Other Rosslare Gateway manuals

Rosslare
Rosslare AY-B1663 User manual

Rosslare
Rosslare AY-Q64 Assembly instructions

Rosslare
Rosslare AC-525 User manual

Rosslare
Rosslare MD-W11 User manual

Rosslare
Rosslare AYC-W6500 User manual

Rosslare
Rosslare AY-Q65 Assembly instructions

Rosslare
Rosslare MD-N32 Troubleshooting guide

Rosslare
Rosslare AC-020 User manual

Rosslare
Rosslare AC-B3x Assembly instructions

Rosslare
Rosslare AY-M26 Manual